# NIC Health Monitor: Link State Detection

---

## Table of Contents

1. [Overview](#1-overview)
2. [Architecture](#2-architecture)
3. [State Monitoring Specification](#3-state-monitoring-specification)
4. [Management NIC Exclusion, NIC Role Classification, and Uncabled Port Detection](#4-management-nic-exclusion-and-uncabled-port-detection)
5. [Device Discovery and Parsing](#5-device-discovery-and-parsing)
6. [State Change and Flap Detection](#6-state-change-and-flap-detection)
7. [Device Disappearance Handling](#7-device-disappearance-handling)
8. [SR-IOV Virtual Function Handling](#8-sr-iov-virtual-function-handling)
9. [RoCE State Monitoring](#9-roce-state-monitoring)
10. [Supported Hardware](#10-supported-hardware)
11. [Data Structures](#11-data-structures)
12. [Configuration](#12-configuration)
13. [Event Management](#13-event-management)
- [Appendix A: Quick Reference - Fatal Condition Classification](#appendix-a-quick-reference---fatal-condition-classification)

**Related Documents:**
- [Link Counter Detection](/nvsentinel/components/nic-health-monitor/link-counter-detection) - Counter-based degradation monitoring
- [Syslog Detection & Correlation](/nvsentinel/components/nic-health-monitor/syslog-detection-and-correlation) - Kernel log monitoring and repeat failure detection

---

## 1. Overview

### 1.1 Problem Statement

Modern GPU clusters suffer from **Grey Failures** (subtle degradations) and **straggler effects** where a single degraded link throttles thousands of GPUs. Simple UP/DOWN polling is the first line of defense for detecting hard failures where the NIC becomes completely unavailable.

### 1.2 Scope of Link State Detection

This document covers the **State Monitoring** component of the NIC Health Monitor, which detects:

- **Hard UP/DOWN transitions** - Link completely lost, no connectivity
- **Device disappearance** - NIC no longer visible in sysfs (fell off PCIe bus)
- **Physical state changes** - Port disabled, polling, or in error recovery
- **Uncabled port anomaly detection** - Card has fewer active ports than its peers (via homogeneity check)
- **Management NIC auto-exclusion** - NICs on NUMA nodes with no compute GPU are automatically excluded

### 1.3 Binary Severity Model

This monitor uses a binary severity model based on **workload impact**:

| Severity      | Meaning                                  | Example                                            |
|---------------|------------------------------------------|----------------------------------------------------|
| **Fatal**     | Workload WILL fail or HAS failed         | NIC DOWN, device disappeared, phys_state=Disabled  |
| **Non-Fatal** | Degradation detected, workload continues | Transient state changes that recover automatically |

**Key Design Principle**: The only question that matters is **"Will the running workload fail because of this?"**

### 1.4 State Detection Overview Diagram

```
┌─────────────────────────────────────────────────────────────────────────────┐
│                     LINK STATE DETECTION FLOW                               │
├─────────────────────────────────────────────────────────────────────────────┤
│                                                                             │
│  ┌─────────────────────────────────────────────────────────────────────┐   │
│  │                     DATA SOURCES (sysfs)                             │   │
│  ├─────────────────────────────────────────────────────────────────────┤   │
│  │  /sys/class/infiniband/<dev>/ports/<port>/                          │   │
│  │  ├── state           →  Logical state (DOWN, INIT, ARMED, ACTIVE)   │   │
│  │  └── phys_state      →  Physical state (LinkUp, Disabled, Polling)  │   │
│  │                                                                      │   │
│  │  /sys/class/net/<interface>/                                         │   │
│  │  └── operstate       →  Interface state (up, down, unknown)         │   │
│  │                                                                      │   │
│  └─────────────────────────────────────────────────────────────────────┘   │
│                                     │                                       │
│                                     ▼                                       │
│  ┌─────────────────────────────────────────────────────────────────────┐   │
│  │                  STATE MONITOR (1s polling interval)                 │   │
│  ├─────────────────────────────────────────────────────────────────────┤   │
│  │                                                                      │   │
│  │  DETECTS:                                                            │   │
│  │  ├── Hard DOWN            → Link completely lost (FATAL)            │   │
│  │  ├── Device disappeared   → NIC not in sysfs (FATAL)               │   │
│  │  ├── Uncabled port anomaly→ Card below peer mode (FATAL)            │   │
│  │  ├── Physical disabled    → Port disabled (FATAL)                   │   │
│  │  └── Link error recovery  → Active link problems (FATAL)           │   │
│  │                                                                      │   │
│  └─────────────────────────────────────────────────────────────────────┘   │
│                                     │                                       │
│                                     ▼                                       │
│  ┌─────────────────────────────────────────────────────────────────────┐   │
│  │              RAW EVENTS → PLATFORM CONNECTOR → MongoDB               │   │
│  └─────────────────────────────────────────────────────────────────────┘   │
│                                     │                                       │
│                                     ▼                                       │
│  ┌─────────────────────────────────────────────────────────────────────┐   │
│  │            HEALTH EVENTS ANALYZER (Correlation Rules)                │   │
│  ├─────────────────────────────────────────────────────────────────────┤   │
│  │  • Link Flap Detection: "link_downed 3+ times in 10 min"            │   │
│  │  • Stabilization Windows: Prevent alert blinking                     │   │
│  │  • Cross-node correlation: Detect fabric-wide issues                 │   │
│  └─────────────────────────────────────────────────────────────────────┘   │
│                                                                             │
└─────────────────────────────────────────────────────────────────────────────┘
```

---

## 2. Architecture

### 2.1 Design Rationale: NVSentinel's "Report Raw, Correlate Centrally" Pattern

The State Monitor follows NVSentinel's established architectural pattern where:

1. **Health Monitors (DaemonSets)** report **raw events as-is** to the Platform Connector
2. **Health Events Analyzer (Centralized Deployment)** performs all correlation, aggregation, and pattern detection
3. **MongoDB** serves as the source of truth for event history and correlation queries

| Architectural Principle     | Implementation                             | Purpose                                                                   |
|-----------------------------|--------------------------------------------|---------------------------------------------------------------------------|
| **Raw Event Reporting**     | Health boundary crossing → immediate event | One event per port per healthy↔fatal transition                           |
| **Centralized Correlation** | Health Events Analyzer MongoDB pipelines   | Flexible, configurable rules without monitor code changes                 |
| **Temporal Correlation**    | Analyzer rules with time windows           | Detects patterns like "3 link flaps in 10 minutes"                        |
| **Stabilization Windows**   | Analyzer rules with sticky XID-style logic | Prevents "Alert Blinking" where transient recoveries hide critical issues |

### 2.2 Component Responsibilities

| Component                            | Responsibility                                                                                                                              | What It Does NOT Do                                        |
|--------------------------------------|---------------------------------------------------------------------------------------------------------------------------------------------|------------------------------------------------------------|
| **NIC Health Monitor (State Check)** | Poll sysfs state files, detect UP/DOWN transitions, persist port state snapshots and known device list, emit raw events and recovery events | Aggregation, deduplication, correlation, pattern detection |
| **Health Events Analyzer**           | Correlate events, detect link flap patterns, escalate severity                                                                              | Direct hardware access                                     |

> **Local State Persistence**: The State Check persists port state snapshots (`state`, `phys_state` per port) and the known device list to the shared NIC health monitor state file (hostPath-backed, see [Link Counter Detection, Section 6.6](/nvsentinel/components/nic-health-monitor/link-counter-detection#66-persistent-state-file)). This enables the monitor to (1) emit **recovery events** (`IsHealthy=true`) after pod restart when a previously-DOWN port has been fixed, (2) detect **device disappearance** across pod restarts by comparing the current device list against the persisted known devices, and (3) on **host reboot** (boot ID change), clear all state and emit **healthy baseline events** for all currently-healthy ports to clear stale FATAL conditions on the platform — since the node may have had NICs replaced during maintenance (see [Link Counter Detection, Section 6.5](/nvsentinel/components/nic-health-monitor/link-counter-detection#65-boot-id-handling)).

### 2.3 State Check Data Flow (1s polling interval)

```
Reads:
├── state          → Logical link state (DOWN, INIT, ARMED, ACTIVE)
├── phys_state     → Physical layer state (LinkUp, Disabled, Polling, LinkErrorRecovery)
└── operstate      → Ethernet interface state (up, down, unknown)

Detects:
├── Hard DOWN            → Link completely lost, no connectivity
├── Device disappearance → NIC no longer visible in sysfs
├── Uncabled port anomaly→ Card has fewer active ports than peers
└── Physical disabled    → Port administratively or physically disabled

On device disappearance:
└── Device not in sysfs → Hardware failure (FATAL)

Persists (to shared state file after each poll cycle):
├── Port state snapshots → state + phys_state per port (for recovery events)
└── Known device list    → Device names seen (for disappearance across restarts)

Emits: Raw STATE_CHANGE events → Platform Connector → MongoDB
       Recovery events (IsHealthy=true) when previously-DOWN port recovers
       (Link flap detection handled by Health Events Analyzer)
```

### 2.4 System Context

```
┌────────────────────────────────────────────────────────────────────────────────┐
│                      NVSentinel NIC STATE MONITORING                           │
├────────────────────────────────────────────────────────────────────────────────┤
│                                                                                │
│  ┌──────────────────────────────────────────────────────────────────────────┐  │
│  │                       PER-NODE DAEMONSET                                 │  │
│  ├──────────────────────────────────────────────────────────────────────────┤  │
│  │                                                                          │  │
│  │  ┌────────────────────────────────────┐                                  │  │
│  │  │     NIC HEALTH MONITOR             │                                  │  │
│  │  │     (State Check - 1s interval)    │                                  │  │
│  │  │     ══════════════════════════     │                                  │  │
│  │  │                                    │                                  │  │
│  │  │  DATA SOURCES:                     │                                  │  │
│  │  │  • /sys/class/infiniband/          │                                  │  │
│  │  │  • /sys/class/net/                 │                                  │  │
│  │  │  • /sys/bus/pci/devices/           │                                  │  │
│  │  │                                    │                                  │  │
│  │  │  CHECKS:                           │                                  │  │
│  │  │  • InfiniBandStateCheck            │                                  │  │
│  │  │  • EthernetStateCheck              │                                  │  │
│  │  │                                    │                                  │  │
│  │  │  BEHAVIOR:                         │                                  │  │
│  │  │  • Reports RAW state events        │                                  │  │
│  │  │  • Persistent local state          │                                  │  │
│  │  │    (port states, known devices,    │                                  │  │
│  │  │    counter snapshots, breach flags,│                                  │  │
│  │  │    boot ID)                        │                                  │  │
│  │  │  • Correlation centralized         │                                  │  │
│  │  └──────────────┬─────────────────────┘                                  │  │
│  │                 │                                                        │  │
│  └─────────────────┼────────────────────────────────────────────────────────┘  │
│                    │                                                           │
│                    ▼                                                           │
│  ┌──────────────────────────────────┐                                          │
│  │     PLATFORM CONNECTOR           │                                          │
│  │     ══════════════════           │                                          │
│  │  • Receives raw events           │                                          │
│  │  • Persists to MongoDB           │                                          │
│  │  • Triggers downstream           │                                          │
│  └──────────────┬───────────────────┘                                          │
│                 │                                                              │
│                 ▼                                                              │
│  ┌──────────────────────────────────────────────────────────────────────────┐  │
│  │                    HEALTH EVENTS ANALYZER                                │  │
│  │                    (Link Flap Detection)                                 │  │
│  │                    ══════════════════════                                │  │
│  │                                                                          │  │
│  │  NIC STATE CORRELATION RULES:                                            │  │
│  │  • RepeatedNICLinkFlap: "link_downed 3+ times in 10 min → REPLACE_VM"    │  │
│  │  • NICStabilizationWindow: Prevent flapping (similar to sticky XID)      │  │
│  └──────────────────────────────────────────────────────────────────────────┘  │
│                                                                                │
└────────────────────────────────────────────────────────────────────────────────┘
```

---

## 3. State Monitoring Specification

### 3.1 Port States (Full Enumeration)

Port states are defined by the Linux kernel InfiniBand sysfs interface. **Reference**: [Linux Kernel sysfs-class-infiniband ABI](https://www.kernel.org/doc/Documentation/ABI/stable/sysfs-class-infiniband)

```go
const (
    // Port logical states
    IBStateDown    = "1: DOWN"      // No connectivity
    IBStateInit    = "2: INIT"      // Initializing (problematic if stuck >30s)
    IBStateArmed   = "3: ARMED"     // Armed but not active (check SM)
    IBStateActive  = "4: ACTIVE"    // Normal operational state

    // Port physical states
    IBPhysStateSleep     = "1: Sleep"
    IBPhysStatePolling   = "2: Polling"                    // Link training
    IBPhysStateDisabled  = "3: Disabled"                   // CRITICAL - port disabled
    IBPhysStateTraining  = "4: PortConfigurationTraining"  // Link negotiation
    IBPhysStateLinkUp    = "5: LinkUp"                     // Normal
    IBPhysStateLinkErr   = "6: LinkErrorRecovery"          // Active error recovery
    IBPhysStatePhyTest   = "7: Phy Test"                   // Diagnostic mode
)
```

### 3.2 State Transitions

**Logical State Flow**: `DOWN (1)` → `INIT (2)` → `ARMED (3)` → `ACTIVE (4)`

- **DOWN**: No connectivity (FATAL)
- **INIT**: Initializing — normal transient state during startup. Every port passes through INIT during boot and Subnet Manager configuration. For **InfiniBand ports**, classified as **Non-Fatal** (`IsFatal=false`) because INIT can persist while waiting for SM configuration. For **Ethernet/RoCE ports**, INIT is a brief sub-second transient during link training and is not reported (logged at DEBUG level only). If an IB port remains stuck in INIT, it won't satisfy the `ACTIVE/LinkUp` condition, causing the card's active port count to fall below its peers, which is caught as a Fatal condition by the card homogeneity check (see Section 4.2).
- **ARMED**: Waiting for Subnet Manager — same rationale as INIT. For **InfiniBand ports**, classified as **Non-Fatal** (`IsFatal=false`). For **Ethernet/RoCE ports**, this state is rare/transient and is not reported. Prolonged ARMED state on IB is caught by the card homogeneity check.
- **ACTIVE**: Normal operational state (HEALTHY)

**Physical State Substates**: `Sleep (1)`, `Polling (2)`, `Disabled (3)`, `Training (4)`, `LinkUp (5)`, `LinkErrorRecovery (6)`

- **Polling (2)**: Transient state during link training. Every port passes through Polling when establishing a connection. Classified as **Non-Fatal** (`IsFatal=false`). If a port remains in Polling, it won't count as active in the card homogeneity check, so the card's active port count will fall below the peer mode and be caught as a Fatal anomaly (see Section 4.2).
- **LinkErrorRecovery (6)**: Active error recovery in progress. Classified as **Non-Fatal** (`IsFatal=false`) because the HCA firmware is actively retrying. If recovery fails and the port remains unhealthy, the card homogeneity check (Section 4.3) escalates to Fatal by detecting fewer active ports than peers.

### 3.3 Diagnostic Commands

```bash
# Check logical and physical port states
ibstat
# Output:
# CA 'mlx5_0'
# 	Port 1:
# 		State: Active
# 		Physical state: LinkUp
# 		Rate: 400
# 		Link layer: InfiniBand

# Check specific port state via sysfs
cat /sys/class/infiniband/mlx5_0/ports/1/state
# Output: 4: ACTIVE

cat /sys/class/infiniband/mlx5_0/ports/1/phys_state
# Output: 5: LinkUp
```

### 3.4 State-Based Event Generation Algorithm

**Port Health Evaluation Steps:**

1. **Read port state** from `/sys/class/infiniband/<dev>/ports/<port>/state` and `phys_state`
2. **Load previous port state** from persistent state file (or in-memory if available from a prior poll in this pod's lifetime)
3. **Determine health status:**
   - If `state = ACTIVE` AND `phys_state = LinkUp` → **Healthy**
   - Otherwise → **Unhealthy** (the specific state/phys_state combination determines the message)

4. **Emit event only on health boundary crossing:**
   - **First poll after host reboot (boot ID changed — state cleared)**:
     - All persisted state has been discarded (see [Link Counter Detection, Section 6.5](/nvsentinel/components/nic-health-monitor/link-counter-detection#65-boot-id-handling))
     - Healthy ports (`ACTIVE/LinkUp`): Emit **healthy event** (`IsHealthy=true`) — this clears any stale FATAL conditions on the platform from the previous boot (the node may have had NICs replaced, cables reseated, etc.)
     - Unhealthy ports on **anomalous cards**: Emit fatal event as usual
     - Unhealthy ports on **expected cards**: **Suppressed** (uncabled port, not a failure)
   - **First poll with no persisted state (fresh node, corrupt/missing state file)**:
     - Same behavior as the reboot case above
   - **First poll with persisted previous state (pod restart, same boot)**:
     - Compare current health against **persisted** previous state
     - Emit events on boundary crossings as with subsequent polls below (this is the key benefit of persistence — a port that was DOWN before restart and is now ACTIVE triggers a recovery event)
   - **Subsequent polls**: Only emit when `wasHealthy ≠ isHealthy`
     - Healthy → Unhealthy: **FATAL event** with consolidated message (e.g., "state DOWN, phys_state Disabled - no connectivity")
     - Unhealthy → Healthy: **HEALTHY event** (e.g., "healthy (ACTIVE, LinkUp)")
     - Unhealthy → Unhealthy (e.g., DOWN/Disabled → DOWN/Polling): **No event** — still unhealthy, intermediate transition suppressed
     - Healthy → Healthy: **No event** — still healthy

4. **One consolidated event per port per transition:**
   - Logical state and physical state are combined into a single message
   - For Ethernet/RoCE, the operstate is also included in the same event
   - `EntitiesImpacted` includes both NIC and Port entities
   - `RecommendedAction = REPLACE_VM` for fatal events

---

## 4. Management NIC Exclusion and Uncabled Port Detection

This section describes three zero-configuration mechanisms that replace the previous `gpu_port_config` / `AtLeastPorts` / `AtLeastRate` approach. These mechanisms require no per-GPU-type configuration and work automatically across DGX, HGX, Grace-based superchips (GB200/GH200), OEM servers, and cloud VMs.

- **Section 4.1**: NUMA-based management NIC exclusion (exclude NICs on non-GPU NUMA nodes)
- **Section 4.2**: NIC role classification (topo matrix + link layer + default-route exclusion)
- **Section 4.3**: Role-based card homogeneity (detect uncabled ports and failures within each role group)

The classification of each NIC uses a **three-step decision** built from four complementary signals:

1. **Step 1 — Management gate (NUMA locality, Section 4.1)**: Is the NIC on a CPU socket that hosts GPUs? If not, exclude it.
2. **Step 2 — Compute vs Storage (topo matrix + link layer, Section 4.2)**: For NICs that pass Step 1, consult the `nvidia-smi topo -m` GPU↔NIC relationship. If the topo matrix shows PCIe proximity (PIX/PXB), classify as Compute. Otherwise, use the NIC's **link layer** as a tiebreaker: InfiniBand NICs are Compute fabric; Ethernet NICs are Storage.
3. **Step 3 — Default route exclusion (Section 4.2)**: If the NIC carries the host's default IP route, classify as Management regardless of topo or link layer. This catches management NICs that share a NUMA node with GPUs (e.g., on-prem L40S, GB200). The classifier reads the host's `/proc/net/route` (bind-mounted at `/nvsentinel/proc/net/route`) at startup to resolve the default route interface.

These steps use four **complementary signals**, each covering platforms where the others fail:

| Signal                          | What it answers                                 | Platforms where it's the decisive signal                                                |
|---------------------------------|-------------------------------------------------|-----------------------------------------------------------------------------------------|
| **NUMA locality**               | "Is this NIC near any GPU?"                     | A100 DGX (4-socket: mgmt NICs on non-GPU sockets)                                       |
| **Topo matrix (PIX/PXB)**       | "Does this NIC share a PCIe switch with a GPU?" | H100 OCI, A100 OCI (SXM systems with PCIe switch pairing)                               |
| **Link layer (IB vs Ethernet)** | "Is this NIC on the InfiniBand compute fabric?" | On-prem L40S, GB200 (PCIe-only/Grace where topo can't distinguish compute from storage) |
| **Default route**               | "Does this NIC carry host networking?"          | On-prem L40S, GB200 (management NIC shares NUMA with GPUs)                              |

Removing any one signal causes at least one platform to misclassify. Together they cover x86 SXM (DGX/HGX), x86 PCIe (L40S), Grace (GB200/GH200), on-prem datacenter, and OEM/cloud platforms.

> **Hard dependency on metadata**: The NIC Health Monitor requires the raw GPU↔NIC topology matrix (and the GPU list) published by the metadata collector in `/var/lib/nvsentinel/gpu_metadata.json`. The monitor **fails to start** if the file is missing or unreadable, or if `nic_topology` is absent/empty. There is no silent-fallback mode. This is enforced at startup by `topology.LoadFromMetadata()`, which is called before any polling begins; failure returns an error that causes the process to exit. See [Section 12.1](#121-state-monitoring-configuration).
>
> **Responsibility split**: The metadata collector publishes raw facts: per-GPU NUMA nodes (from the `nvidia-smi topo -m` NUMA Affinity column) and the raw per-NIC topology-level matrix (one entry per GPU in `gpus[]` order). The NIC Health Monitor reads these together with per-NIC NUMA nodes (from its own sysfs access — the collector does not enumerate InfiniBand devices) and performs the compute/storage/management classification locally. The monitor never invokes `nvidia-smi` itself; the matrix and GPU NUMA are produced once by the collector and cached in JSON.
>
> **Why `nvidia-smi topo -m` text parsing**: The GPU↔NIC topology relationship is not available through any structured API. NVML exposes three topology functions (`DeviceGetTopologyCommonAncestor`, `DeviceGetTopologyNearestGpus`, `SystemGetTopologyGpuSet`), but all operate exclusively on `nvmlDevice_t` handles which represent GPUs only — NVML has no concept of NIC/InfiniBand devices. DCGM's `dcgmGetDeviceTopology` has the same GPU-only limitation. The `nvidia-smi topo` subcommand does not support `--format=json/xml/yaml` (unlike `nvidia-smi --query-gpu`); the only output format is the whitespace-aligned ASCII matrix (`-m`). No existing open-source library parses the full GPU↔NIC matrix from this output — HAMi's `parseNvidiaNumaInfo` only extracts GPU NUMA affinity (not NIC columns) and was itself replaced with sysfs reads due to parsing fragility. The metadata collector therefore includes a purpose-built parser with handling for known format variations (ANSI escape codes, `NICn` legend remapping, wrapped headers, Grace NUMA ranges).

### 4.1 Management NIC Exclusion (NUMA-Based)

#### 4.1.1 The Problem

DGX systems (e.g., DGX A100) have Mellanox ConnectX management NICs that appear in `/sys/class/infiniband/` alongside compute fabric NICs. If monitored, a management NIC going DOWN would trigger `IsFatal=true` with `RecommendedAction_REPLACE_VM` — an incorrect remediation for a NIC that doesn't affect GPU workloads. The design doc's severity model (Fatal = "workload WILL fail") is specifically designed for compute and storage NICs, not management NICs.

#### 4.1.2 Detection Mechanism

Management NICs on DGX systems are placed on CPU sockets that have **no compute GPUs**. The monitor exploits this by checking whether each NIC's NUMA node has a compute GPU on it:

1. Read `gpus[].numa_node` from `/var/lib/nvsentinel/gpu_metadata.json` (the metadata collector parses this from the `nvidia-smi topo -m` NUMA Affinity column and publishes it per GPU).
2. Build `gpu_numa_set` from the distinct `numa_node` values across all GPUs (ignoring -1 / unknown).
3. For each `mlx5_*` NIC discovered in `/sys/class/infiniband/`, read `/sys/class/infiniband/<dev>/device/numa_node`.
4. If `nic_numa ∉ gpu_numa_set` → **exclude** (management NIC on separate socket).

**Edge case — GPU**: If `gpus[].numa_node = -1` (unknown, common in VMs or single-socket systems), that GPU is excluded from the `gpu_numa_set`. If *all* GPUs have -1, the set is empty and the NIC Health Monitor **fails to start** — without GPU NUMA information the NUMA gate cannot distinguish management NICs from compute NICs, and monitoring everything would risk false `REPLACE_VM` on management NIC failures.

**Edge case — NIC**: If a NIC's `numa_node = -1` (unknown), the NIC is **excluded**. Under-monitoring (missing a NIC failure) is preferable to over-monitoring (issuing a false `REPLACE_VM` on a management NIC that happens to go down).

#### 4.1.3 Field Validation

| Cluster                          | Management NICs                                                                            | NUMA Check Result | Correct? |
|----------------------------------|--------------------------------------------------------------------------------------------|-------------------|----------|
| **A100 OCI RoCE** (4-socket AMD) | `mlx5_0` (NUMA 0), `mlx5_13` (NUMA 6) — no compute GPU on those NUMAs                      | Excluded          | Yes      |
| **L40 on-prem** (2-socket)       | None visible (BMC is non-Mellanox, invisible in `/sys/class/infiniband/`)                  | Nothing excluded  | Yes      |
| **L40S OCI** (2-socket Intel)    | None (all 6 Mellanox PFs share NUMA with GPUs)                                             | All monitored     | Yes      |
| **H100 DGX** (2-socket)          | Storage/mgmt NICs share NUMA with GPUs — correctly kept for monitoring                     | All monitored     | Yes      |
| **H100 OCI** (2-socket Intel)    | None (all 18 Mellanox PFs share NUMA with GPUs)                                            | All monitored     | Yes      |
| **GB200 NVL4** (Grace 2-socket)  | None (all 6 Mellanox PFs share NUMA with GPUs; management handled in Section 4.2 fallback) | All monitored     | Yes      |

> **Design Note**: Storage NICs (e.g., H100 Slot1/Slot2 ConnectX-7 cards) share a NUMA node with compute GPUs. They are intentionally **not excluded** because storage NIC failures also impact workloads (I/O hangs, checkpoint failures). The NUMA check only excludes NICs on NUMA nodes with **zero** compute GPUs.

### 4.2 NIC Role Classification (Topo Matrix)

#### 4.2.1 The Problem

DGX/HGX systems have both **compute fabric NICs** (OSFP ports on the GPU tray) and **storage NICs** (Slot1/Slot2 on the CPU motherboard). These are the same hardware (ConnectX-7) but serve different roles, may have different port counts, and run at different speeds. The card homogeneity check (Section 4.3) must compare NICs of the same role — compute against compute, storage against storage — to avoid false positives.

#### 4.2.2 Detection Mechanism: `nvidia-smi topo -m` Matrix Lookup

The metadata collector runs `nvidia-smi topo -m` on the node at startup, parses the GPU↔NIC relationship matrix into a raw per-NIC array of topology levels (one entry per GPU in `gpus[]` order), and publishes it to `/var/lib/nvsentinel/gpu_metadata.json` under the `nic_topology` field. The NIC Health Monitor consumes this matrix and applies the classification rules below to each NIC locally — no sysfs path walking, no PCIe-depth heuristics, and no direct invocation of `nvidia-smi` in the monitor.

The mapping from NVIDIA topology levels (the `nvmlGpuTopologyLevel_t` enum, displayed as `nvidia-smi topo -m` abbreviations) to NIC roles is:

| NVML topology level   | `nvidia-smi topo` | Meaning                                     | NIC Role                                                                                   |
|-----------------------|-------------------|---------------------------------------------|--------------------------------------------------------------------------------------------|
| `TOPOLOGY_SINGLE`     | **PIX**           | Single PCIe bridge between NIC and GPU      | **Compute** (shares a PCIe switch with a GPU — standard compute fabric NIC on DGX/HGX)     |
| `TOPOLOGY_MULTIPLE`   | **PXB**           | Multiple PCIe bridges between NIC and GPU   | **Compute** (still within a shared PCIe switch hierarchy)                                  |
| `TOPOLOGY_HOSTBRIDGE` | **PHB**           | Shared PCIe host bridge (CPU root complex)  | **Storage** (same host bridge but no switch — behaves like NODE for compute fabric intent) |
| `TOPOLOGY_NODE`       | **NODE**          | Same NUMA node, different PCIe host bridges | **Storage** (on same CPU socket but no PCIe proximity — typical storage NIC layout)        |
| `TOPOLOGY_SYSTEM`     | **SYS**           | Cross-NUMA (SMP interconnect like QPI/UPI)  | Falls through to NUMA-based classification (see Level 1 gate and fallback below)           |

**Classification algorithm** (applied per NIC after discovery):

```
classify_nic(nic):
    # Step 1: Default route exclusion
    # Catches management NICs that share a NUMA node with GPUs
    # (e.g., on-prem L40S, GB200). Runs first so the management NIC
    # is excluded even if it has PCIe proximity to a GPU.
    if device == default_route_device:
        return Management

    # Step 2: NUMA isolation gate
    if nic_numa not in gpu_numa_set:
        return Management

    # Step 3: Role determination (topo + link layer)
    topo = topo_matrix[nic]  # array of relationships, one per GPU

    if any GPU has PIX or PXB:
        return Compute

    # Step 4: Topology-based classification
    if link_layer == "InfiniBand":
        return Compute

    if any GPU has NODE or PHB:
        return Storage

    # All-SYS fallback (Grace/GB200 where GPUs aren't on PCIe)
    return Storage
```

**Precedence explained**:

1. **PIX/PXB → Compute**: The topo matrix authoritatively identifies NICs that share a PCIe switch with a GPU. This is the primary signal on SXM systems (DGX/HGX A100, H100).

2. **Default route → Management**: Runs before topology classification. The classifier reads `/proc/net/route` at startup, finds the default route interface, and maps it to an IB device via `/sys/class/net/<iface>/device/infiniband/`. This prevents the management NIC from being monitored as Storage, avoiding false REPLACE_VM for control-plane network failures. If `/proc/net/route` is unavailable or the interface has no IB backing, the check is silently skipped.

3. **InfiniBand → Compute**: On platforms where no NIC has PIX/PXB to a GPU (PCIe-only GPUs like L40S, or Grace where GPUs aren't on PCIe), the link layer distinguishes compute fabric NICs (InfiniBand) from storage/management NICs (Ethernet). This is the decisive signal on on-prem L40S and GB200.

4. **NODE/PHB → Storage**: NICs that share a NUMA node or host bridge with a GPU but don't share a PCIe switch and aren't InfiniBand. Typical storage NIC layout on H100 OCI (Slot1/Slot2 ConnectX-7 Ethernet cards).

5. **All-SYS fallback → Storage**: NICs on a GPU NUMA but with no PCIe relationship and Ethernet link layer. Safe default: monitored.

#### 4.2.3 Three-Tier Classification

Combined with the NUMA gate from Section 4.1, the monitor assigns each NIC to one of three roles:

| Role           | Detection                                                                                                                     | Monitoring Behavior                                            |
|----------------|-------------------------------------------------------------------------------------------------------------------------------|----------------------------------------------------------------|
| **Management** | NIC NUMA has no compute GPU, **or** NIC carries the host's default route, **or** NIC is a BlueField DPU in the all-SYS branch | Excluded from monitoring entirely                              |
| **Compute**    | Any GPU has PIX or PXB relationship to this NIC, **or** NIC link layer is InfiniBand (when no PIX/PXB exists)                 | Monitored; compared against other compute NICs for homogeneity |
| **Storage**    | Ethernet NIC with NODE or PHB to a GPU, **or** Ethernet NIC in all-SYS fallback on GPU NUMA                                   | Monitored; compared against other storage NICs for homogeneity |

> **Key design property**: On every validated platform, InfiniBand NICs and Ethernet NICs end up in **separate classification groups** (Compute vs Storage). This ensures the card homogeneity check (Section 4.3) never compares IB compute fabric NICs against Ethernet storage/management NICs, preventing false positives from hardware diversity (e.g., different port counts, different link speeds).

#### 4.2.4 Field Validation

Verified against real hardware on five distinct platforms covering x86 SXM (A100, H100), x86 PCIe (L40S OCI, on-prem L40S), and Grace (GB200). The link-layer check improves classification on on-prem and GB200 compared to the previous sysfs PCIe path-walk algorithm, while producing identical results on all other platforms.

**A100 OCI RoCE (4-socket AMD EPYC, 8 GPUs, 18 PF NICs):**

| NIC Pattern                             | Topo relationship       | Classification        |
|-----------------------------------------|-------------------------|-----------------------|
| `mlx5_0` (NUMA 0)                       | All SYS, NUMA ∉ GPU set | **Management**        |
| `mlx5_13` (NUMA 6)                      | All SYS, NUMA ∉ GPU set | **Management**        |
| `mlx5_1`–`mlx5_12`, `mlx5_14`–`mlx5_17` | PXB to paired GPUs      | **Compute** (16 NICs) |

Result: 2 Management + 16 Compute + 0 Storage. 18/18 match current algorithm.

**H100 OCI (2-socket Intel Xeon Platinum 8480+, 8 GPUs, 18 PF NICs):**

| NIC       | Topo relationship         | Classification |
|-----------|---------------------------|----------------|
| `mlx5_2`  | NODE to all GPUs (no PXB) | **Storage**    |
| `mlx5_11` | NODE to all GPUs (no PXB) | **Storage**    |
| Other 16  | PXB to one paired GPU     | **Compute**    |

Result: 0 Management + 16 Compute + 2 Storage. Matches documented storage NIC layout on OCI H100.

**L40S OCI (2-socket Intel, 4 PCIe GPUs, 6 PF NICs — all Ethernet/RoCE):**

Every NIC shows NODE to some GPUs and SYS to others; no NIC has any PIX or PXB (L40S is PCIe-attached, not SXM — there are no shared PCIe switches). All 6 NICs are Ethernet (RoCE). The link-layer check does not promote any to Compute (no InfiniBand). NODE → Storage for all.

Result: 0 Management + 0 Compute + 6 Storage. All NICs monitored in a single Storage homogeneity group. This is correct because OCI L40S uses RoCE for all cluster networking — there is no separate compute fabric link layer.

**On-prem L40S (2-socket Intel, 8 PCIe GPUs, 5 PF NICs: 1 Ethernet mgmt + 4 IB compute):**

On-prem datacenter nodes with PCIe GPUs and native InfiniBand for the compute fabric typically have a separate Ethernet NIC for pod networking. The topo matrix shows NODE to local GPUs for all 5 NICs (PCIe-only system, no shared switches). Without the link-layer check, all 5 would be classified as Storage (same group), corrupting the homogeneity check if port counts differ.

With the link-layer check:

| NIC      | Link layer | Topo               | Classification | Reason                               |
|----------|------------|--------------------|----------------|--------------------------------------|
| `mlx5_0` | Ethernet   | NODE to local GPUs | **Storage**    | Ethernet, not PIX/PXB → Storage      |
| `mlx5_1` | InfiniBand | NODE to local GPUs | **Compute**    | IB → Compute (link-layer tiebreaker) |
| `mlx5_2` | InfiniBand | NODE to local GPUs | **Compute**    | IB → Compute                         |
| `mlx5_3` | InfiniBand | NODE to local GPUs | **Compute**    | IB → Compute                         |
| `mlx5_4` | InfiniBand | NODE to local GPUs | **Compute**    | IB → Compute                         |

Result: 0 Management + 4 Compute + 1 Storage. The 4 IB NICs are in the Compute homogeneity group; the Ethernet management NIC is in a separate Storage group. No cross-comparison between IB and Ethernet, preventing false positives from hardware diversity.

With the default-route check: `mlx5_0` (carries default route) → **Management** (excluded). Result: 1 Management + 4 Compute + 0 Storage.

**GB200 NVL4 (2-socket Grace Neoverse-V2, 4 GPUs, 6 PF NICs: 4 ConnectX-7 IB + 2 BlueField-3 DPU):**

Every NIC↔GPU cell is SYS (GPUs are on NVLink-C2C, not PCIe — no shared PCIe ancestor exists). All NIC NUMAs are in the GPU NUMA set. No PIX/PXB or NODE/PHB relationships exist. The **link-layer check** and **HCA-based DPU detection** are the only signals that can distinguish roles:

| NIC           | Link layer | HCA type              | Classification | Reason                   |
|---------------|------------|-----------------------|----------------|--------------------------|
| `ibp3s0`      | InfiniBand | MT4129 (ConnectX-7)   | **Compute**    | IB → Compute             |
| `ibP2p3s0`    | InfiniBand | MT4129 (ConnectX-7)   | **Compute**    | IB → Compute             |
| `ibP16p3s0`   | InfiniBand | MT4129 (ConnectX-7)   | **Compute**    | IB → Compute             |
| `ibP18p3s0`   | InfiniBand | MT4129 (ConnectX-7)   | **Compute**    | IB → Compute             |
| `roceP6p3s0`  | Ethernet   | MT41692 (BlueField-3) | **Management** | BlueField DPU → excluded |
| `roceP22p3s0` | Ethernet   | MT41692 (BlueField-3) | **Management** | BlueField DPU → excluded |

Result: 2 Management (BlueField DPUs) + 4 Compute (IB ConnectX-7) + 0 Storage. The 4 IB NICs are monitored in the Compute homogeneity group; the 2 DPUs are excluded.

Known BlueField HCA types excluded: MT41682 (BlueField-2), MT41686 (BlueField-2 variant), MT41692 (BlueField-3). Unrecognised HCA types fall through to Storage (monitored) — the safe direction for future hardware.

With the default-route check: `roceP6p3s0` (carries default route) would be excluded by Step 3 before the HCA check even runs. Same result, different detection path.

### 4.3 Uncabled Port Detection (Role-Based Card Homogeneity)

#### 4.3.1 The Problem

Some NIC cards have multiple ports, but not all ports are cabled. For example, dual-port ConnectX cards may have only port 1 cabled and port 2 unused. The monitor must distinguish between a genuinely failed port and an intentionally uncabled one — without requiring static configuration like `gpu_port_config`.

Additionally, compute and storage NICs may have different port counts (e.g., dual-port compute cards vs single-port storage cards). The homogeneity check must compare NICs within the same role group to avoid false positives.

#### 4.3.2 Detection Mechanism

NICs are grouped by **role** (Compute or Storage, from Section 4.2), then within each role group:

1. Group NICs by **physical card** (PCI `bus:device` address — e.g., `0000:47:00` groups `0000:47:00.0` and `0000:47:00.1`)
2. Count active (`ACTIVE` + `LinkUp`) ports per card
3. Calculate the **mode** (most common active-port-count) within the role group
4. Any card with fewer active ports than its role's mode → **FATAL event**

#### 4.3.3 Algorithm

```
For all monitored PF NICs:
  Classify each NIC as Compute or Storage (Section 4.2)
  Group by physical card (PCI bus:device)
  Assign each card's role from its NICs

  For each role group (Compute, Storage):
    Calculate mode_active = most common active-port-count in this group
    For each card in this group:
      If card_active_count < mode_active:
        FATAL event: "Card <pci> (<role>) has <n> active ports, expected <mode>"
```

#### 4.3.4 Field Validation

**H100 OCI (compute dual-port + storage single-port):**
```
Compute group (8 cards): all dual-port, 2 active each → mode = 2
Storage group (2 cards): all single-port, 1 active each → mode = 1
→ No false positives (storage NICs NOT compared against compute mode)

If compute card drops to 1 active → 1 < mode 2 → FATAL
If storage card drops to 0 active → 0 < mode 1 → FATAL
```

**L40 (dual-port compute NICs, 1 port cabled per card):**
```
Compute group (2 cards): Card A (1 active, 1 down), Card B (1 active, 1 down) → mode = 1
→ Uncabled ports NOT flagged (consistent pattern)

If Card A drops to 0 active → 0 < mode 1 → FATAL
```

> **Probability analysis**: For the mode to be incorrect (masking real failures), more than half of the cards in a role group would need to be independently failed at startup. With a ~1% per-NIC failure rate, the probability of 4+ out of 8 NICs failing simultaneously is ~0.00003% — effectively impossible.

### 4.4 Design Decision: Why Speed Degradation Detection Was Removed

The previous design included a speed degradation check that compared the sysfs `rate` against an expected rate from `gpu_port_config`. This was removed for the following reasons:

1. **Required per-GPU-type static configuration** (`gpu_port_config`) that doesn't exist for non-DGX systems (L40, T4, cloud VMs, OEM servers)
2. **Cannot distinguish compute from storage NICs**: On H100 DGX, compute NICs run at 400 Gb/s (InfiniBand) while storage NICs may run at different speeds (Ethernet). Applying the same rate threshold to both causes false positives
3. **Counter checks already detect the underlying degradation**: When a cable degrades enough to cause speed fallback, the physical layer generates errors. The `symbol_error` and `link_error_recovery` counters (see [Link Counter Detection](/nvsentinel/components/nic-health-monitor/link-counter-detection)) detect this degradation before or during the retrain event
4. **Sysfs does not expose the expected/supported speed**: The `rate` file only shows the current negotiated speed, not the maximum supported speed of the NIC or cable

> **Note**: Speed degradation remains a real failure mode in GPU clusters. A 400G link dropping to 200G halves collective operation throughput. However, this is better addressed by counter-based degradation monitoring (Layer 2) which detects the physical signal degradation that causes the speed fallback, rather than by comparing the negotiated speed against a static configuration value.

---

## 5. Device Discovery and Parsing

### 5.1 Discovery Logic

The NIC Health Monitor discovers and parses InfiniBand/RoCE devices by iterating over sysfs:

1. Iterating over `/sys/class/infiniband`
2. Parsing `hca_type`, `fw_ver`, and `board_id`
3. Enumerating ports and reading `link_layer`, `state`, and `phys_state`
4. Identifying device type (PF vs VF) for proper alerting

### 5.2 Device Discovery Diagram

```
┌─────────────────────────────────────────────────────────────────────────────────┐
│                        NIC DEVICE DISCOVERY FLOW                                 │
├─────────────────────────────────────────────────────────────────────────────────┤
│                                                                                  │
│  /sys/class/infiniband/                                                          │
│  │                                                                               │
│  ├── mlx5_0/                     ◄── Physical Function (PF)                      │
│  │   ├── hca_type                    → "MT4123" (ConnectX-6)                     │
│  │   ├── fw_ver                      → "20.31.1014"                              │
│  │   ├── board_id                    → "MT_0000000010"                           │
│  │   ├── device/                                                                 │
│  │   │   ├── sriov_totalvfs          → "16" (PF indicator)                       │
│  │   │   └── uevent                  → PCI_SLOT_NAME=0000:3b:00.0               │
│  │   └── ports/                                                                  │
│  │       └── 1/                                                                  │
│  │           ├── state               → "4: ACTIVE"                               │
│  │           ├── phys_state          → "5: LinkUp"                               │
│  │           ├── link_layer          → "InfiniBand"                              │
│  │           └── counters/           → (see counter detection doc)               │
│  │                                                                               │
│  ├── mlx5_1/ ... mlx5_17/        ◄── More Physical Functions                     │
│  │                                                                               │
│  └── mlx5_18/ ... mlx5_33/       ◄── Virtual Functions (VFs)                     │
│      └── device/                                                                 │
│          └── physfn → ../0000:3b:00.0  (VF indicator - points to parent PF)     │
│                                                                                  │
└─────────────────────────────────────────────────────────────────────────────────┘
```

### 5.3 Vendor Detection

The monitor detects Mellanox devices using the following logic:
1. Check if device name matches `mlx5_\d+` (Mellanox).
2. Fallback: Check driver symlink in `/sys/class/infiniband/<dev>/device/driver` for `mlx5_core`.

| Vendor                 | Detection                              | State Monitoring  | Fatal Detection    |
|------------------------|----------------------------------------|-------------------|--------------------|
| **Mellanox (IB/RoCE)** | Device name `mlx5_*` or driver symlink | Yes - state files | State + PCI checks |

---

## 6. State Change and Flap Detection

The NIC Health Monitor reports **health boundary events** — one event per port when the port transitions between healthy and unhealthy states. Intermediate transitions (e.g., DOWN/Disabled → DOWN/Polling) are suppressed. The **Health Events Analyzer** performs pattern detection to distinguish between persistent drops and transient flapping.

### 6.1 Architecture

1. NIC Health Monitor reports health boundary crossings (healthy→fatal, fatal→healthy)
2. Events flow to MongoDB via Platform Connector
3. Health Events Analyzer applies correlation rules to detect patterns

### 6.2 Port Drop Detection (Analyzer Rule: `NICPortDrop`)

An InfiniBand port is marked as "Dropped" when the Analyzer detects:
- The port has been reporting `state=DOWN` for at least 4 minutes
- No `link_downed` delta events during this period (indicating no recovery attempts)

### 6.3 Port Flap Detection (Analyzer Rule: `RepeatedNICLinkFlap`)

An InfiniBand port is marked as "Flapping" (**Severity: FATAL**) when the Analyzer detects:
- 3+ `link_downed` events within 10 minutes on the same NICPort entity
- This indicates repeated DOWN→ACTIVE transitions (unstable hardware)

### 6.4 Link Flap Detection Diagram

```
┌─────────────────────────────────────────────────────────────────────────────────┐
│                         LINK FLAP DETECTION FLOW                                 │
├─────────────────────────────────────────────────────────────────────────────────┤
│                                                                                  │
│  TIME        NIC STATE           RAW EVENTS SENT                                 │
│  ────        ─────────           ───────────────                                 │
│                                                                                  │
│  T+0:00      ACTIVE              (baseline)                                      │
│  T+1:30      DOWN ────────────►  Event: link_downed, mlx5_0_port1               │
│  T+1:45      ACTIVE              (recovered)                                     │
│  T+4:20      DOWN ────────────►  Event: link_downed, mlx5_0_port1               │
│  T+4:35      ACTIVE              (recovered)                                     │
│  T+7:10      DOWN ────────────►  Event: link_downed, mlx5_0_port1               │
│              │                                                                   │
│              │   ┌─────────────────────────────────────────────────────────┐    │
│              └──►│        HEALTH EVENTS ANALYZER                           │    │
│                  │                                                          │    │
│                  │  Query: SELECT COUNT(*) FROM health_events              │    │
│                  │         WHERE agent = 'nic-health-monitor'              │    │
│                  │         AND message LIKE '%link_downed%'                │    │
│                  │         AND entity = 'mlx5_0_port1'                     │    │
│                  │         AND timestamp > NOW() - 10 minutes              │    │
│                  │                                                          │    │
│                  │  Result: 3 events                                        │    │
│                  │                                                          │    │
│                  │  Rule: RepeatedNICLinkFlap                               │    │
│                  │        IF count >= 3 THEN FATAL                         │    │
│                  │                                                          │    │
│                  │  ┌─────────────────────────────────────────────────┐    │    │
│                  │  │  OUTPUT: FATAL EVENT                            │    │    │
│                  │  │  Message: "NIC port flapping detected"          │    │    │
│                  │  │  RecommendedAction: REPLACE_VM                  │    │    │
│                  │  │  Entity: mlx5_0_port1                           │    │    │
│                  │  └─────────────────────────────────────────────────┘    │    │
│                  └─────────────────────────────────────────────────────────┘    │
│                                                                                  │
└─────────────────────────────────────────────────────────────────────────────────┘
```

> **Effect**: The Analyzer emits a new fatal event with `RecommendedAction_REPLACE_VM`. The stabilization window logic (similar to sticky XID) can be implemented as an Analyzer rule to prevent rapid re-alerting.

---

## 7. Device Disappearance Handling

### 7.1 Purpose

When the State Monitor detects a device has disappeared from `/sys/class/infiniband/`, this is treated as a **FATAL** condition requiring VM replacement.

### 7.2 Detection

Device disappearance is detected through three complementary mechanisms:

**Case 1: Runtime disappearance (monitor has in-memory or persisted state, same boot)**

The monitor tracks devices across polling cycles via an in-memory device set and a persisted `KnownDevices` list (see [Link Counter Detection, Section 6.6](/nvsentinel/components/nic-health-monitor/link-counter-detection#66-persistent-state-file)). If a previously-seen device is no longer present in `/sys/class/infiniband/`, a FATAL event is generated immediately with the exact device name.

This works both during normal operation (in-memory state from prior poll) and **after pod restart on the same boot** (persisted `KnownDevices` loaded from the state file). Without persistence, a device that disappeared while the pod was restarting would go undetected — the new pod would have no knowledge the device ever existed.

- Example: `mlx5_3` was in the persisted `KnownDevices`, but is absent from sysfs on startup → `EntityType: "NIC", EntityValue: "mlx5_3"`

**Case 2: Device missing after host reboot (boot ID changed — state cleared)**

On host reboot, all persisted state (including `KnownDevices`) is cleared because the node may have had NICs replaced (see [Link Counter Detection, Section 6.5](/nvsentinel/components/nic-health-monitor/link-counter-detection#65-boot-id-handling)). The monitor cannot compare against prior devices because they may be entirely different hardware. Device disappearance detection after reboot falls through to Case 3 (homogeneity check).

**Case 3: Device missing on startup (no persisted state — fresh node, post-reboot, or corrupt state file)**

On the **first poll cycle after startup with no persisted state**, the monitor uses the **card homogeneity check** (see Section 4.2) to detect anomalies without requiring prior state or static configuration. This covers fresh nodes, post-reboot startups (where state was cleared), and corrupt state files. After the first poll, all runtime state changes (cable pulls, link failures, recoveries) are handled by the per-port boundary-crossing transition detection, making repeated homogeneity checks unnecessary:

1. Group all monitored PF NICs by physical card (PCI `bus:device`)
2. Count active (`ACTIVE/LinkUp`) ports per card
3. Calculate the mode (most common active-port-count) across all cards
4. Any card with fewer active ports than the mode → FATAL event

This startup homogeneity check requires no persisted state and works immediately as a fallback. It detects missing ports by comparing against **peer NICs on the same node** rather than against a static expected count.

- Example: 8 single-port NIC cards, 7 are ACTIVE, 1 is DOWN → mode is 1, the DOWN card has 0 active → FATAL
- Message: "Card 0000:XX:00 has 0 active ports, expected 1 (peer mode)"

> **Why the homogeneity assumption is safe**: Compute fabric NICs are all the same model on GPU cluster nodes (DGX, HGX, or OEM). This approach works for both InfiniBand and Ethernet (RoCE) NICs. Management NICs on separate NUMA nodes are excluded before this check runs (see Section 4.1). For the mode to be incorrect, more than half of the NICs would need to be independently failed at startup — a probability of ~0.00003% for an 8-NIC system.

### 7.3 Event Classification

| Condition                                                  | Severity  | Recommended Action               |
|------------------------------------------------------------|-----------|----------------------------------|
| Device disappeared from `/sys/class/infiniband/` (runtime) | **FATAL** | **RecommendedAction_REPLACE_VM** |
| Card active ports below peer mode (startup/runtime)        | **FATAL** | **RecommendedAction_REPLACE_VM** |

> **Design Note**: All device disappearances are treated as FATAL because in production environments, unexpected device loss indicates a hardware issue requiring investigation and VM replacement. The monitor does not differentiate between "clean" removals (driver unload) and "dirty" removals (hardware crash).

---

## 8. SR-IOV Virtual Function Handling

### 8.1 Background: Why VFs Being DOWN is Expected

**SR-IOV (Single Root I/O Virtualization)** is a technology that allows a single physical NIC to appear as multiple virtual NICs. Understanding this is critical for correct alerting behavior.

> **Note**: Clusters with the **NVIDIA Network Operator** installed will have SR-IOV enabled by default. This applies to both **VM-based** and **baremetal container** environments. In baremetal Kubernetes with SR-IOV, unassigned VFs will still appear as DOWN — the filtering logic applies equally to both deployment types.

**The Problem Without Understanding SR-IOV:**
```
Monitor starts → Sees 34 devices → 16 are DOWN → Generates 16 FATAL alerts!
But... those 16 devices are supposed to be DOWN. False alarm storm!
```

**Why VFs are DOWN by default:**
When SR-IOV is enabled, Virtual Functions are pre-created by the driver but remain in DOWN state until they are:
1. Assigned to a VM or container via passthrough/device allocation
2. Administratively enabled (for InfiniBand, also requires Subnet Manager configuration)

Unassigned VFs are essentially "empty slots" waiting for workloads. A DOWN VF is not a hardware failure—it's normal SR-IOV behavior.

### 8.2 Key Terminology

| Term   | Full Name         | Description                                                           |
|--------|-------------------|-----------------------------------------------------------------------|
| **PF** | Physical Function | The "real" NIC controlled by the host OS. It should ALWAYS be ACTIVE. |
| **VF** | Virtual Function  | A "virtual clone" of the PF. Created for VMs/containers to use.       |

### 8.3 VF Lifecycle

```
STAGE 1: System Boot (SR-IOV Enabled)
├── PF created: mlx5_0 → ACTIVE (host uses it)
├── VFs created: mlx5_18, mlx5_19, ... → DOWN (waiting for assignment)
└── This is NORMAL - VFs are pre-provisioned resources. Their ports remain DOWN 
    until assigned to a workload (VM or container) and configured by the Subnet 
    Manager. This is standard SR-IOV behavior, not a hardware failure.

STAGE 2: VM Starts
├── Orchestrator assigns VF to VM: mlx5_18 → VM1
├── mlx5_18 state changes: DOWN → ACTIVE
└── VM now has dedicated NIC hardware

STAGE 3: VM Shuts Down
├── VF released back to pool: mlx5_18
├── mlx5_18 state changes: ACTIVE → DOWN
└── Ready for next VM - back to "parking spot" state
```

### 8.4 Alerting Decision Matrix

| Device Type | State    | Should Alert? | Reason                                |
|-------------|----------|---------------|---------------------------------------|
| PF          | ACTIVE   | No            | Normal operation                      |
| PF          | **DOWN** | **YES!**      | Real problem - host lost connectivity |
| VF          | DOWN     | **No**        | Normal - VF not assigned to any VM    |
| VF          | ACTIVE   | No            | Normal - VF assigned and in use       |

### 8.5 Auto-Detection: PF vs VF

The Linux kernel provides clear indicators in sysfs:

| Indicator                    | PF (Physical Function)      | VF (Virtual Function)        |
|------------------------------|-----------------------------|------------------------------|
| `device/physfn` symlink      | Does NOT exist              | EXISTS (points to parent PF) |
| `device/sriov_totalvfs` file | EXISTS (shows max VF count) | Does NOT exist               |

```
# PF Example (mlx5_0):
/sys/class/infiniband/mlx5_0/device/
├── sriov_totalvfs    ← EXISTS (value: 16 = can create 16 VFs)
└── (no physfn)       ← Doesn't exist

# VF Example (mlx5_18):
/sys/class/infiniband/mlx5_18/device/
├── (no sriov_totalvfs)  ← Doesn't exist
└── physfn → ../0000:93:00.1  ← EXISTS (points to parent PF)
```

### 8.6 Real Example from Field Validation (34-NIC System)

```
┌────────────────────────────────────────────────────────────────────────┐
│  Device      State    Type   Alert if DOWN?   Reason                   │
├────────────────────────────────────────────────────────────────────────┤
│  mlx5_0      ACTIVE   PF     YES              Host management NIC      │
│  mlx5_1      ACTIVE   PF     YES              RDMA data path           │
│  ...                                                                    │
│  mlx5_17     ACTIVE   PF     YES              RDMA data path           │
│  ─────────────────────────────────────────────────────────────────────  │
│  mlx5_18     DOWN     VF     NO               Unassigned, waiting      │
│  mlx5_19     DOWN     VF     NO               Unassigned, waiting      │
│  ...                                                                    │
│  mlx5_33     DOWN     VF     NO               Unassigned, waiting      │
└────────────────────────────────────────────────────────────────────────┘
```

### 8.7 Implementation

To determine if a `DOWN` state is expected, the monitor detects if a device is an SR-IOV Virtual Function (VF) or Physical Function (PF).

- **Method 1 (Primary)**: Check for `physfn` symlink in the device directory. If present, it's a VF.
- **Method 2 (Secondary)**: Check for `sriov_totalvfs` file. If present, it's a PF.

VFs are expected to be `DOWN` when unassigned. PFs are expected to be `ACTIVE`.

---

## 9. RoCE State Monitoring

RoCE (RDMA over Converged Ethernet) devices appear in **both** `/sys/class/net` and `/sys/class/infiniband`. The monitor accesses RoCE devices via the InfiniBand interface (`/sys/class/infiniband/`). The following monitoring applies to RoCE:

- **State monitoring**: `state`, `phys_state` (via InfiniBand sysfs interface)
- **Device identification**: Check `link_layer` file for "Ethernet"

### 9.1 GID Table Information (RoCE Routing Diagnostics)

The GID (Global Identifier) table is critical for RoCE routing. Each device exposes GIDs at:
- `/sys/class/infiniband/<dev>/ports/<port>/gids/<index>`
- `/sys/class/infiniband/<dev>/ports/<port>/gid_attrs/types/<index>`

**GID Types** ([Linux Kernel sysfs ABI](https://www.kernel.org/doc/Documentation/ABI/stable/sysfs-class-infiniband)):
- `IB/RoCE v1` = InfiniBand and RoCE v1 (GRH-based, layer 2)
- `RoCE v2` = RoCE v2 (UDP-encapsulated, layer 3, firewall-friendly)

At the API level (`ibv_gid_type`), there are three distinct types:
- `IBV_GID_TYPE_IB` (InfiniBand)
- `IBV_GID_TYPE_ROCE_V1` (RoCE v1)
- `IBV_GID_TYPE_ROCE_V2` (RoCE v2)

**Example GID table from 34-NIC system:**
```
DEV     PORT  INDEX  GID                                      IPv4           VER   DEV
mlx5_0  1     0      fe80:0000:0000:0000:ba3f:d2ff:fec3:65c4               v1    eth0
mlx5_0  1     1      fe80:0000:0000:0000:ba3f:d2ff:fec3:65c4               v2    eth0
mlx5_0  1     2      0000:0000:0000:0000:0000:ffff:0a33:ba20  10.51.186.32 v1    eth0
mlx5_0  1     3      0000:0000:0000:0000:0000:ffff:0a33:ba20  10.51.186.32 v2    eth0
mlx5_1  1     0      fe80:0000:0000:0000:ba3f:d2ff:fe7c:7570               v1    rdma4
mlx5_1  1     2      0000:0000:0000:0000:0000:ffff:ac10:0120  172.16.1.32  v1    rdma4
```

**Diagnostic value:**
- Empty GID table → `Error 61 (ENODATA)` during QP setup
- Missing IPv4 GIDs → routing issues for RoCE v2
- GID type mismatch between peers → connection failures

**Helper Functions:**
- `getGIDCount`: Enumerates `/sys/class/infiniband/<dev>/ports/<port>/gids/` to count valid GIDs.
- `getNetDevForIBDevice`: Discovers the network interface (e.g., `eth0`, `rdma4`) associated with an IB device by reading `/sys/class/infiniband/<dev>/device/net/`. This is critical for reading Ethernet statistics on RoCE devices.

---

## 10. Supported Hardware

> **Current Scope**: This initial implementation focuses on **Mellanox/NVIDIA InfiniBand and RoCE** devices only. The architecture is designed to be extensible for future support of additional NIC vendors.

| Vendor                 | Detection                              | State Monitoring  | Fatal Detection    |
|------------------------|----------------------------------------|-------------------|--------------------|
| **Mellanox (IB/RoCE)** | Device name `mlx5_*` or driver symlink | Yes - state files | State + PCI checks |

### 10.1 Future Work

- **AWS EFA Support**: Device names matching `rdmap\d+s\d+`
- **Plain Ethernet**: `operstate = down` detection via `/sys/class/net/<interface>/operstate`
- **TCPXO Support**: TCP Express Offload support

---

## 11. Data Structures

### 11.1 State Monitoring Structures

```go
// IBPort is the per-poll snapshot the state check reads from sysfs.
// Counter fields (e.g., link_downed) live in the degradation check and
// are documented in link-counter-detection.md.
type IBPort struct {
    Device        string `json:"device,omitempty"`         // e.g., "mlx5_0"
    Port          uint   `json:"port,omitempty"`           // Port number
    State         string `json:"state,omitempty"`          // raw sysfs value, e.g., "4: ACTIVE", "1: DOWN"
    PhysicalState string `json:"physical_state,omitempty"` // raw sysfs value, e.g., "5: LinkUp", "3: Disabled"
    LinkLayer     string `json:"link_layer,omitempty"`     // "InfiniBand" or "Ethernet"
}

// Device is the discovered NIC record. HCAType / FWVer are purely
// informational today; they are surfaced to the event message when
// useful but do not drive any classification.
type Device struct {
    Name      string   `json:"name"`       // e.g., "mlx5_0"
    Vendor    string   `json:"vendor"`     // e.g., "mellanox"
    HCAType   string   `json:"hca_type"`   // e.g., "MT4123"
    FWVersion string   `json:"fw_ver"`
    Ports     []IBPort `json:"ports"`
    IsVF      bool     `json:"is_vf"`      // true for SR-IOV Virtual Functions; these are skipped
    NetDev    string   `json:"net_dev,omitempty"` // associated net device for RoCE
}
```

### 11.2 Entity Model

NICs and Ports are modeled as separate entity types to enable precise fault localization:

| Entity Type | Entity Value Format | Example  | Use Case                                       |
|-------------|---------------------|----------|------------------------------------------------|
| `NIC`       | `<device_name>`     | `mlx5_0` | Device-level failures (disappeared, PCI error) |
| `NICPort`   | `<port_number>`     | `1`      | Port-level failures (DOWN, uncabled anomaly)   |

**Rationale**: A single NIC (e.g., `mlx5_0`) can have multiple ports. Port-level events include **both** the NIC and Port entities in `EntitiesImpacted`, enabling:
- Precise fault localization (NIC + Port together identify the exact failing component)
- Precise cable replacement (which port's cable is faulty)
- Targeted firmware diagnostics
- Accurate capacity planning (one failed port vs entire NIC)

---

## 12. Configuration

### 12.1 State Monitoring Configuration

Configuration is split between a ConfigMap mounted at
`/etc/nic-health-monitor/config.toml` (rendered TOML, sourced from the
Helm `values.yaml` shown below) and command-line flags that govern
runtime paths and polling cadence. Both surfaces are documented below.

**Helm values (YAML)** — covers sysfs mount points and device filtering:

```yaml
# Comma-separated regex patterns for NICs to exclude from discovery.
# Names matching any pattern are dropped before any classification runs.
nicExclusionRegex: "^veth.*,^docker.*,^br-.*,^lo$"

# OPTIONAL. When non-empty, bypasses automatic NIC discovery and monitors
# only IB device names matching these comma-separated regex patterns.
# The NUMA gate, topology classification, and NicExclusionRegex are all
# skipped — intended as an emergency override for operators who need to
# hand-pin a device list. Leave empty for the normal flow.
nicInclusionRegexOverride: ""

# sysfs mount points as seen inside the container. The monitor runs with
# the host's /sys bind-mounted under /nvsentinel/sys in the DaemonSet.
sysClassInfinibandPath: "/nvsentinel/sys/class/infiniband"
sysClassNetPath:        "/nvsentinel/sys/class/net"

# Counter detection settings live under `counterDetection:` — they are
# consumed by the counter PR and ignored by the state check.
counterDetection:
  enabled: true
  counters: [] # see link-counter-detection.md Section 10
```

**Command-line flags** — cover runtime wiring that changes per deployment:

| Flag                          | Default                                                                                       | Purpose                                                                                                                                                                                                            |
|-------------------------------|-----------------------------------------------------------------------------------------------|--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------|
| `--checks`                    | `InfiniBandStateCheck,InfiniBandDegradationCheck,EthernetStateCheck,EthernetDegradationCheck` | Comma-separated list of enabled checks. Unknown names are logged and skipped.                                                                                                                                      |
| `--config`                    | `/etc/nic-health-monitor/config.toml`                                                         | Path to the TOML ConfigMap shown above.                                                                                                                                                                            |
| `--metadata-path`             | `/var/lib/nvsentinel/gpu_metadata.json`                                                       | Path to the GPU metadata file produced by the metadata collector (see Section 12.2).                                                                                                                               |
| `--state-polling-interval`    | `1s`                                                                                          | Polling interval for state checks. Counter checks run on a fixed 1-second cadence regardless of this setting.                                                                                                      |
| `--platform-connector-socket` | `unix:///var/run/nvsentinel.sock`                                                             | gRPC target for the platform connector that receives health events.                                                                                                                                                |
| `--metrics-port`              | `2112`                                                                                        | HTTP port that exposes `/metrics` (Prometheus) and `/healthz`.                                                                                                                                                     |
| `--state-file`                | `/var/run/nic_health_monitor/state.json`                                                      | Path to the persistent state file (hostPath-backed JSON). Seeds previous-poll port state across pod restarts and emits healthy baselines after host reboots. Missing or corrupt files are treated as a fresh boot. |
| `--boot-id-path`              | `/nvsentinel/proc/sys/kernel/random/boot_id`                                                  | Path to the kernel boot ID file. Detects host reboots; state is cleared and healthy baselines emitted when the ID changes.                                                                                         |
| `--processing-strategy`       | `EXECUTE_REMEDIATION`                                                                         | Event processing strategy (`EXECUTE_REMEDIATION` or `STORE_ONLY`).                                                                                                                                                 |
| `--node-name`                 | `${NODE_NAME}`                                                                                | Node name stamped on every event. Falls back to the `NODE_NAME` env var; startup fails if unset.                                                                                                                   |

**GPU metadata** is a hard startup dependency — see [Section 4](#4-management-nic-exclusion-and-uncabled-port-detection) for the fail-fast conditions and [Section 12.2](#122-metadata-collector-requirements) for the required fields.

**SR-IOV Virtual Function handling**

VFs are detected via the `device/physfn` sysfs symlink and skipped
unconditionally. There is no configuration knob — unassigned VFs are
expected to stay DOWN by design and monitoring them would produce false
positives.

> **Note**: The previous `gpu_port_config` and `MonitorNetworkType` configuration options have been removed. Management NIC exclusion is automatic via NUMA detection (Section 4.1). NIC role classification uses the topo matrix published by the metadata collector (Section 4.2). Uncabled port detection uses the card homogeneity check (Section 4.3). Both InfiniBand and Ethernet (RoCE) NICs are monitored equally — no link layer filtering is required.

### 12.2 Metadata Collector Requirements

The NIC Health Monitor is a **hard consumer** of topology data produced by the NVSentinel metadata collector. The collector must run on every node before (or alongside) the NIC Health Monitor DaemonSet and must populate the following fields in `/var/lib/nvsentinel/gpu_metadata.json`:

| Field                | Type                   | Source                                                    | Used by                                                  |
|----------------------|------------------------|-----------------------------------------------------------|----------------------------------------------------------|
| `gpus[].pci_address` | string                 | NVML                                                      | Card grouping (PCI bus:device)                           |
| `gpus[].numa_node`   | int                    | `nvidia-smi topo -m` NUMA Affinity column (-1 if unknown) | Section 4.1 Management exclusion (builds `gpu_numa_set`) |
| `nic_topology`       | map\<string,string[]\> | `nvidia-smi topo -m` relationship matrix                  | Section 4.2 topo-based classification                    |

**`nic_topology` format**: Keys are InfiniBand device names (e.g., `mlx5_0`, `ibp3s0`). Values are a slice of topology-level strings — one entry per GPU listed in `gpus[]`, in the same order. Each entry is one of `"X"`, `"PIX"`, `"PXB"`, `"PHB"`, `"NODE"`, `"SYS"`, or `"NV<n>"` (an NVLink bond count). The collector publishes this matrix verbatim; interpretation is the NIC Health Monitor's responsibility.

**Example `gpu_metadata.json` excerpt**:

```json
{
  "version": "1.0",
  "node_name": "gpu-node-42",
  "gpus": [
    {"gpu_id": 0, "pci_address": "0000:0f:00.0", "numa_node": 0, "uuid": "...", "serial_number": "..."},
    {"gpu_id": 1, "pci_address": "0000:15:00.0", "numa_node": 1, "uuid": "...", "serial_number": "..."}
  ],
  "nic_topology": {
    "mlx5_0": ["SYS", "SYS"],
    "mlx5_1": ["PIX", "SYS"],
    "mlx5_2": ["SYS", "PIX"],
    "mlx5_8": ["NODE", "NODE"]
  }
}
```

**Ordering guarantee**: The NIC Health Monitor DaemonSet pod manifest must declare a dependency (via init container, readiness gate, or pod startup ordering) such that the metadata collector completes its write before the NIC monitor starts. If this ordering is violated, the NIC monitor will fail at startup with a clear error pointing at the missing file.

---

## 13. Event Management

### 13.1 State Event Construction

Events are emitted only on **health boundary crossings** — one consolidated event per port per transition. Logical state and physical state are combined into a single message.

**Example Event Fields (Fatal - IB Port DOWN):**

| Field             | Value                                                                                     |
|-------------------|-------------------------------------------------------------------------------------------|
| Agent             | `nic-health-monitor`                                                                      |
| CheckName         | `InfiniBandStateCheck`                                                                    |
| ComponentClass    | `NIC`                                                                                     |
| Message           | "Port mlx5_0 port 1: state DOWN, phys_state Disabled"                                     |
| IsFatal           | `true`                                                                                    |
| IsHealthy         | `false`                                                                                   |
| RecommendedAction | `REPLACE_VM`                                                                              |
| EntitiesImpacted  | `[{EntityType: "NIC", EntityValue: "mlx5_0"}, {EntityType: "NICPort", EntityValue: "1"}]` |

**Example Event Fields (Fatal - RoCE Port DOWN):**

| Field             | Value                                                                                     |
|-------------------|-------------------------------------------------------------------------------------------|
| Agent             | `nic-health-monitor`                                                                      |
| CheckName         | `EthernetStateCheck`                                                                      |
| ComponentClass    | `NIC`                                                                                     |
| Message           | "RoCE port mlx5_0 port 1: state DOWN, phys_state Disabled, operstate down"                |
| IsFatal           | `true`                                                                                    |
| IsHealthy         | `false`                                                                                   |
| RecommendedAction | `REPLACE_VM`                                                                              |
| EntitiesImpacted  | `[{EntityType: "NIC", EntityValue: "mlx5_0"}, {EntityType: "NICPort", EntityValue: "1"}]` |

**Example Event Fields (Healthy - Recovery):**

| Field             | Value                                                                                     |
|-------------------|-------------------------------------------------------------------------------------------|
| Agent             | `nic-health-monitor`                                                                      |
| CheckName         | `InfiniBandStateCheck`                                                                    |
| ComponentClass    | `NIC`                                                                                     |
| Message           | "Port mlx5_0 port 1: healthy (ACTIVE, LinkUp)"                                            |
| IsFatal           | `false`                                                                                   |
| IsHealthy         | `true`                                                                                    |
| RecommendedAction | `NONE`                                                                                    |
| EntitiesImpacted  | `[{EntityType: "NIC", EntityValue: "mlx5_0"}, {EntityType: "NICPort", EntityValue: "1"}]` |

**Example Event Fields (Fatal - Device Disappeared):**

| Field             | Value                                                                   |
|-------------------|-------------------------------------------------------------------------|
| Agent             | `nic-health-monitor`                                                    |
| CheckName         | `InfiniBandStateCheck`                                                  |
| ComponentClass    | `NIC`                                                                   |
| Message           | "NIC mlx5_0 disappeared from /sys/class/infiniband/ - hardware failure" |
| IsFatal           | `true`                                                                  |
| IsHealthy         | `false`                                                                 |
| RecommendedAction | `REPLACE_VM`                                                            |
| EntitiesImpacted  | `[{EntityType: "NIC", EntityValue: "mlx5_0"}]`                          |

---

## Appendix A: Quick Reference - Fatal Condition Classification

The key question: **"Will the workload fail because of this?"**

### Fatal State Conditions (IsFatal = true)

| Condition                     | Recommended Action               | Rationale                                                  |
|-------------------------------|----------------------------------|------------------------------------------------------------|
| **NIC state = DOWN**          | **RecommendedAction_REPLACE_VM** | No network connectivity, workloads will timeout            |
| **Device disappeared**        | **RecommendedAction_REPLACE_VM** | Hardware failure, immediate job failure                    |
| **phys_state = Disabled**     | **RecommendedAction_REPLACE_VM** | Port disabled, no communication possible                   |
| **Uncabled port anomaly**     | **RecommendedAction_REPLACE_VM** | Card has fewer active ports than peers (homogeneity check) |
| **Port flapping (3+ cycles)** | **RecommendedAction_REPLACE_VM** | Intermittent hardware/cable instability                    |

### Non-Fatal State Conditions (IsFatal = false)

| Condition                          | Recommended Action         | Rationale                                                                                  |
|------------------------------------|----------------------------|--------------------------------------------------------------------------------------------|
| **phys_state = LinkErrorRecovery** | **RecommendedAction_NONE** | HCA firmware actively retrying; escalated to fatal by card homogeneity check if persistent |
| **phys_state = Polling**           | **RecommendedAction_NONE** | Transient link training; escalated to fatal by card homogeneity check if persistent        |

### Fatal Counters (IsFatal = true)

| Counter                           | Threshold           | Recommended Action               |
|-----------------------------------|---------------------|----------------------------------|
| `link_downed`                     | Delta > 0 (runtime) | **RecommendedAction_REPLACE_VM** |
| `excessive_buffer_overrun_errors` | > 0 (any)           | **RecommendedAction_REPLACE_VM** |
| `local_link_integrity_errors`     | > 0 (any)           | **RecommendedAction_REPLACE_VM** |
| `rnr_nak_retry_err`               | > 0 (any)           | **RecommendedAction_REPLACE_VM** |

### Driver/Firmware Logs

For kernel log pattern details (fatal and non-fatal classifications, regex patterns, log line examples, and kernel source references), see [Syslog Detection & Correlation](/nvsentinel/components/nic-health-monitor/syslog-detection-and-correlation). This document focuses on link state detection; syslog monitoring is covered in its own dedicated document to keep each document focused on a single problem.

### State Detection Paths

| Condition                        | Recommended Action               | Path/Source                                                                                                     |
|----------------------------------|----------------------------------|-----------------------------------------------------------------------------------------------------------------|
| `state = DOWN`                   | **RecommendedAction_REPLACE_VM** | `/sys/class/infiniband/<dev>/ports/<port>/state`                                                                |
| `phys_state = Disabled`          | **RecommendedAction_REPLACE_VM** | `/sys/class/infiniband/<dev>/ports/<port>/phys_state`                                                           |
| `phys_state = LinkErrorRecovery` | **RecommendedAction_NONE**       | `/sys/class/infiniband/<dev>/ports/<port>/phys_state` (non-fatal; escalated by homogeneity check if persistent) |
| Uncabled port anomaly            | **RecommendedAction_REPLACE_VM** | Card homogeneity check (PCI card grouping + mode)                                                               |
| Device disappeared               | **RecommendedAction_REPLACE_VM** | Device enumeration in `/sys/class/infiniband/`                                                                  |

---

## References

1. [Linux Kernel sysfs-class-infiniband documentation](https://www.kernel.org/doc/Documentation/ABI/stable/sysfs-class-infiniband)
2. [DGX A100 User Guide](https://docs.nvidia.com/dgx/dgxa100-user-guide/introduction-to-dgxa100.html)
3. [DGX H100 User Guide](https://docs.nvidia.com/dgx/dgxh100-user-guide/introduction-to-dgxh100.html)
4. [DGX B200 User Guide](https://docs.nvidia.com/dgx/dgxb200-user-guide/introduction-to-dgxb200.html)
5. [GB200 NVL2](https://www.nvidia.com/en-us/data-center/gb200-nvl2/)

---