PowerShelf Platform Update Examples#
NVFWUPD 2.0.9 introduces support for PowerShelf platforms from Delta and LiteOn manufacturers. Firmware updates are performed using Redfish APIs.
Supported PowerShelf Platforms#
PowerShelf platforms from various manufacturers are supported, including:
Delta PowerShelf: Delta power distribution and management systems
LiteOn PowerShelf: LiteOn power distribution and management systems
All PowerShelf platforms use the same servertype: Powershelf
Displaying Current PowerShelf Firmware Versions#
To display the current firmware versions on a PowerShelf platform, use the show_version command with servertype Powershelf:
Example 1: Delta PowerShelf#
$ nvfwupd -t ip=<PowerShelf BMC IP> user=***** password=***** servertype=Powershelf show_version -p nvidia-pmc-3.2.3-RELEASE.FOR.UPDATE.CEC-CFG.fwpkg
System Model: AHE50V660A33KWL
Part number: ECD68000091
Serial number: THASQ25220015
Packages: ['3.2.3']
Connection Status: Successful
Firmware Devices:
AP Name Sys Version Pkg Version Up-To-Date
------- ----------- ----------- ----------
FW_ERoT_BMC_0 1203 N/A No
FW_PMC_alt 3.2.4 3.2.3 Yes
FW_PMC_primary 3.2.4 3.2.3 Yes
FW_PSU_1 01050105 N/A No
FW_PSU_2 01050105 N/A No
FW_PSU_3 01050105 N/A No
FW_PSU_4 01050105 N/A No
FW_PSU_5 01050105 N/A No
FW_PSU_6 01050105 N/A No
----------------------------------------------------------
Error Code: 0
Example 2: LiteOn PowerShelf#
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** servertype=Powershelf show_version -p cm14mp2rd-r1.3.9-rc1.tar
System Model: PF-1333-13RD
Part number: PF-1333-13RD
Serial number: 6133313RD01X1528174
Packages: ['LiteOnPMCImages/cm14mp2rd-r1.3.9-rc1.tar']
Connection Status: Successful
Firmware Devices:
AP Name Sys Version Pkg Version Up-To-Date
------- ----------- ----------- ----------
mcu 0 N/A No
pmc_86ae677a r1.3.9 r1.3.9-rc1 No
powerdevice0 0x1 / 0x1 N/A No
powerdevice1 0x1 / 0x1 N/A No
powerdevice2 0x1 / 0x1 N/A No
powerdevice3 0x1 / 0x1 N/A No
powerdevice4 0x1 / 0x1 N/A No
powerdevice5 0x1 / 0x1 N/A No
----------------------------------------------------------
Error Code: 0
Updating PowerShelf Firmware#
To update components on a PowerShelf platform, run the update_fw command without specifying individual targets:
LiteOn PMC Update:
LiteOn PMC updates begin immediately and return a task id that cannot be used to monitor the update progress as the PMC becomes unresponsive until the update is complete.
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** servertype=Powershelf update_fw -p cm14mp2rd-r1.3.9-rc1.tar
Updating ip address: ip=XXXX
FW package: ['LiteOnPMCImages/cm14mp2rd-r1.3.9-rc1.tar']
Ok to proceed with firmware update? <Y/N>
y
FW update started, Task Id: 1
Firmware update in progress
use show_update_progress command to monitor the progress
------------------------------------------------------------------------------------------------------------------------
Error Code: 0
~ Wait approximately 20 minutes for the PMC update to complete.
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** servertype=Powershelf show_version -p cm14mp2rd-r1.3.9-rc1.tar
System Model: PF-1333-13RD
Part number: PF-1333-13RD
Serial number: 6133313RD01X1528174
Packages: ['LiteOnPMCImages/cm14mp2rd-r1.3.9-rc1.tar']
Connection Status: Successful
Firmware Devices:
AP Name Sys Version Pkg Version Up-To-Date
------- ----------- ----------- ----------
mcu 0 N/A No
pmc_86ae677a r1.3.9-rc1 r1.3.9-rc1 Yes
powerdevice0 0x1 / 0x1 N/A No
powerdevice1 0x1 / 0x1 N/A No
powerdevice2 0x1 / 0x1 N/A No
powerdevice3 0x1 / 0x1 N/A No
powerdevice4 0x1 / 0x1 N/A No
powerdevice5 0x1 / 0x1 N/A No
----------------------------------------------------------
Error Code: 0
Delta PMC Update:
Delta PMC updates may be initially monitored using the show_update_progress command with task ID, but eventually the PMC will become unresponsive after performing an auto reboot for activation.
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** show_version -p DeltaPR3PSUS/nvidia-pmc-3.2.3-RELEASE.FOR.UPDATE.CEC-CFG.fwpkg
System Model: AHE50V660A33KWL
Part number: ECD68000091
Serial number: THASQ25220015
Packages: ['3.2.3']
Connection Status: Successful
Firmware Devices:
AP Name Sys Version Pkg Version Up-To-Date
------- ----------- ----------- ----------
FW_ERoT_BMC_0 1203 N/A No
FW_PMC_alt 3.2.4 3.2.3 Yes
FW_PMC_primary 3.2.4 3.2.3 Yes
FW_PSU_1 01050105 N/A No
FW_PSU_2 01050105 N/A No
FW_PSU_3 01050105 N/A No
FW_PSU_4 01050105 N/A No
FW_PSU_5 01050105 N/A No
FW_PSU_6 01050105 N/A No
----------------------------------------------------------
Error Code: 0
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** update_fw -p DeltaPR3PSUS/nvidia-pmc-3.2.3-RELEASE.FOR.UPDATE.CEC-CFG.fwpkg
Updating ip address: ip=XXXX
FW package: ['DeltaPR3PSUS/nvidia-pmc-3.2.3-RELEASE.FOR.UPDATE.CEC-CFG.fwpkg']
Ok to proceed with firmware update? <Y/N>
y
FW update started, Task Id: 3
Firmware update in progress
use show_update_progress command to monitor the progress
------------------------------------------------------------------------------------------------------------------------
Error Code: 0
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** show_update_progress -i 3
Task Info for Id: 3
StartTime: 2024-05-02T15:45:44+00:00
TaskState: Running
PercentComplete: 49
TaskStatus: OK
Overall Task Status: {
"@odata.id": "/redfish/v1/TaskService/Tasks/3",
"@odata.type": "#Task.v1_7_4.Task",
"HidePayload": false,
"Id": "3",
"Messages": [
{
"@odata.type": "#Message.v1_1_1.Message",
"Message": "The task with Id '3' has started.",
"MessageArgs": [
"0"
],
"MessageId": "TaskEvent.1.0.3.TaskStarted",
"MessageSeverity": "OK",
"Resolution": "None."
},
{
"@odata.type": "#Message.v1_1_1.Message",
"Message": "The task with Id '3' has changed to progress 10 percent complete.",
"MessageArgs": [
"0",
"10"
],
"MessageId": "TaskEvent.1.0.3.TaskProgressChanged",
"MessageSeverity": "OK",
"Resolution": "None."
},
{
"@odata.type": "#Message.v1_1_1.Message",
"Message": "The task with Id '3' has changed to progress 23 percent complete.",
"MessageArgs": [
"0",
"23"
],
"MessageId": "TaskEvent.1.0.3.TaskProgressChanged",
"MessageSeverity": "OK",
"Resolution": "None."
},
{
"@odata.type": "#Message.v1_1_1.Message",
"Message": "The task with Id '3' has changed to progress 36 percent complete.",
"MessageArgs": [
"0",
"36"
],
"MessageId": "TaskEvent.1.0.3.TaskProgressChanged",
"MessageSeverity": "OK",
"Resolution": "None."
},
{
"@odata.type": "#Message.v1_1_1.Message",
"Message": "The task with Id '3' has changed to progress 49 percent complete.",
"MessageArgs": [
"0",
"49"
],
"MessageId": "TaskEvent.1.0.3.TaskProgressChanged",
"MessageSeverity": "OK",
"Resolution": "None."
}
],
"Name": "Task 3",
"Payload": {
"HttpHeaders": [],
"HttpOperation": "POST",
"JsonBody": "null",
"TargetUri": "/redfish/v1/UpdateService/update"
},
"PercentComplete": 49,
"StartTime": "2024-05-02T15:45:44+00:00",
"TaskMonitor": "/redfish/v1/TaskService/Tasks/3/Monitor",
"TaskState": "Running",
"TaskStatus": "OK"
}
Update is still running.
------------------------------------------------------------------------------------------------------------------------
Error Code: 0
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** show_version -p DeltaPR3PSUS/nvidia-pmc-3.2.3-RELEASE.FOR.UPDATE.CEC-CFG.fwpkg
System Model: AHE50V660A33KWL
Part number: ECD68000091
Serial number: THASQ25220015
Packages: ['3.2.3']
Connection Status: Successful
Firmware Devices:
AP Name Sys Version Pkg Version Up-To-Date
------- ----------- ----------- ----------
44ecaa94 01050105 N/A No
62031a50 01040104 N/A No
FW_ERoT_BMC_0 1203 N/A No
FW_PMC_alt 3.2.4 3.2.3 Yes
FW_PMC_primary 3.2.3 3.2.3 Yes
----------------------------------------------------------
Error Code: 0
LiteOn PSU Update:
LiteOn PSUs may only be updated one at a time. To select the PSU to update, a special JSON file containing the “LiteOnPowerDeviceId” value is required. The index value matches exactly to the powerdevice index in the firmware inventory.
Note
Currently, LiteOn PSU package versioning in the show_version output is not supported, therefore “N/A” is expected for the package version field. This will be improved in a future release.
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** show_version -p LiteOnPSUPackages/SP-2552-7RD_F1F1_Bootloader_20250611.D2DAppA.tar
System Model: PF-1333-13RD
Part number: PF-1333-13RD
Serial number: 6133313RD01X1528174
Packages: ['LiteOnPSUPackages/SP-2552-7RD_F1F1_Bootloader_20250611.D2DAppA.tar']
Connection Status: Successful
Firmware Devices:
AP Name Sys Version Pkg Version Up-To-Date
------- ----------- ----------- ----------
mcu 0 N/A No
pmc_6afb1cf5 r1.3.9-rc1 N/A No
powerdevice0 0x1 / 0x1 N/A No
powerdevice1 0x1 / 0x1 N/A No
powerdevice2 0x1 / 0x1 N/A No
powerdevice3 0x1 / 0x1 N/A No
powerdevice4 0x1 / 0x1 N/A No
powerdevice5 0x1 / 0x1 N/A No
----------------------------------------------------------
Error Code: 0
Note
Setting the “LiteOnPowerDeviceId” value in the special JSON file is mandatory for LiteOn PSU updates.
Only a single LiteOn PSU can be updated at a time.
- The index value must match exactly to the powerdevice index in the firmware inventory.
For example, to update “powerdevice0”, set the “LiteOnPowerDeviceId” value to “0”.
To update “powerdevice1”, set the “LiteOnPowerDeviceId” value to “1”, and so on.
cat liteon_psu_device0.json
{
"LiteOnPowerDeviceId": "0"
}
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** update_fw -p LiteOnPSUPackages/SP-2552-7RD_F1F1_Bootloader_20250611.D2DAppA.tar -s liteon_psu_device0.json
Updating ip address: ip=XXXX
yFW package: ['LiteOnPSUPackages/SP-2552-7RD_F1F1_Bootloader_20250611.D2DAppA.tar']
Ok to proceed with firmware update? <Y/N>
y
Performing LiteOn PSU firmware update (Device ID: 0)...
LiteOn PSU firmware update started successfully (Device ID: 0)
Run "show_update_progress -i powerdevice0" to monitor update progress.
------------------------------------------------------------------------------------------------------------------------
Error Code: 0
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** show_update_progress -i powerdevice0
LiteOn PSU Update Info for Device: powerdevice0
Name: power unit 0
Model: SP-2552-7RD
SerialNumber: 6PL7Y01X15284JW
Version: 0x1 / 0x1
Status: OK
State: Boot
UpdateProgress: 3%
Update is in progress.
Full Response: {
"@odata.id": "/redfish/v1/Chassis/powershelf/PowerUnits/powerdevice0",
"@odata.type": "#LiteOn.v1_0_0.PowerUnit",
"Id": "0",
"Model": "SP-2552-7RD",
"Name": "power unit 0",
"SerialNumber": "6PL7Y01X15284JW",
"Version": "0x1 / 0x1",
"ambient": {
"Unit": "\u00b0C",
"Value": 26.0
},
"exhaust": {
"Unit": "\u00b0C",
"Value": 30.25
},
"fan1": {
"Unit": "RPMS",
"Value": 14720.0
},
"freqin": {
"Unit": "Hz",
"Value": 60.0
},
"hotspot": {
"Unit": "\u00b0C",
"Value": 31.0
},
"iin": {
"Unit": "A",
"Value": 0.5
},
"iout": {
"Unit": "A",
"Value": 0.64
},
"pin": {
"Unit": "W",
"Value": 56.68
},
"pout": {
"Unit": "W",
"Value": 41.5
},
"state": "Boot",
"status": "OK",
"updateProgress": 3,
"vin": {
"Unit": "V",
"Value": 242.0
},
"vout": {
"Unit": "V",
"Value": 50.38
}
}
------------------------------------------------------------------------------------------------------------------------
Error Code: 0
After the update is complete, the PSU version is updated to 0xf1.
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** show_version -p LiteOnPSUPackages/SP-2552-7RD_F1F1_Bootloader_20250611.D2DAppA.tar
System Model: PF-1333-13RD
Part number: PF-1333-13RD
Serial number: 6133313RD01X1528174
Packages: ['LiteOnPSUPackages/SP-2552-7RD_F1F1_Bootloader_20250611.D2DAppA.tar']
Connection Status: Successful
Firmware Devices:
AP Name Sys Version Pkg Version Up-To-Date
------- ----------- ----------- ----------
mcu 0 N/A No
pmc_6afb1cf5 r1.3.9-rc1 N/A No
powerdevice0 0xf1 / 0xf1 N/A No
powerdevice1 0x1 / 0x1 N/A No
powerdevice2 0x1 / 0x1 N/A No
powerdevice3 0x1 / 0x1 N/A No
powerdevice4 0x1 / 0x1 N/A No
powerdevice5 0x1 / 0x1 N/A No
----------------------------------------------------------
Error Code: 0
Delta PSU Update:
Delta PSUs update simultaneously and no special JSON file is required. You can monitor the update progress using the show_update_progress command with task ID.
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** show_version -p DeltaPR3PSUS/Nvidia_GB300_5500W_APP_01050105_20251013.hex.tar
System Model: AHE50V660A33KWL
Part number: ECD68000091
Serial number: THASQ25220015
Packages: ['DeltaPR3PSUS/Nvidia_GB300_5500W_APP_01050105_20251013.hex.tar']
Connection Status: Successful
Firmware Devices:
AP Name Sys Version Pkg Version Up-To-Date
------- ----------- ----------- ----------
FW_ERoT_BMC_0 1203 N/A No
FW_PMC_alt 3.2.4 N/A No
FW_PMC_primary 3.2.4 N/A No
FW_PSU_1 01050105 01050105 Yes
FW_PSU_2 01040104 01050105 No
FW_PSU_3 01040104 01050105 No
FW_PSU_4 01040104 01050105 No
FW_PSU_5 01040104 01050105 No
FW_PSU_6 01040104 01050105 No
-------------------------------------------------------
Error Code: 0
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** update_fw -p DeltaPR3PSUS/Nvidia_GB300_5500W_APP_01050105_20251013.hex.tar
Updating ip address: ip=XXXX
FW package: ['DeltaPR3PSUS/Nvidia_GB300_5500W_APP_01050105_20251013.hex.tar']
Ok to proceed with firmware update? <Y/N>
y
FW update started, Task Id: 0
Firmware update in progress
use show_update_progress command to monitor the progress
------------------------------------------------------------------------------------------------------------------------
Error Code: 0
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** show_update_progress -i 0
Task Info for Id: 0
StartTime: 2024-05-02T15:45:44+00:00
TaskState: Running
PercentComplete: 49
TaskStatus: OK
Overall Task Status: {
"@odata.id": "/redfish/v1/TaskService/Tasks/0",
"@odata.type": "#Task.v1_7_4.Task",
"HidePayload": false,
"Id": "0",
"Messages": [
{
"@odata.type": "#Message.v1_1_1.Message",
"Message": "The task with Id '0' has started.",
"MessageArgs": [
"0"
],
"MessageId": "TaskEvent.1.0.3.TaskStarted",
"MessageSeverity": "OK",
"Resolution": "None."
},
{
"@odata.type": "#Message.v1_1_1.Message",
"Message": "The task with Id '0' has changed to progress 10 percent complete.",
"MessageArgs": [
"0",
"10"
],
"MessageId": "TaskEvent.1.0.3.TaskProgressChanged",
"MessageSeverity": "OK",
"Resolution": "None."
},
{
"@odata.type": "#Message.v1_1_1.Message",
"Message": "The task with Id '0' has changed to progress 23 percent complete.",
"MessageArgs": [
"0",
"23"
],
"MessageId": "TaskEvent.1.0.3.TaskProgressChanged",
"MessageSeverity": "OK",
"Resolution": "None."
},
{
"@odata.type": "#Message.v1_1_1.Message",
"Message": "The task with Id '0' has changed to progress 36 percent complete.",
"MessageArgs": [
"0",
"36"
],
"MessageId": "TaskEvent.1.0.3.TaskProgressChanged",
"MessageSeverity": "OK",
"Resolution": "None."
},
{
"@odata.type": "#Message.v1_1_1.Message",
"Message": "The task with Id '0' has changed to progress 49 percent complete.",
"MessageArgs": [
"0",
"49"
],
"MessageId": "TaskEvent.1.0.3.TaskProgressChanged",
"MessageSeverity": "OK",
"Resolution": "None."
}
],
"Name": "Task 0",
"Payload": {
"HttpHeaders": [],
"HttpOperation": "POST",
"JsonBody": "null",
"TargetUri": "/redfish/v1/UpdateService/update"
},
"PercentComplete": 49,
"StartTime": "2024-05-02T15:45:44+00:00",
"TaskMonitor": "/redfish/v1/TaskService/Tasks/0/Monitor",
"TaskState": "Running",
"TaskStatus": "OK"
}
Update is still running.
------------------------------------------------------------------------------------------------------------------------
Error Code: 0
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** show_version -p DeltaPR3PSUS/Nvidia_GB300_5500W_APP_01050105_20251013.hex.tar
System Model: AHE50V660A33KWL
Part number: ECD68000091
Serial number: THASQ25220015
Packages: ['DeltaPR3PSUS/Nvidia_GB300_5500W_APP_01050105_20251013.hex.tar']
Connection Status: Successful
Firmware Devices:
AP Name Sys Version Pkg Version Up-To-Date
------- ----------- ----------- ----------
FW_ERoT_BMC_0 1203 N/A No
FW_PMC_alt 3.2.4 N/A No
FW_PMC_primary 3.2.4 N/A No
FW_PSU_1 01050105 01050105 Yes
FW_PSU_2 01050105 01050105 Yes
FW_PSU_3 01050105 01050105 Yes
FW_PSU_4 01050105 01050105 Yes
FW_PSU_5 01050105 01050105 Yes
FW_PSU_6 01050105 01050105 Yes
-------------------------------------------------------
Error Code: 0
Configuration File for PowerShelf Updates#
PowerShelf updates can be configured using a YAML configuration file for easier management:
TargetPlatform: 'Powershelf'
FWUpdateFilePath:
- "DeltaPR3PSUS/Nvidia_GB300_5500W_APP_01040104_20250807.hex.tar"
BMC_IP: "POWERSHELF_BMC_IP"
RF_USERNAME: "PMC_USERNAME"
RF_PASSWORD: "PMC_PASSWORD"
Using the configuration file:
$ nvfwupd -c powershelf_config.yaml show_version
$ nvfwupd -c powershelf_config.yaml update_fw
Monitoring Update Progress#
Monitor the progress of PowerShelf firmware updates using the show_update_progress command:
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** servertype=Powershelf show_update_progress -i 2
Task Info for Id: 2
StartTime: 2024-04-29T16:21:51+00:00
TaskState: Running
PercentComplete: 0
TaskStatus: OK
Overall Task Status: {
"@odata.id": "/redfish/v1/TaskService/Tasks/2",
"@odata.type": "#Task.v1_7_4.Task",
"HidePayload": false,
"Id": "2",
"Messages": [
{
"@odata.type": "#Message.v1_1_1.Message",
"Message": "The task with Id '2' has started.",
"MessageArgs": [
"2"
],
"MessageId": "TaskEvent.1.0.3.TaskStarted",
"MessageSeverity": "OK",
"Resolution": "None."
}
],
"Name": "Task 2",
"Payload": {
"HttpHeaders": [],
"HttpOperation": "POST",
"JsonBody": "null",
"TargetUri": "/redfish/v1/UpdateService/update"
},
"PercentComplete": 0,
"StartTime": "2024-04-29T16:21:51+00:00",
"TaskMonitor": "/redfish/v1/TaskService/Tasks/2/Monitor",
"TaskState": "Running",
"TaskStatus": "OK"
}
Update is still running.
------------------------------------------------------------------------------------------------------------------------
Error Code: 0
Note
Delta Powershelf PMC updates may be monitored to around 60% completion before the PMC reboots itself for activation. This is normal and expected behavior.
If the PMC becomes unresponsive, LiteOn Powershelf PMC updates might not be monitored until the update is complete and the new PMC firmware is activated.
Delta Powershelf PSU updates may be monitored with a provided task ID and the PSU will reboot itself after the update is complete.
LiteOn Powershelf PSU updates do not utilize the Redfish taskservice, so a LiteOn OEM page displays the UpdateProgress as part of the PSU power status output.
Verifying Update Completion#
After the update completes, PowerShelf components automatically activate the new firmware. Wait for any component reboots to complete, then verify the firmware versions:
$ nvfwupd -t ip=<PowerShelf BMC IP> user=*** password=*** servertype=Powershelf show_version -p nvidia-pmc-3.2.3-RELEASE.FOR.UPDATE.CEC-CFG.fwpkg
System Model: AHE50V660A33KWL
Part number: ECD68000091
Serial number: THASQ25220015
Packages: ['3.2.3']
Connection Status: Successful
Firmware Devices:
AP Name Sys Version Pkg Version Up-To-Date
------- ----------- ----------- ----------
44ecaa94 01050105 N/A No
62031a50 01040104 N/A No
FW_ERoT_BMC_0 1203 N/A No
FW_PMC_alt 3.2.4 3.2.3 Yes
FW_PMC_primary 3.2.3 3.2.3 Yes
-------------------------------------------------------
Error Code: 0
Note
In this example, the FW_PMC_primary firmware was successfully downgraded from 3.2.4 to 3.2.3. The component automatically rebooted and activated the new firmware version. Note that the component ordering may change after updates, and new components may appear in the inventory.
Update Workflow Summary#
Based on the Delta PowerShelf PMC update example, here is the typical workflow:
Check Current Versions: Use
show_versionto see current firmware versions before updatingStart Update: Run
update_fwcommand - the tool returns a Task ID for monitoringMonitor Progress: Use
show_update_progresswith the Task ID to check update statusWait for Completion: PowerShelf components will reboot and automatically activate new firmware
Verify Update: Run
show_versionagain to confirm the new firmware is active and up to date
The entire process typically takes several minutes, during which the PowerShelf PMC may become temporarily unreachable during PMC reboots.
Activation and Power Management#
All PowerShelf components activate themselves automatically after the update completes. No additional activation steps are required for PowerShelf platforms.
Important
Wait for the complete update process to finish before verifying firmware versions
The PMC will reboot during the update, causing temporary loss of connectivity
Updates can take several minutes to complete - use
show_update_progressto monitor statusComponent ordering in the firmware inventory may change after updates