Configuration

View as Markdown

You configure the collector through your Helm values file. This page covers each part of it, in the order you’d fill it in. Installation has a complete minimal example, and values.yaml lists every setting with its default.

Passwords never go in the values file. They live in a separate BMC credentials file that you store in a Kubernetes Secret, and the chart only references it.

Targets

List one entry under inventory.targets for each BMC. The collector and NICo hardware health both read this list.

inventory:
computeZone: us-west-dc1
nodeGroup: gb200-training
labels:
site: dc1
targets:
- kind: compute
name: node-01
address: 192.0.2.10
mac: "00:11:22:33:44:55"
credentialsProfile: bmc
labels:
rack: rack-12
- kind: nvswitch
name: switch-tray-01
address: 192.0.2.11
mac: "02:00:0a:00:00:0b"
credentialsProfile: switch
- kind: power_shelf
name: power-shelf-01
address: 192.0.2.12
port: 8443
mac: "02:00:0a:00:00:0c"
credentialsProfile: bmc

You need at least one target. The chart rejects fields it doesn’t recognize, so a typo fails the install instead of being ignored.

FieldRequiredDescription
addressYesIPv4 or IPv6 address of the BMC, with no scheme or port.
macYesMAC address of the BMC. See target identity.
portNoRedfish port. Defaults to the HTTPS port.
kindNocompute, nvswitch, power_shelf, or unknown (the default).
nameNoDisplay name, shown as the inventory name and the NICo machine_name label.
credentialsProfileNoProfile to use from the credentials file. Optional only when a MAC override supplies the credentials.
computeZoneNoOverrides inventory.computeZone for this target. See placement.
nodeGroupNoOverrides inventory.nodeGroup for this target.
labelsNoExtra telemetry labels for this target. See labels.

These settings apply to every target unless the target overrides them:

FieldDescription
inventory.computeZoneDefault compute zone.
inventory.nodeGroupDefault node group.
inventory.labelsLabels for every target. A target label with the same key wins.

Target identity

Fleet Intelligence recognizes a machine by its BMC MAC address, not its IP address. That keeps inventory, attestation, and telemetry for the same machine together even if its IP changes, so every target needs its real BMC MAC.

Write the MAC with colons (00:11:22:33:44:55), hyphens, or no separators, in any letter case. Quote it in YAML. Fleet Intelligence shows it as uppercase with colons. Two targets with the same MAC, however it is spelled, are rejected as duplicates.

Placement

computeZone and nodeGroup place each machine in a Fleet Intelligence compute zone and node group. Use the exact names configured in your Fleet Intelligence account; the values on this page are only examples. A compute zone is typically a location or failure domain, such as us-west-dc1. A node group is typically a pool of similar hardware or workloads, such as gb200-training.

Set them under inventory when every target shares the same placement, and override them on any target that differs:

inventory:
computeZone: us-west-dc1
nodeGroup: gb200-training
targets:
- name: node-01
address: 192.0.2.10
mac: "02:00:0a:00:00:0a"
credentialsProfile: bmc
- name: node-02
address: 192.0.2.11
mac: "02:00:0a:00:00:0b"
credentialsProfile: bmc
computeZone: us-west-dc2
nodeGroup: gb200-inference

Here node-01 uses the shared values, while node-02 is in us-west-dc2 and gb200-inference. If neither place sets a value, the machine is sent without it.

The collector sends placement with the inventory and adds it to telemetry as the compute_zone and node_group labels. Custom labels such as site stay labels; they don’t set placement.

Labels

Labels are added to NICo telemetry for each target.

  • Keys must match [a-zA-Z_][a-zA-Z0-9_]*.
  • Each target can have up to 32 labels. That count includes the labels added automatically: oob="true", plus machine_name, compute_zone, and node_group when name, computeZone, and nodeGroup are set.
  • Label values, and the name, computeZone, and nodeGroup fields, can be up to 1,024 bytes. Those three fields are trimmed and can’t be blank when set.
  • You can’t use reserved names: the four labels above, and the labels NICo sets itself, such as bmc_ip, endpoint_mac, gpu_uuid, machine_id, and system_uuid. The full list is RESERVED_NICO_LABELS in the configuration source.

Helm checks key syntax when you install. The remaining rules are checked when the collector and NICo’s init container load the configuration, so a violation shows up as a failed pod.

BMC credentials file

The credentials file holds named profiles and per-BMC overrides, keyed by MAC address:

{
"profiles": {
"bmc": { "username": "admin", "password": "replace-with-bmc-password" },
"switch": { "username": "switch-admin", "password": "replace-with-switch-password" }
},
"overrides": {
"02:00:0a:00:00:0b": { "password": "replace-with-target-password" }
}
}

Store it in a Kubernetes Secret, either by hand or from Vault or OpenBao, and point the chart at it:

credentials:
existingSecret: fleet-intelligence-bmc-credentials
secretKey: credentials.json

The chart mounts the file into the collector and NICo at /run/secrets/bmc/credentials.json. A complete example is in credentials.example.json.

How credentials are resolved

For each BMC, the collector and NICo look up each field (username, password) in this order:

  1. The override for that BMC’s MAC, if there is one.
  2. The profile named in the target’s credentialsProfile.

A field that is missing or null in the override comes from the profile. An empty string "" is a real value: it is used as-is and doesn’t fall back to the profile. There is no default profile.

Every target must end up with a username. If neither source sets a password, the password is empty.

Override keys follow the same MAC rules as targets: any separator or case works, and two keys for the same MAC are rejected.

The collector rejects a credentials file with unknown fields, invalid MACs, malformed JSON, unknown profile names, or a target without a username. Error messages never include credential values.

When credential changes take effect

You can change passwords without restarting anything: the collector and NICo both re-read the file. See rotation for timing and for what does need a restart.

Fleet Intelligence connection

backend:
url: https://data.fleet-intelligence.nvidia.com
agentToken:
existingSecret: fleet-intelligence-oob-collector-agent-token
secretKey: agent-token

backend.url defaults to the production endpoint shown above. Change it only if you use a different Fleet Intelligence endpoint. Use the API’s base address, without a path such as /v1/agent. The URL can’t contain a username, password, query string, or fragment.

backend.agentToken points to the Secret that holds the bootstrap token. The collector and the bundled gateway both use it.

Components and telemetry

By default, the chart runs the collector, NICo hardware health, and a gateway that forwards NICo’s metrics and logs to Fleet Intelligence. Each has an enabled switch:

To runSet
Everything (default)Nothing
Inventory and attestation onlynicoHardwareHealth.enabled: false and otelGateway.enabled: false
Health telemetry onlybmcCollector.enabled: false
NICo with your own OTLP/gRPC collectortelemetry.endpoint (an http:// or https:// URL) and otelGateway.enabled: false

The gateway requires NICo.

NICo defaults to automatic log collection: it starts with Redfish SSE streaming, falls back to periodic polling when SSE is unavailable or keeps failing, and retries SSE after 30 minutes of polling. You can select fixed SSE streaming or periodic polling with nicoHardwareHealth.config.logsMode. It sends metrics and logs in batches of up to 512 records, at least every two seconds.

NICo collection controls

Set these optional values under nicoHardwareHealth.config. Workload settings such as image, resources, and scheduling remain under nicoHardwareHealth. Omitted or null settings use the defaults below, including on native installations without a [nico_health] section. Timing settings alone preserve each collector’s enabled state: metrics, telemetry reports, firmware, and the iteration limiter require their corresponding *Enabled: true setting to start. TCP reachability checks are enabled by default; set reachabilityEnabled: false to disable them. Logs default to auto mode with SSE recovery enabled.

Setting under nicoHardwareHealth.configDefaultDescription
bmcRequestConcurrency2Shared maximum concurrent Redfish operations per BMC.
endpointDiscoveryIntervalSeconds300Interval between endpoint reconciliation iterations.
discoveryRefreshIntervalSeconds3600Interval between Redfish entity-tree discovery iterations.
discoveryConcurrency4Concurrent endpoint identity resolutions.
sensorFetchIntervalSeconds60Interval between sensor fetch iterations.
sensorsEnabledtrueCollect sensor readings.
includeSensorThresholdstrueInclude thresholds in sensor attributes.
leakDetectorEnabledtrueQuery thermal-subsystem leak detectors.
leakDetectorPollIntervalSeconds60Interval between leak-detector polls.
leakDetectorStateRefreshIntervalSeconds1800Interval between leak-detector discovery refreshes.
logsEnabledtrueCollect BMC logs.
logsModeautosse, periodic, or auto (SSE with per-endpoint polling fallback).
logsSseInitialBackoffSeconds1Initial reconnect backoff, before jitter.
logsSseMaxBackoffSeconds30Maximum reconnect backoff, before jitter.
logsCollectionIntervalSeconds300Interval between log polls in periodic mode or auto fallback.
logsStateRefreshIntervalSeconds1800Interval between log-service discovery refreshes.
logsExcludeServices["Journal"]Skip LogServices whose resource IDs contain any listed substring; [] includes every service.
logsSkipInitialHistoryfalseSkip retained history on the first successful baseline without a checkpoint.
logsAutoSseNotAvailableThreshold1Unsupported-SSE attempts before falling back to polling.
logsAutoConnectFailureWindowSeconds300Window for counting SSE connection failures.
logsAutoConnectFailureThreshold5Connection failures within that window before falling back.
logsAutoRetrySseAfterDowngradetrueIn auto mode, retry SSE after 30 minutes of polling fallback. Set false to remain in polling mode.
metricsEnabledfalseCollect Redfish entity metrics.
metricsFetchIntervalSeconds120Interval between entity-metric iterations.
telemetryEnabledfalseCollect Redfish TelemetryService reports.
telemetryFetchIntervalSeconds60Interval between report-fetch iterations.
firmwareEnabledfalseCollect firmware inventory in NICo.
firmwareRefreshIntervalSeconds7200Interval between firmware iterations.
managerEnabledtruePoll Manager status for NICo power-shelf endpoints.
managerPollIntervalSeconds300Interval between eligible Manager polls.
reachabilityEnabledtrueProbe eligible endpoint TCP ports.
reachabilityIntervalSeconds60Interval between TCP probe cycles.
reachabilityTimeoutSeconds3Timeout for one TCP connection attempt.
reachabilityLogModeunreachableLog failed probes (unreachable) or every probe (all).
rateLimitEnabledfalseEnable NICo’s global collector-iteration token bucket.
rateLimitBucketBurst100Collector iterations admitted in a burst.
rateLimitBucketReplenishMilliseconds30Interval between token replenishments.
rateLimitMaxJitterMilliseconds50Maximum token-bucket jitter; 0 disables this jitter.

For example:

nicoHardwareHealth:
config:
sensorFetchIntervalSeconds: 120
bmcRequestConcurrency: 2
leakDetectorPollIntervalSeconds: 120
logsSseMaxBackoffSeconds: 60

Integer controls accept 1 through 4294967295; rateLimitMaxJitterMilliseconds also accepts 0. SSE maximum backoff must be at least its initial backoff. Explicit false, zero jitter, and empty exclusion arrays are preserved.

Controls apply to all NICo targets, independently of inventory and attestation. Polling intervals are waits between iterations. Each collector runs independently, so disabling sensors leaves discovery for GPU identity and other enabled collectors active. Established SSE streams release their concurrency slot after the handshake. The global limiter counts collector iterations, not HTTP requests.

Auto fallback uses the configured log-polling fields. Mode changes can replay or miss records when SSE and LogService histories differ; temporary checkpoints can be lost on pod replacement or native directory cleanup. Manager polling requires power-shelf metadata and stays inactive for the renderer’s generic endpoints.

Apply with helm upgrade, or use flat snake_case fields under [nico_health] and restart fleetint-nico-health.service on native installations.

Collection settings

SettingDefaultDescription
bmcCollector.intervalSeconds86400Wait time after one collection cycle ends before the next starts (24 hours).
bmcCollector.targetConcurrency64Number of BMCs collected at the same time.
bmcCollector.redfish.maxInFlight2Maximum simultaneous requests to one BMC.
bmcCollector.redfish.requestsPerSecond10Maximum request rate to one BMC. Short bursts up to the same number are allowed.
bmcCollector.redfish.timeoutSeconds30Redfish request timeout.
bmcCollector.redfish.insecureTlstrueSkip BMC certificate verification. See TLS.
bmcCollector.latencyProbe.enabledtrueMeasure network latency to each BMC.

These limits apply to the collector only. NICo makes its own requests to the BMCs on its own schedule. The two concurrency limits are independent, so inventory and NICo can each issue two requests to the same BMC at once with the defaults. See request limits for how they work together.

Workload settings

Every workload (bmcCollector, nicoHardwareHealth, and otelGateway) accepts enabled, image, resources, nodeSelector, tolerations, affinity, podAnnotations, and logLevel. otelGateway.replicas sets the number of gateway replicas.

NICo application logging defaults to warn to suppress routine per-reading messages. Set nicoHardwareHealth.logLevel to info or debug when investigating collection. This setting controls application log verbosity; BMC event log collection and telemetry export continue independently.

Collector and NICo image tags default to the chart version. If you pull images through a private registry mirror, set imagePullSecrets.

Reported collector behavior

With each inventory upload, the collector reports its version and the settings it is running with, such as the collection interval, request limits, and which telemetry components are enabled. The report never includes secrets, credential references, or URLs. It describes configuration, not whether those components are healthy.

collector.config.nicoHealth reports explicitly configured controls in camelCase from each cycle’s [nico_health] snapshot. Omitted controls stay omitted. These are configured values; checking what NICo has loaded requires checking that service after a restart.

NICo reports also include enabled, logLevel, and telemetryDestination. Pod settings such as image, resources, and scheduling stay in Helm. Component reports require explicit deployment metadata, supplied by Helm or native service.conf; a manually started collector without it omits those reports.

Proxy and TLS

To send traffic through an HTTP proxy, enable proxy and set the proxy URLs. They must be reachable from the cluster and can’t contain credentials.

proxy:
enabled: true
httpsProxy: http://proxy.example.com:3128
noProxy: localhost,127.0.0.1,.svc,.cluster.local

proxy also accepts httpProxy and allProxy. The default noProxy keeps local and in-cluster traffic off the proxy; if you change it, keep those entries.

bmcCollector.redfish.insecureTls defaults to true, turning off BMC certificate checks for the collector. Set it to false to verify BMC certificates. It doesn’t change how the collector verifies the Fleet Intelligence backend. NICo doesn’t verify BMC certificates, whatever this setting is.