Installation Instructions
Tool-Less 4-Post Mounting Rail-Kit
# | Illustration | ||
---|---|---|---|
1. | Extract the inner rails (A) from the other rails by pressing the spring latch and pulling it out, as shown in the following illustration: | ||
2. |
| ||
3. | Install the outer rails (B+C) in the rack, as shown in the following illustration: | ||
4. | Mount the chassis onto the rack
|
Tool-Less 2-Post Mounting Rail-Kit
This mounting kit is optional and should be ordered separately.
The 2-post mounting installation may cause sinking of the switch. The rear end sag is 6-8mm.
# | Illustration | ||
---|---|---|---|
1. | Attach the two brackets (A) to the chassis, using the 12 M4 screws (B) provided in the kit, according to your installation selection:
| ||
2. | Install 4 cage nuts (C) in the desired 1U slots of the rack an mount the device in the rack, using 10-32 rack mounting screws. | ||
3. | The cable retainer should be used to secure the cable when installing the system. To secure the power cord inside the retainer, press the small tab on the retainer strip to loosen the loop. |
System Interfaces
Connector (Front) Side |
FRU (Rear) Side |
* It may take up to five minutes to turn on the system. If the System Status LED shows amber after five minutes, unplug the system and contact your NVIDIA representative.
LED Assignments
Symbol | Description | Normal Status |
---|---|---|
System health | Green | |
Fan health | Green | |
Power supply health | Green | |
Bad port detected | Off | |
Identifier LED | Off/Blue | |
Reset button |
Configuration
- Connect the host PC to the Console (RJ-45) port.
Configure a serial terminal program.
Parameter
Settings
Baud rate
115200
Data bits
8
Stop bits
1
Parity
None
Flow control
None
Login:
OS
Username
Password
Onyx (MLNX-OS)
admin
admin
ONIEb
-
-
Cumulus Linuxc
cumulus
CumulusLinux! (case sensitive)
a. No login is required. Press Enter to activate the console.
Initial configuration
- Onyx (MLNX-OS): Go through the configuration wizard. For further information, please refer to: https://docs.nvidia.com/networking/category/mlnxos.
- ONIE: Please refer to ONIE User Manual - https://docs.nvidia.com/networking/category/oniesw.
- Cumulus: By default, the MGMT port will acquire the IP from DHCP. You can cross reference the MAC of the switch with your DHCP server (MAC can be found on switch label) or using "ifconfig eth0" (when using MGMT0). For further information, refer to: https://docs.nvidia.com/networking-ethernet-software/cumulus-linux-53/Quick-Start-Guide/.
For full installation instructions, go to https://docs.nvidia.com/networking/category/switchen.