Appendix A-D: Submission & Standards
Appendix A-D: Submission & Standards
Appendix A: Data Submission Requirements
Every test must include:
- Raw time-series (CSV)
- Summary plots (PDF)
- Test configuration (single-line of test setup, controller settings, SOC)
- Pass/fail statement tied to criteria
- Known issues and deviations list
Appendix B: Core Requirements Checklist
Partners must fill out a one-page checklist mapping: Core Requirement → Test IDs → Evidence references.
Appendix C: Partner Model Package Requirements
Minimum:
- EMT model (PSCAD/EMTDC, RTDS, or equivalent), including control blocks
- dq impedance plots at:
- 10%, 50%, 100% P
- High and low Q
- Multiple SCR values
- Nyquist/passivity artifact and interpretation
- Version-controlled parameter export
Model Validity
Models that cannot reproduce hardware behavior within stated tolerances are invalid.
Appendix D: Industrial Standards and Regulatory Certificates
Partners must provide a list of industrial standards the system is designed to comply with, as well as test certificates granted by countries or economic areas. Key standards include:
- IEEE 1547-2018, IEEE 2800
- UL 9540 / UL 9540A
- NFPA 855
- CE/UKCA
- RoHS/REACH
- IEC 60068
- ISO 9001
- NERC Reliability Guidelines
- NERC CIP (Critical Infrastructure Protection)
- IEC 62443 (Industrial Automation and Control Systems Security)
- NIST Cybersecurity Framework (CSF)