# Appendix A-D: Submission & Standards

> Lists appendix submission requirements, model-package expectations, and governing industrial and regulatory standards for BESS review.

## Appendix A: Data Submission Requirements

Every test must include:

* Raw time-series (CSV)
* Summary plots (PDF)
* Test configuration (single-line of test setup, controller settings, SOC)
* Pass/fail statement tied to criteria
* Known issues and deviations list

## Appendix B: Core Requirements Checklist

Partners must fill out a one-page checklist mapping: **Core Requirement → Test IDs → Evidence references.**

## Appendix C: Partner Model Package Requirements

**Minimum:**

* EMT model (PSCAD/EMTDC, RTDS, or equivalent), including control blocks
* dq impedance plots at:
  * 10%, 50%, 100% P
  * High and low Q
  * Multiple SCR values
* Nyquist/passivity artifact and interpretation
* Version-controlled parameter export

#### Model Validity

Models that cannot reproduce hardware behavior within stated tolerances are invalid.

## Appendix D: Industrial Standards and Regulatory Certificates

Partners must provide a list of industrial standards the system is designed to comply with, as well as test certificates granted by countries or economic areas. Key standards include:

* IEEE 1547-2018, IEEE 2800
* UL 9540 / UL 9540A
* NFPA 855
* CE/UKCA
* RoHS/REACH
* IEC 60068
* ISO 9001
* NERC Reliability Guidelines
* NERC CIP (Critical Infrastructure Protection)
* IEC 62443 (Industrial Automation and Control Systems Security)
* NIST Cybersecurity Framework (CSF)