# Rack Management And Management Policies

## 3.1  Introduction

Rack management is the process of using tools and software to organize and manage the infrastructure components and racks in a data center.

A DGX GB200 system can be thought of as a “disaggregated supercomputer in a rack”. The cluster administrator can manage the individual nodes in the traditional way, but BCM rack management features introduced in BCM version 11 allow the GB200 nodes to be managed more conveniently as unified NVL domains.

## 3.2  Basic Rack Management

Basic rack management is covered in [section 3.16 of the *Administrator Manual*](/admin/configuring#316-managing-and-configuring-a-rack). The commands in `rack` mode that are discussed there include:

* The `list` command can give useful information on how the devices in racks are organized, if the attributes of racks in `rack` mode have been set up in a meaningful way. An example is given in section [4.9.1](/nvidia-mission-control/powershelf#491-the-list-command).

* The `display` command is useful for seeing the position of where devices are located in the rack, if the cluster administrator has recorded the device positions in the rack. An example is given in section [4.9.3](/nvidia-mission-control/powershelf#493-the-display-command).

* The `addrackposition` command ([here](/admin/configuring#31622-assigning-devices-to-a-rack-using-cmsh)) was introduced in BCM version 11. It allows rack positions in a cluster to be filled more easily than with a looping script.

* The `rackoverview` command ([here](/admin/configuring#rackoverview)) was also introduced in BCM version 11. It allows rack positions in a cluster to be overviewed conveniently. It shows information about the types of entities in a rack. It also then lists some more detailed information about some of the entity types.

For a DGX GB200 platform that has been configured, the output of the `rackoverview` command looks similar to the following for a specified rack (here it is a rack named `b05` that has 18 nodes, 9 switches, and 8 power shelves):

**Example**

```bash
[a03-p1-head-01->rack]% rackoverview b05
Type              Up               Down             Closed           Total
----------------- ---------------- ---------------- ---------------- -----------
Nodes             18               0                0                18
DPU nodes         0                0                0                0
Managed switches  0                0                0                0
NVLink switches   9                0                0                9
Power shelves     8                0                0                8
Devices           0                0                0                0
Cores             2,592            -                -                2,592
GPUs              72               -                -                72

Name                        Value
--------------------------- -----------------
User CPU                    0.03%
System CPU                  0.07%
Idle CPU                    99.9%
Other CPU                   0.0%
Memory used                 1.09 TiB (3.75%)
Memory unused               28.4 TiB (97.9%)
Memory total                29.0 TiB
Total GPU utilization       0 W
Total GPU power usage       11.6 KW
Total GPU NVlink bandwidth  0 W
Average GPU temperature     30.9028 C
Total CPU power usage       1.60 KW
Average CPU temperature     48.6361 C

Node               GPU      Utilization  Temperature  Power usage  Memory used...
------------------ -------- ------------ ------------ ------------ -----------...
b05-p1-dgx-05-c01  gpu0     0.0%         30 C         167.184 W    0 B        ...
b05-p1-dgx-05-c01  gpu1     0.0%         31 C         154.726 W    0 B        ...
b05-p1-dgx-05-c01  gpu2     0.0%         32 C         154.894 W    0 B        ...
b05-p1-dgx-05-c01  gpu3     0.0%         31 C         170.649 W    0 B        ...
b05-p1-dgx-05-c02  gpu0     0.0%         31 C         162.994 W    0 B        ...
b05-p1-dgx-05-c02  gpu1     0.0%         31 C         151.328 W    0 B        ...
b05-p1-dgx-05-c02  gpu2     0.0%         31 C         151.149 W    0 B        ...
b05-p1-dgx-05-c02  gpu3     0.0%         31 C         170.537 W    0 B        ...
b05-p1-dgx-05-c03  gpu0     0.0%         31 C         166.664 W    0 B        ...
b05-p1-dgx-05-c03  gpu1     0.0%         31 C         154.725 W    0 B        ...
b05-p1-dgx-05-c03  gpu2     0.0%         31 C         151.047 W    0 B        ...
b05-p1-dgx-05-c03  gpu3     0.0%         31 C         170.125 W    0 B        ...
b05-p1-dgx-05-c04  gpu0     0.0%         31 C         170.642 W    0 B        ...
b05-p1-dgx-05-c04  gpu1     0.0%         31 C         155.034 W    0 B        ...
b05-p1-dgx-05-c04  gpu2     0.0%         31 C         152.078 W    0 B        ...
b05-p1-dgx-05-c04  gpu3     0.0%         31 C         166.551 W    0 B        ...
b05-p1-dgx-05-c05  gpu0     0.0%         31 C         170.516 W    0 B        ...
b05-p1-dgx-05-c05  gpu1     0.0%         31 C         158.7 W      0 B        ...
b05-p1-dgx-05-c05  gpu2     0.0%         31 C         158.7 W      0 B        ...
b05-p1-dgx-05-c05  gpu3     0.0%         31 C         174.413 W    0 B        ...
b05-p1-dgx-05-c06  gpu0     0.0%         30 C         166.44 W     0 B        ...
b05-p1-dgx-05-c06  gpu1     0.0%         30 C         154.628 W    0 B        ...
b05-p1-dgx-05-c06  gpu2     0.0%         31 C         154.865 W    0 B        ...
b05-p1-dgx-05-c06  gpu3     0.0%         31 C         170.423 W    0 B        ...
b05-p1-dgx-05-c07  gpu0     0.0%         31 C         164.078 W    0 B        ...
b05-p1-dgx-05-c07  gpu1     0.0%         31 C         158.303 W    0 B        ...
b05-p1-dgx-05-c07  gpu2     0.0%         31 C         150.958 W    0 B        ...
b05-p1-dgx-05-c07  gpu3     0.0%         31 C         170.537 W    0 B        ...
b05-p1-dgx-05-c08  gpu0     0.0%         31 C         166.661 W    0 B        ...
b05-p1-dgx-05-c08  gpu1     0.0%         31 C         155.875 W    0 B        ...
b05-p1-dgx-05-c08  gpu2     0.0%         31 C         154.726 W    0 B        ...
b05-p1-dgx-05-c08  gpu3     0.0%         32 C         170.311 W    0 B        ...
b05-p1-dgx-05-c09  gpu0     0.0%         31 C         166.331 W    0 B        ...
b05-p1-dgx-05-c09  gpu1     0.0%         31 C         155.469 W    0 B        ...
b05-p1-dgx-05-c09  gpu2     0.0%         30 C         154.751 W    0 B        ...
b05-p1-dgx-05-c09  gpu3     0.0%         32 C         175.429 W    0 B        ...
b05-p1-dgx-05-c10  gpu0     0.0%         30 C         174.181 W    0 B        ...
b05-p1-dgx-05-c10  gpu1     0.0%         31 C         158.523 W    0 B        ...
b05-p1-dgx-05-c10  gpu2     0.0%         31 C         152.808 W    0 B        ...
b05-p1-dgx-05-c10  gpu3     0.0%         31 C         166.551 W    0 B        ...
b05-p1-dgx-05-c11  gpu0     0.0%         30 C         166.704 W    0 B        ...
b05-p1-dgx-05-c11  gpu1     0.0%         31 C         154.726 W    0 B        ...
b05-p1-dgx-05-c11  gpu2     0.0%         31 C         155.034 W    0 B        ...
b05-p1-dgx-05-c11  gpu3     0.0%         30 C         170.679 W    0 B        ...
b05-p1-dgx-05-c12  gpu0     0.0%         31 C         170.424 W    0 B        ...
b05-p1-dgx-05-c12  gpu1     0.0%         31 C         155.601 W    0 B        ...
b05-p1-dgx-05-c12  gpu2     0.0%         31 C         150.892 W    0 B        ...
b05-p1-dgx-05-c12  gpu3     0.0%         31 C         166.806 W    0 B        ...
b05-p1-dgx-05-c13  gpu0     0.0%         31 C         166.766 W    0 B        ...
b05-p1-dgx-05-c13  gpu1     0.0%         30 C         151.894 W    0 B        ...
b05-p1-dgx-05-c13  gpu2     0.0%         31 C         151.22 W     0 B        ...
b05-p1-dgx-05-c13  gpu3     0.0%         31 C         170.205 W    0 B        ...
b05-p1-dgx-05-c14  gpu0     0.0%         31 C         172.778 W    0 B        ...
b05-p1-dgx-05-c14  gpu1     0.0%         31 C         162.152 W    0 B        ...
b05-p1-dgx-05-c14  gpu2     0.0%         31 C         150.857 W    0 B        ...
b05-p1-dgx-05-c14  gpu3     0.0%         31 C         166.33 W     0 B        ...
b05-p1-dgx-05-c15  gpu0     0.0%         31 C         166.518 W    0 B        ...
b05-p1-dgx-05-c15  gpu1     0.0%         31 C         154.729 W    0 B        ...
b05-p1-dgx-05-c15  gpu2     0.0%         31 C         154.1 W      0 B        ...
b05-p1-dgx-05-c15  gpu3     0.0%         31 C         170.537 W    0 B        ...
b05-p1-dgx-05-c16  gpu0     0.0%         30 C         174.067 W    0 B        ...
b05-p1-dgx-05-c16  gpu1     0.0%         30 C         158.385 W    0 B        ...
b05-p1-dgx-05-c16  gpu2     0.0%         31 C         151.157 W    0 B        ...
b05-p1-dgx-05-c16  gpu3     0.0%         31 C         166.77 W     0 B        ...
b05-p1-dgx-05-c17  gpu0     0.0%         31 C         166.161 W    0 B        ...
b05-p1-dgx-05-c17  gpu1     0.0%         31 C         158.62 W     0 B        ...
b05-p1-dgx-05-c17  gpu2     0.0%         31 C         151.058 W    0 B        ...
b05-p1-dgx-05-c17  gpu3     0.0%         31 C         169.704 W    0 B        ...
b05-p1-dgx-05-c18  gpu0     0.0%         31 C         166.441 W    0 B        ...
b05-p1-dgx-05-c18  gpu1     0.0%         31 C         155.164 W    0 B        ...
b05-p1-dgx-05-c18  gpu2     0.0%         31 C         150.758 W    0 B        ...
b05-p1-dgx-05-c18  gpu3     0.0%         31 C         169.752 W    0 B        ...

Switch          Utilization  Temperature Power usage  Fan speed Links active L...
--------------- ------------ ----------- ------------ --------- ------------ -...
B05-P1-NVSW-01  30.2%        0 C         0 W          0 RPM     0            0
B05-P1-NVSW-02  27.5%        0 C         0 W          0 RPM     0            0
B05-P1-NVSW-03  0.0%         0 C         0 W          0 RPM     0            0
B05-P1-NVSW-04  27.6%        0 C         0 W          0 RPM     0            0
B05-P1-NVSW-05  27.6%        0 C         0 W          0 RPM     0            0
B05-P1-NVSW-06  27.5%        0 C         0 W          0 RPM     0            0
B05-P1-NVSW-07  27.5%        0 C         0 W          0 RPM     0            0
B05-P1-NVSW-08  27.5%        0 C         0 W          0 RPM     0            0
B05-P1-NVSW-09  27.6%        0 C         0 W          0 RPM     0            0

Power shelf    Input power  Output power Temperature  Fan speed Active PSU  To...
-------------- ------------ ------------ ------------ --------- ----------- --...
B05-P1-PWR-01  3.7 KW       3.5 KW       43.3333 C    6.7 KRPM  6           6
B05-P1-PWR-02  3.11 KW      2.95 KW      42.4 C       6.7 KRPM  6           6
B05-P1-PWR-03  3.7 KW       3.5 KW       44.1667 C    6.7 KRPM  6           6
B05-P1-PWR-04  3.8 KW       3.6 KW       44 C         6.7 KRPM  6           6
B05-P1-PWR-05  3.6 KW       3.4 KW       45.5 C       6.7 KRPM  6           6
B05-P1-PWR-06  3.8 KW       3.6 KW       47.1667 C    6.7 KRPM  6           6
B05-P1-PWR-07  3.5 KW       3.4 KW       46 C         6.7 KRPM  6           6
B05-P1-PWR-08  3.6 KW       3.5 KW       47 C         6.7 KRPM  6           6
[a03-p1-head-01->rack]%
```

## 3.3  Introduction To Advanced Features In Rack Management

Over time, clusters have become more powerful and their cooling requirements have become more demanding. Liquid cooling technology has therefore become more common over time.

The monitoring associated with liquid cooling has also developed. Monitoring of the electrical supply, fans, component temperatures, and coolant values such as flow and pressure has become popular. Coolant monitoring in BCM includes an ability to detect leaks and then take actions. An NVIDIA-conforming BMS (section [3.3.1](#331-how-bms-and-bcm-work-together)) provides some of these monitoring and managing features, including features associated with liquid cooling and electrical isolation.

The cluster administrator can monitor these advanced features using mostly `rack` mode commands (section [3.3.2.1](#3321-the-electricaloverview-command)).

### 3.3.1  How BMS And BCM Work Together

A Building Management System (BMS) is a software used to manage IT assets in a building. A BMS software that can integrate with BCM, is known as a *conforming BMS*. The conformance is to a reference design for data center planning ([NVIDIA Controls and Monitoring Reference Design](https://apps.nvidia.com/pid/contentlibraries/detail?id=1118640)), available to some NVIDIA product users.

Since BCM version 11, BCM integrates with a conforming BMS for leak detection and control in the data center (DC). The [*NVIDIA Mission Control Software Installation Guide*](https://docs.nvidia.com/mission-control/docs/nmc-software-installation-guide/2.0.0/) describes the implementation of the integration between BCM and a conforming BMS at:

[https://docs.nvidia.com/mission-control/docs/nmc-software-installation-guide/2.0.0/integration-of-bms-with-bcm.html](https://docs.nvidia.com/mission-control/docs/nmc-software-installation-guide/2.0.0/integration-of-bms-with-bcm.html)

The guide is also meant to serve as a guide to NVIDIA customers who may use different BMS solutions.

BCM communicates with a conforming BMS. Together they monitor the DC. The integration works with DGX GB200 systems that are liquid-cooled, as well as other systems.

In a DC, a conforming BMS is able to detect most of the detected leak-related events. The remaining detected leak-related events, from the in-tray BMCs (compute tray and switch tray), are dealt with by BCM.

BCM uses the MQTT protocol for two-way communication with the conforming BMS, using a BCM service `cm-mqtt`.

The BMS sends BCM information about the inventory of the DC, and about the leak-related events it knows about (non-tray events). MQTT topics are created, and structured in a way that BCM can parse.

BCM in turn sends the BMS instructions on liquid management or power management, according to defined policies on events such as leaks or power outages (section [4.8](/nvidia-mission-control/powershelf#48-power-shelf-circuit-monitoring)).

#### 3.3.1.1  Building Management System Configuration

BMS integration can be configured in BCM in partition mode in `cmsh` and Base View.

The type of BMS can be configured in `partition` mode:

**Example**

```bash
root@basecm11:~# cmsh
[basecm11]% partition
[basecm11->partition[base]]% set bms nvidia-conforming bms; commit
```

In the preceding example, the BMS is set to an NVIDIA-conforming BMS. The possible types of BMS configuration can be:

* `NVIDIA-conforming BMS`

* `pipe`

* `file`

* `URL`

If `bms` is set to the URL of a BMS server, for example `http://bmserver/path`, then credentials for it can then be set as follows:

**Example**

```bash
root@basecm11:~# cmsh
[basecm11]% partition
[basecm11->partition[base]]% set bms url
[basecm11->partition*[base*]]% set bmscertificate <BMS certificate>
[basecm11->partition*[base*]]% set bmspath http://bmsserver/path
[basecm11->partition*[base*]]% set bmsprivatekey <BMS private key>
[basecm11->partition*[base*]]% commit
```

In the following example, an `mqtt` role is assigned in the `mqtt` configuration overlay. The overlay specifies where the `cm-mqtt` service should run. In this case it runs on all the head nodes:

**Example**

```bash
root@basecm11:~# cmsh
[basecm11->partition[base]]% configurationoverlay
[basecm11->configurationoverlay]% add mqtt
[basecm11->configurationoverlay*[mqtt*]]% set allheadnodes yes
```

Within the role assignment, the administrator specifies the hostname or IP address of where the BMS server runs, and where the `cm-mqtt` service pulls data from:

```bash
[basecm11->configurationoverlay*[mqtt*]]% roles
[basecm11->configurationoverlay*[mqtt*]->roles]% assign mqtt
[basecm11->configurationoverlay*[mqtt*]->roles*[mqtt*]]% show
Parameter                        Value
-------------------------------- ----------------------------------------------------------
Name                             mqtt
Revision
Type                             MQTTRole
Add services                     yes
Servers                          <0 in submode>
CA certificate path              /cm/local/apps/cmd/pythoncm/lib/python3.12/site-packages/\
                                 pythoncm/etc/cacert.pem
Private key path                 /cm/local/apps/cmd/cm-mqtt/etc/mqtt.key
Certificate path                 /cm/local/apps/cmd/cm-mqtt/etc/mqtt.pem
Write named pipe path            /var/spool/cmd/mqtt.pipe
[basecm11->configurationoverlay*[mqtt*]->roles*[mqtt*]]% servers
[basecm11->configurationoverlay*[mqtt*]->roles*[mqtt*]->servers]% list
Server (key)     Port       Disabled
---------------- ---------- ----------
[basecm11->configurationoverlay*[mqtt*]->roles*[mqtt*]->servers]% add mqhost
[basecm11->configurationoverlay*[mqtt*]->roles*[mqtt*]->servers*[mqhost*]]% show
Parameter                        Value
-------------------------------- ------------------------------------------------
Revision
Server                           mqhost
Port                             1883
Topic                            BCM/#
Disabled                         no
Username
Password                         < not set >
Transport                        tcp
Protocol                         v3.1.1
Certificate required             yes
CA certificate
Certificate
Private key
[basecm11->configurationoverlay*[mqtt*]->roles*[mqtt*]->servers*[mqhost*]]% set certificate
...
```

A username, password, and service certificate can be set. These allow BCM to communicate with the BMS securely:

```bash
[basecm11->configurationoverlay[mqtt]->roles[mqtt]->servers[mqhost]]% show
Parameter                        Value
-------------------------------- ------------------------------------------------
Revision
Server                           mqhost
Port                             1883
Topic                            BCM/#
Disabled                         no
Username                         cronus
Password                         ********
Transport                        tcp
Protocol                         v3.1.1
Certificate required             yes
CA certificate
Certificate
Private key
[basecm11->configurationoverlay[mqtt]->roles[mqtt]->servers[mqhost]]%
```

If the cluster manager has correctly established communication with the BMS, then the status of the BMS (metrics for power circuit, CDUs, electrical, and liquid cooling) can be seen from within `cmsh` (section [4.8](/nvidia-mission-control/powershelf#48-power-shelf-circuit-monitoring)).

**Example**

```bash
[basecm11]% powercircuit overview
Power circuit  Power     Current     Current limit   Current phase 1  Current phase 2 ...
-------------- --------- ----------- --------------- ---------------- ----------------...
RPP-B12-3      14.0 KW   26.1118 A   0 A             17.7822 A        26.1118 A       ...
RPP-B14-3      15.3 KW   29.6178 A   0 A             17.7419 A        29.6178 A       ...
RPP-B21-5      7.5 KW    11.2255 A   0 A             10.4872 A        10.5412 A       ...
...
```

### 3.3.2  Commands For Monitoring Advanced Features In Rack Management

#### 3.3.2.1  The `electricaloverview` Command

The `electricaloverview` command within `rack` mode gives a convenient overview of the electrical supply to the cluster.

The power used and the power budget of a specified rack (`B05` in the following example) can be seen:

**Example**

```bash
[basecm11->rack[B05]]% electricaloverview
Rack             Power used       Power budget     Isolation status
---------------- ---------------- ---------------- ----------------
B05              28.5 kW          135 kW           0
```

If no rack is specified, then the command displays the information for all racks.

#### 3.3.2.2  The `liquidcoolingoverview` Command

The `liquidcoolingoverview` command can be run from within `rack` mode, and conveniently displays coolant metrics:

```bash
[basecm11->rack]% liquidcoolingoverview a05
      Supply        Return       Flow        Differential  Isolation
Rack  temperature   temperature  rate        pressure      status
----- ------------- -----------  ----------- ------------- -----------
A05   26.03 C       30.78 C      70.938 LPM  31 KPa        0
```

If no rack is specified, then the command displays the information for all racks.

#### 3.3.2.3  The `leakdetectionoverview` Command

The `leakdetectionoverview` command within `rack` mode gives a convenient overview about sensor readings related to leak detection in BCM and the electrical isolation status.

The output from the command applied to a specific rack looks similar to the following:

```bash
[basecm11->rack]% leakdetectionoverview a05
                              Liquid    Liquid              Electrical Electrical
              Leak     Leak   isolation isolation Liquid    isolation  isolation  Electrical
     Leak     tray     sensor request   request   isolation request    request    isolation
Rack detected detected fault  (BCM)     (BMS)     status    (BCM)      (BMS)      status
---- -------- -------- ------ --------- --------- --------- ---------- ---------  ----------
A05  0        0        0      0         0         0         0          0          0
[basecm11->rack]%

```

If no rack is specified, then the command displays the information for all racks.

#### 3.3.2.4  Leak Detection Within `device` Mode: The `leakinfo` Command

The `leakinfo` command, is related to leakage detection, but it is not a `rack` mode command. It is a `device` mode command. It is noted in this section for completeness. It can be run at `device` mode level to list all leaks detected in the cluster.

Typically, and ideally, running the command shows something similar to:

```bash
[basecm11->device]% leakinfo
Hostname         Timestamp Severity  Info
---------------- --------- --------- ----------------
[basecm11->device]%
```

If there are issues on the devices, then the output may look similar to:

```bash
[basecm11->device]% leakinfo
Hostname        Timestamp Severity  Info
--------------- --------- --------- --------------------------------------------
a05-dgx-01-c09  15:09:23  large     The state of resource `Chassis_0_LeakDete...
a07-dgx-03-c16  15:38:48  large     The state of resource `Chassis_0_LeakDete...
b05-dgx-05-c08  09:11:06  large     The state of resource `Chassis_0_LeakDete...
b05-dgx-05-c10  09:11:05  large     The state of resource `Chassis_0_LeakDete...
b06-dgx-06-c17  11:49:30  large     The state of resource `Chassis_0_LeakDete...
[basecm11->device]%
```

Running `help leakinfo` lists further command options.

#### 3.3.2.5  Leak Detection Within `device` Mode: The `latestmonitoringdata` Command For NVL8 Clusters

The `latestmonitoringdata` command ([section 10.6.3 of the *Administrator Manual*](/admin/monitoring#1063-the-latest-data-and-counter-valuesthe-latestdata-and-latestmetriccounters-commands)) is also a `device` mode command rather than a `rack` mode command. It, too, is given an extra mention in this leak detection section, because, for NVL8 hardware, it can be used to inspect raw Redfish leak detector states.

For example, on NVL8 hardware, in `device` mode, filtered by leak, it might display something like:

```bash
[basecm11->device[a10-u25-p01-fractal-002]]% latestmonitoringdata | grep -i leak
RF_LD_LeakDetection                          LeakDetector/Status   OK       2m 2s
RF_LeakDetector  HGX_Chassis_0_LeakDetector_0  LeakDetector/Moisture OK     2m 2s
RF_LeakDetector  HGX_Chassis_0_LeakDetector_1  LeakDetector/Moisture OK     2m 2s
RF_LeakDetector  LeakDetector_GB_0             LeakDetector/Moisture Degraded 2m 2s
RF_LeakDetector  LeakDetector_GB_1             LeakDetector/Moisture Degraded 2m 2s
RF_LeakDetector  LeakDetector_SWB_0            LeakDetector/Moisture Degraded 2m 2s
```

The output includes:

* `RF_LD_LeakDetection`: The status of the dedicated hardware leak detection system on the device (`LeakDetector/Status`). This reflects whether the leak detection hardware itself has reported a leak event, and is independent of the individual moisture sensor readings, described next.

* `RF_LeakDetector`: Per-detector Redfish moisture readings (`LeakDetector/Moisture`). A `Degraded` status indicates that the sensor has detected elevated moisture, which may or may not have crossed the threshold to trigger a leak event in `RF_LD_LeakDetection`. The parameter column identifies the detector location:

  * `HGX_Chassis_0_LeakDetector_N`: detectors on the HGX chassis

  * `LeakDetector_GB_N`: detectors on the Grace-Blackwell compute modules

  * `LeakDetector_SWB_N`: detectors on the NVLink switchboard

A status of `OK` indicates no moisture is detected. A status of `Degraded` indicates that the detector has detected moisture. The `leakinfo` command (section [3.3.2.4](#3324-leak-detection-within-device-mode-the-leakinfo-command)) and `leakdetectionoverview` command (section [3.3.2.3](#3323-the-leakdetectionoverview-command)) provide higher-level views of cluster-wide leak status and isolation state.

#### 3.3.2.6  The `isolationrequestinfo` Command

If a leak is detected, then BCM receives the report. BCM then:

* powers off the node that is leaking

* powers off the rack if multiple nodes are leaking

* isolates the rack to prevent other nodes suffering the same fate

Isolation means that power no longer runs through the leaking racks.

The isolation status of a rack can be viewed with the `isolationrequestinfo` command, which normally shows something similar to:

**Example**

```bash
[basecm11->rack]% isolationrequestinfo
Rack             Timestamp    Kind         Value    Info
---------------- ------------ ------------ -------- ----------------
[basecm11->rack]%
```

During a leakage event, the output may show something similar to:

**Example**

```bash
[basecm11->rack]% isolationrequestinfo
Rack  Timestamp Kind Value Info
----- --------- ---- ----- ----------------------------
B05   03:40:01       4     Default building policy/Rack
[basecm11->rack]%
```

### 3.3.3  Managing Leaks With `rules` In `leakactionpolicies`

The cluster administrator has the freedom to construct actions based on triggers based on leak detection measurables. While that is powerful, that can be quite labor-intensive for cluster administrators.

BCM provides a simpler way to deal with leaks, based on leak action policies. Leak action policies are a collection of rules that carry out actions to be followed when leaks are detected. Racks play an important part in these policies and rules.

The policies use predefined scopes, or groupings. The names of these groupings are rules. The groupings are listed next, in order from largest to smallest, along with their associated descriptions:

* `Building`: a building is made up of rooms

* `Room`: A room has rows of racks in it.

* `Row`: A row of racks has individual racks in it.

* `Rack`: An individual rack has devices in it.

* `Device`: The smallest possible grouping

The policies can be listed in the `leakactionpolicies` submode, under `partition` mode.

**Example**

```bash
[basecm11->partition[base]->leakactionpolicies]% list
Name (key)               Rules
------------------------ ----------------------------------
Default building policy  Building, Device, Rack, Room, Row
Default device policy    Device
Default rack policy      Device, Rack
Default room policy      Device, Rack, Room, Row
Default row policy       Device, Rack, Row
```

The rules used by each policy are also shown, under the `Rules` column in the preceding example.

Each rule in a policy is a copy of a template. By default the rules per policy are identical.

Just the rules used by a specific policy can also be viewed:

**Example**

```bash
[basecm11->partition[base]->leakactionpolicies]% use default building policy
[basecm11->partition[base]->leakactionpolicies[Default building policy]]% show
Parameter                        Value
-------------------------------- ------------------------------------------------
Name                             Default building policy
Revision
Rules                            Building, Device, Rack, Room, Row
```

Within a policy, the value of the settings for these rules can be listed:

**Example**

```bash
[basecm11->...leakactionpolicies[Default building policy]->rules]% list
                      Power  Power    Electrical Liquid     Minimal Maximal
Name (key)  Scope     off    off rack isolation  isolation  devices devices
----------- --------- ------ -------- ---------- ---------- ------- -------
Building    building  yes    yes      no         no         11      100000
Device      device    yes    no       no         no
Rack        rack      yes    yes      yes        yes        3       100
Room        room      yes    yes      no         no         7       100000
Row         row       yes    yes      no         no         5       100
```

The rules for each policy can be modified independently for each policy, so that, for example the `Rack` rule values may differ between `Default row policy` and `Default building policy`. However, a sensible cluster administrator is not expected to carry out such a modification.

Another way of phrasing this is: The values of the rules can be changed from the defaults. In that case, a sensible administrator is expected to keep the values synchronized across the rules in the leak action policies.

In the preceding example:

If the minimal devices criterion is met for leaking for each rule in a policy, then the values for the column header are applied to the rules of that policy.

So, for the policy rules in the preceding example, when leaking is detected:

* If only one or two devices are detected as leaking, then only the devices involved are powered off.

* If, in one rack, more than 3 devices, but less than 5 devices, are detected as leaking, then in addition to the device rules being applied, the entire rack is powered off. Isolation is also carried out for the electrical power and liquid coolant.

* If more devices meet the conditions, so a larger scope is affected by leaking, then the rules for the larger scope are also applied.

The rules for a specific policy can be removed. The `row` rule for `Default building policy` can be removed with, for example:

```bash
[basecm11->partition[base]->leakactionpolicies[Default building policy]]% rules
[basecm11->...leakactionpolicies[Default building policy]->rules]% remove <TAB><TAB>
building  device    rack      room      row
[basecm11->...leakactionpolicies[Default building policy]->rules]% remove row; commit
```

#### 3.3.3.1  Custom Rules For `leakactionpolicies`

The names for the rules (`Device`, `Rack`, `Row` ...) are really just default labels, and a sensible cluster administrator is expected to have the description associated with the name match the physical reality. Creating a custom rule may help with this.

Custom rules can be added by the cluster administrator, by first adding another policy:

```bash
[basecm11->partition[base]->leakactionpolicies[Default building policy]]% add mypolicy
[basecm11->partition*[base*]->leakactionpolicies*[mypolicy*]]% list
Name (key)               Rules
------------------------ ----------------------------------
Default building policy  Building, Device, Rack, Room, Row
Default device policy    Device
Default rack policy      Device, Rack
Default room policy      Device, Rack, Room, Row
Default row policy       Device, Rack, Row
mypolicy                 none
[basecm11->partition*[base*]->leakactionpolicies*[mypolicy*]]% show
Parameter                        Value
-------------------------------- ------------------------------------------------
Name                             mypolicy
Revision
Rules                            none

```

By default, there are no rules in the new policy:

```bash
[basecm11->partition*[base*]->leakactionpolicies*[mypolicy*]]% rules
[basecm11->partition*[base*]->leakactionpolicies*[mypolicy*]->rules]% list

                                                 Electrical  Liquid     Minimal Maximal
Name (key)  Scope     Power off  Power off rack  isolation   isolation  devices devices
----------- --------- ---------- --------------- ---------- ----------- -------- ------

```

The cluster administrator may have a testing room in which to keep a rack. In that case, the following might be added:

```bash
[basecm11->partition*[base*]->leakactionpolicies*[mypolicy*]->rules]% add testroom
[basecm11->partition*[base*]->leakactionpolicies*[mypolicy*]->rules*[testroom*]]% show
Parameter                        Value
-------------------------------- ------------------------------------------------
Name                             testroom
Revision
Scope                            rack
Disabled                         no
Minimal devices                  1
Maximal devices                  100
Grace period                     0s
Correlation window               5m
Power off                        yes
Power off rack                   no
Electrical isolation             no
Liquid isolation                 no
Minimal severity                 1
Maximal severity                 100

```

Adding a rule adds a default with the preceding rack-based rule values.

The rule values can be modified using the `set` command.

Running `set` without any options provides a help text explaining what can be set:

```bash
[basecm11->partition*[base*]->leakactionpolicies*[mypolicy*]->rules]% set
```