Networking Planning and Design#
Network architecture planning for GB200 and GB300 systems following the SuperPOD reference design framework. The majority of networking requirements are comprehensively addressed in the Ethernet reference documentation. The SuperPOD reference design for GB200/GB300 adopts an EVPN Multihoming VXLAN architecture with Head-End Replication for North-South networking, leveraging symmetric routing for optimal traffic flow. Additional supporting information is provided in this document.
Figure 3 GB200/GB300 EVPN w/ Head-End Replication#
EVPN Symmetric routing with Cumulus Linux: Each VTEP automatically uses a unique MAC address by default.
Pros |
Cons |
|---|---|
Simple — each VTEP uses its own MAC. No coordination required for a shared address. Easier to troubleshoot per-node traffic. |
When a host MAC moves (e.g. failover), remote VTEPs must update their MAC tables for the new VTEP’s MAC. |
North-South Ethernet Networking#
Data and OOB prefix layout#
Networks are allocated from a data prefix (in-band and related subnets) and an OOB prefix (out-of-band management). Example root ranges appear in the table titles; use your site’s actual prefixes. Sizes, VLAN IDs, and names are reference examples—align all values with your design and BCM configuration.
Network |
Size |
VLAN |
Purpose |
|---|---|---|---|
internalnet |
/24 |
100 |
InBand (data) control plane |
dgxnet[1-n] |
/25 |
10[1-n] |
Group of 4 GB200 racks |
dgxnet[1-n] |
/24 |
10[1-n] |
Group of 8 GB300 racks |
inband_loopbacks |
/27 |
— |
Loopbacks for inband VRFs |
Network |
Size |
VLAN |
Purpose |
|---|---|---|---|
ipminet0 |
/23 |
201 |
Primary OOB, switch eth0 |
ipminet1 |
/22 |
202 |
DGX BMC, IB switch COMe |
oob_loopbacks |
/27 or /26 |
— |
OOB VRF loopback pool |
ipminet2 |
/25 |
203 |
Secondary control plane OOB |
Subnetting Breakout#
For subnetting breakout based on DGX system type and scale unit, refer to the Network Breakdown IP Plan Subnetting Calculator.
Ethernet Planning#
This section provides a comprehensive guide for planning and designing the Ethernet networking for the GB200/GB300 SuperPOD.
Verify the hardware components for accuracy in model and quantity#
Ethernet switches (SN5600)
Transceivers (optical)
Cables (DAC / AOC)
Required NVLink Switch (NVOS) Version#
The Software Bill of Materials (SBOM) for your Mission Control release lists the required NVLink Switch (NVOS) version.
Confirm Required Cumulus Linux Software Version#
The SBOM for your Mission Control release lists the required Cumulus Linux version.
Obtain Customer Network Requirements#
Content/Consideration List#
Customer-Edge to Cluster connectivity
Transceiver type, compatibility and HW order status
Electrical signaling/encoding (NRZ vs PAM4)
Speed/Bandwidth
Uplink Quantity (transceiver, cable, fiber)
IP Addressing - P2P Uplinks
Routing protocol (default: BGP)
EVPN Planning Stage#
VRF / VLAN / VNI Mapping#
Per scalable unit, InBand and OOB VLANs require L3VNIs. VRF-level identifiers are summarized in the following table.
VRF Type |
L3VNI |
L3VNI VLAN |
Purpose |
Route leaked within VRF |
|---|---|---|---|---|
OOB |
10010 |
1001 |
OOB control plane |
Import EXIT (optional) |
INBAND |
200100 |
2001 |
InBand data control plane and DGX |
Import EXIT (required) |
STORAGE |
400100 |
RoCEv2 high-speed storage |
||
EXIT |
Edge routing to external switches |
|
Cluster Route Advertisement and External Reachability#
Cluster Route Advertisement and External Reachability is checked for the following components:
BMS Connectivity - Data Center Environment Monitoring
3rd Party Appliance Connectivity Requirements (Storage, etc.)
Physical Connectivity (Type, Speed, etc.)
Logical Connectivity (L2, Bond, L3, etc.)
IP Addressing
Preparation Information Requirements#
The following information is required for the preparation:
Obtain the factory rack inventory file. Refer to Appendix Section 3 for an example.
Coordinate with the factory to generate copies of the serial and MAC address files for racks being shipped.
The rack inventory is essential for mapping MAC addresses to IP allocations; otherwise, this data would need to be collected manually per NIC, which is time-consuming.
“Factory File” Available from Manufacturing Partner
Includes component level MAC/Interface/SN/PN Information:
GB200/GB300 compute tray
NVLink Switch
MGX Rack Power Shelf
SN2201
Gather MACs#
Host: BMC + N/S Provisioning Interfaces
Mgmt Servers (control plane)
UFM Servers
NetQ servers
Switch: Mgmt interface (mgmt. or eth0)
Ethernet
PDUs: Mgmt interface (mgmt. or eth0)
Point-to-Point Cabling Connectivity Plan (Required)