Network Breakdown IP Plan Subnetting Calculator#

Use this calculator to estimate subnet sizes for NVIDIA DGX SuperPOD IP plans. Select a System Type and Scalable Units value, then choose Calculate.

The calculator supports Vera Rubin NVL72, DGX Rubin NVL8, GB200, GB300, B200, and B300. A scalable unit (SU) is a group of systems whose size depends on the system type.

Network Subnetting Calculator
DGX and Vera Rubin subnet planning
Note: Vera Rubin NVL72 uses one BMC address per compute tray. Each NVLink switch uses two management addresses (BMC and OS eth0) on nvlinknet.

Select a system type and scalable unit count, then choose Calculate.

Vera Rubin Scale and BMC Assumptions#

For Vera Rubin NVL72 and DGX Rubin NVL8, you can select from 1 through 64 scalable units.

The calculator uses the following baseboard management controller (BMC) address counts:

  • Vera Rubin NVL72 uses one BMC management address per compute tray.

  • Vera Rubin NVL72 uses two management addresses per NVLink switch: BMC and OS eth0. Those addresses use nvlinknet<s>, not cinbmcnet1.

  • Vera Rubin NVL72 uses one management address per power shelf on pdunet<s>.

  • Vera Rubin NVL72 uses one BlueField BMC address per compute tray on dgxbfbmcnet<s> in noDPU mode.

  • DGX Rubin NVL8 uses one BMC management address per DGX Rubin NVL8 system.

DGX Rubin NVL8 includes built-in NVLink switches. The calculator does not allocate a separate NVLink Switch (NVLSW) network for NVL8.

Subnet Connection Guide#

TAN stands for tenant access network. TAN1 carries storage traffic over converged Ethernet and tenant or user access traffic. It also connects user-facing interfaces for control-plane services, such as Kubernetes, NVIDIA Run:ai, and Slurm. Keep the management interfaces for control-plane equipment, including Base Command Manager (BCM), Kubernetes administration nodes, and Slurm controllers, on the ADMIN networks.

Use the following mapping to connect each subnet to the intended devices and interfaces:

Table 1 Subnet-to-device mapping#

VRF

Subnet

Connected Devices and Interfaces

Do Not Connect

ADMIN

adminnet1

BCM and cluster-management servers, Kubernetes administration nodes, Network File System (NFS) or storage-management servers, and infrastructure management interfaces such as M1, M2, or bonded management interfaces

GPU data interfaces, chassis BMCs, or switch-management ports

ADMIN

adminbmcnet1

BMCs for control-plane and infrastructure servers, HSS management, infrastructure BlueField BMC interfaces, data processing unit (DPU) operating-system management interfaces, and appliance management ports

Compute-tray chassis BMCs unless the IP plan explicitly includes and counts them

ADMIN

switchnet1

Ethernet switch-management ports, leaf and spine management interfaces, top-of-rack (ToR) management ports, and out-of-band (OOB) management switches

ConnectX-9 data-plane ports or production traffic

ADMIN

cinbmcnet1

Compute interconnect network (CIN) switch ETH0 or MGMT ports and related fabric-management appliances

NVLink switch BMC or OS eth0 ports. Those addresses use nvlinknet<s>.

ADMIN

dgxbmcnet1

Vera Rubin compute-tray chassis BMCs or DGX Rubin NVL8 chassis BMCs

GPUs, ConnectX-9 data ports, host operating-system interfaces, or service virtual IP (VIP) addresses

ADMIN

nvlinknet1 (or nvlinknet<s>)

NVLink switch BMC and OS eth0 (ComE) management ports for that scalable unit

GPU NVLink data or CIN data-plane ports

ADMIN

pdunet1 (or pdunet<s>)

Power shelf and PDU management interfaces for that scalable unit

Compute-tray BMCs or Ethernet switch-management ports

ADMIN

dgxbfbmcnet1 (or dgxbfbmcnet<s>)

Compute-tray BlueField BMC in noDPU mode. DPU mode uses two DPU-OOB addresses per tray.

Chassis BMCs on dgxbmcnet1, or NVLink switch ports

TAN1

internalnet

Kubernetes user services, NVIDIA Run:ai services, Slurm login nodes, API endpoints, and user-facing service interfaces such as an M1 and M2 bond0 interface

Chassis BMCs or fabric-management interfaces

TAN1/EXIT

MISC

Loopback addresses, service VIPs, load-balancer VIPs, DNS, NTP, monitoring, logging, and other shared infrastructure endpoints

Bulk allocations for compute nodes

TAN1/EXIT

edge

Point-to-point router, firewall, or external gateway interfaces

Servers, BMCs, or large endpoint groups

dgxbfbmcnet<s>, nvlinknet<s>, and pdunet<s> use IntraPod addressing (default 100.64.0.0/10). They do not come from the customer ADMIN root.

Vera Rubin Connection and Counting Guidance#

Use the following counting rules to confirm that the selected subnet contains enough usable addresses:

Table 2 Vera Rubin subnet connection guidance#

Subnet

Vera Rubin Devices

Counting Rule

adminnet1

Cluster-management, Kubernetes administration, and storage-management servers

One IP address per attached management interface

adminbmcnet1

Control-plane BMCs, infrastructure BMCs, and infrastructure DPU-management interfaces

Count each independently managed interface

switchnet1

OOB, leaf, spine, and ToR switch-management ports

One IP address per switch-management interface

cinbmcnet1

CIN switch-management interfaces when the site uses CIN

One IP address per CIN switch-management interface

dgxbmcnet1

Vera Rubin NVL72 compute-tray chassis BMCs or DGX Rubin NVL8 chassis BMCs

Vera Rubin NVL72: 18 compute trays per rack × 8 racks per SU × SUs. DGX Rubin NVL8: 64 systems per SU × SUs.

nvlinknet1 (or nvlinknet<s>)

NVLink switch BMC and OS eth0

Two IP addresses per NVLink switch. Vera Rubin NVL72: 9 switches per rack × 8 racks per SU × 2 addresses × SUs. Each SU uses a /23.

pdunet1 (or pdunet<s>)

Power shelves and PDUs

One IP address per power-shelf or PDU management interface. Vera Rubin NVL72: 8 power shelves per rack × 8 racks per SU × SUs. Each SU uses a /24.

dgxbfbmcnet1 (or dgxbfbmcnet<s>)

Compute-tray BlueField BMCs

One IP address per compute tray in noDPU mode. Vera Rubin NVL72: 18 trays per rack × 8 racks per SU × SUs. Each SU uses a /22. DPU mode uses two DPU-OOB addresses per tray.

internalnet

Kubernetes user, NVIDIA Run:ai, Slurm, and shared service interfaces

One IP address per service interface or bond

MISC

Loopbacks, VIPs, and shared services

One IP address per logical endpoint

edge

Router or firewall point-to-point link

Normally two usable IP addresses