Skip to navigation

ExecuteColdReboot

View as MarkdownOpen in Claude

ExecuteColdReboot orchestrates the full DGX GB200 rack COLD reboot sequence on caller-supplied nodes (no inventory registration required): gracefully shut down the compute trays over BMC, power off the power shelves, wait for capacitor discharge, power the shelves back on, wait for the compute/switch tray BMCs and switch NVOS to come up, then power on the compute nodes. Returns a coordinator job ID immediately; poll GetJobStatus on it: while running, execution_state is RUNNING and state_description reports the current stage by its rack-reboot runbook step number(s) (e.g. “Rack reboot step 7-8: …”); on completion or failure the full per-stage stage timeline is written to result_json. Runbook steps 9 (switch fabric provisioning) and 13 (post-reboot host/GPU verification) are out of scope. The sequence is fail-fast with no automated rollback.

ExecuteColdRebootRequest

Request
This endpoint expects an object.
_domainstring
_prestage_shutdown_floor_secondsuint
_prestage_shutdown_poll_max_secondsuint
_discharge_floor_secondsuint
_discharge_poll_max_secondsuint
_bmc_up_floor_secondsuint
_bmc_up_poll_max_secondsuint
_nvos_hello_backoff_secondsuint
_compute_boot_wait_secondsuint
_poll_interval_secondsuint
nodesobject

Participating devices: compute + power-shelf + switch trays (full NodeInfo)

ExecuteColdRebootResponse

Response
This endpoint returns an object.
responseobject

response.job_id is the coordinator job ID for GetJobStatus