This page documents the data that the NVIDIA Fleet Intelligence Out-of-Band Collector collects from the baseboard management controller (BMC) of each enrolled compute node. It also explains why each item is collected. Out-of-band (OOB) collection reads hardware data from the BMC through the Redfish management API. It works independently of the host operating system, so it complements the data that the in-band agent collects. Refer to Data Collection Rationale - In Band for the in-band data, and to the Out-of-Band Collector documentation for the collector itself. Metric descriptions follow the definitions in the DMTF Redfish schemas.

The data is organized into four sections. Labels describe each series and identify the node, the BMC, and the part that a metric describes. Telemetry Metrics are recurring time-series data that the BMC reports for sensors, processors, memory, storage, and power supplies. Alerts are the messages that the collector generates when a sensor reading crosses a threshold that the BMC defines. Logs are the event records, health reports, and firmware inventory that the collector reads from the BMC.

The collector names every metric with the fleetint_hw_ prefix. Sensor metrics are the primary collection path, and they are collected by default. The BMC defines the caution and critical thresholds for each sensor. The collector also collects drive media life and power supply capacity metrics by default because it derives them from sensor and inventory data. To collect all other processor, memory, storage, and power supply metrics, enable the metrics collector. Those metrics come from the Redfish metrics resources, which have no sensor equivalent. The collector skips any value that a sensor already reports to avoid reporting it twice.

Labels

The collector attaches the following labels to every series.

LabelDescriptionRationale
collector_typeType of collector that produced the series.Separates data by collection path so that queries can target one path.
endpoint_keyKey that identifies the BMC endpoint that the data came from.Distinguishes data from different endpoints when a node has more than one.
endpoint_ipIP address of the BMC endpoint.Identifies the management interface that produced the data to help you troubleshoot connectivity and correlation.
endpoint_macMAC address of the BMC endpoint.Provides a stable hardware identifier for the BMC when IP addresses change.
machine_idMachine identifier, which is the same value that the in-band agent reports.Joins out-of-band data with in-band data for the same node.

The collector also attaches the following labels, depending on the type of part that a metric describes.

LabelDescriptionRationale
sensor_nameName of the sensor that produced the reading.Identifies which sensor a reading came from.
physical_contextThe area or device that the sensor measures, such as a GPU, a CPU, memory, a power supply, or the air intake.Groups readings by the part or area that they describe.
processor_id, system_id, processor_type, modelIdentity of the processor, with the type and model when the BMC reports them.Attributes processor metrics to one processor in one system.
memory_id, system_id, device_type, modelIdentity of the memory device, with the type and model when the BMC reports them.Attributes memory metrics to one memory device in one system.
drive_id, storage_id, system_id, modelIdentity of the drive, with the model when the BMC reports it.Attributes storage metrics to one drive in one system.
powersupply_id, chassis_id, modelIdentity of the power supply, with the model when the BMC reports it.Attributes power supply metrics to one supply in one chassis.
sensor_rangeWhether a range metric reports the maximum or the minimum of a sensor.Distinguishes the upper limit from the lower limit on range metrics.

Telemetry Metrics

Thermal and Cooling Sensors

The following table lists the BMC temperature and cooling sensor metrics.

MetricDescriptionRationale
fleetint_hw_sensor_temperature_celsiusTemperature, in degrees Celsius, that a BMC sensor reports. The physical_context label identifies the area or device that the sensor measures, such as a GPU, a CPU, memory, or intake air.Gives a temperature view that does not depend on the host operating system, so it still works when the host is unresponsive or offline. The BMC sets caution and critical thresholds for each sensor, and alerts use them. Use it with the in-band GPU and CPU temperatures to confirm overheating.
fleetint_hw_sensor_rotational_rpmRotational speed of a fan or pump, in revolutions per minute (RPM).A slow or stopped fan or pump is a common cause of rising temperatures. Comparing speed with temperature separates a cooling failure from heat that the workload generates.
fleetint_hw_sensor_liquid_flow_l_sFlow rate of liquid through a cooling loop, in liters per second.Low flow in a liquid cooling loop can cause rapid overheating. Tracking flow helps detect pump failures and blockages before components throttle.
fleetint_hw_sensor_liquid_level_cmLiquid level in a cooling loop, in centimeters.A falling level indicates coolant loss. Tracking it gives early warning before flow and temperatures are affected.
fleetint_hw_sensor_air_flow_fti_3_minAir flow, in cubic feet per minute.Confirms that fans move enough air through the chassis. Low air flow explains temperature increases when fan speeds look normal.

Power Sensors

The following table lists the BMC power sensor metrics.

MetricDescriptionRationale
fleetint_hw_sensor_power_wattsPower, in watts, that a BMC sensor reports for a component or area.Provides an independent power reading for each component. Use it for capacity planning, for detecting abnormal draw, and for cross-checking the power that the in-band agent reports.
fleetint_hw_sensor_voltage_voltsVoltage, in volts, that a BMC sensor reports. The reading can be alternating current (AC) or direct current (DC).Voltage outside the expected range signals unstable or failing power delivery, which can cause errors, throttling, or shutdowns.
fleetint_hw_sensor_current_amperesElectrical current, in amperes, that a BMC sensor reports.Explains power draw together with voltage and helps locate overloaded or failing power paths.
fleetint_hw_sensor_frequency_hertzFrequency, in hertz, that a BMC power sensor reports.Frequency outside the normal range indicates a problem with the electrical supply.
fleetint_hw_sensor_energy_joules_jCumulative energy, in joules.Cumulative energy counters support energy accounting and cost calculations, and they show which nodes use the most power over time.
fleetint_hw_sensor_energy_wh_w_hCumulative energy, in watt-hours.Captures energy readings from BMCs that report in watt-hours instead of joules. It measures the same quantity as the joules metric.
fleetint_hw_sensor_energyk_wh_kw_hCumulative energy, in kilowatt-hours.Captures energy readings from BMCs that report in kilowatt-hours instead of joules. It measures the same quantity as the joules metric.
fleetint_hw_sensor_charge_ah_a_hElectrical charge, in ampere-hours (Ah).Tracks stored charge for components that report it, so that you can detect low charge before it affects the node.

Environmental Sensors

The following table lists the BMC environmental sensor metrics.

MetricDescriptionRationale
fleetint_hw_sensor_humidity_percentRelative humidity, as a percent.High humidity risks condensation and corrosion, and low humidity risks static discharge. Tracking it verifies that the environment stays within the operating range.
fleetint_hw_sensor_absolute_humidity_g_m3Absolute humidity, in grams of water per cubic meter.Complements relative humidity because condensation risk depends on both humidity and temperature.
fleetint_hw_sensor_pressure_paPressure, in pascals.Reports pressure readings from environmental sensors. Changes can indicate air flow or cooling problems.
fleetint_hw_sensor_pressurek_pa_kpaPressure, in kilopascals.Captures pressure readings from BMCs that report in kilopascals instead of pascals.
fleetint_hw_sensor_barometric_mm_hg_Barometric (ambient air) pressure, in millimeters of mercury.Provides ambient pressure context for cooling performance, which varies with altitude and weather.
fleetint_hw_sensor_altitude_paAltitude. The Redfish standard defines this reading in meters, but the NVIDIA GH200 BMC reports it in pascals.Records the installation altitude, which affects air-cooling capacity. Treat it as inventory data.
fleetint_hw_sensor_percent_percentGeneric percentage reading. The meaning depends on the sensor.Captures percentage sensors that do not fit another reading type. Use the sensor_name label to interpret the value.

Sensor Ranges

The following table lists the metrics that report the valid range of a sensor.

MetricDescriptionRationale
fleetint_hw_sensor_<reading_type>_range_max_<unit>Maximum possible value that a sensor can report, for any sensor reading type above.Defines the upper end of the valid range for a sensor. A reading outside the range points to a faulty sensor instead of a hardware problem, so the range helps separate the two.
fleetint_hw_sensor_<reading_type>_range_min_<unit>Minimum possible value that a sensor can report, for any sensor reading type above.Defines the lower end of the valid range for a sensor. It serves the same purpose as the maximum for readings that fall too low.

Processor Metrics

The following table lists the metrics that the BMC reports for each processor on its Redfish processor metrics resource.

MetricDescriptionRationale
fleetint_hw_metric_average_frequency_mhzAverage frequency across all enabled cores of the processor, in MHz.Shows whether the processor runs at the expected frequency over time. Sustained low frequency points to throttling or power-management problems.
fleetint_hw_metric_frequency_ratio_ratioProcessor frequency relative to the nominal processor frequency ratio.Normalizes frequency across processor models so you can compare nodes and find processors that run below nominal frequency.
fleetint_hw_metric_throttling_celsiusThe processor margin to throttle, as a temperature offset in degrees Celsius.Shows how close the processor is to thermal throttling. Use it with the throttle duration metrics to understand why a processor slows down.
fleetint_hw_metric_thermal_limit_throttle_secondsTotal time that a thermal limit throttled the processor since reset, in seconds.Separates temperature-driven throttling from other causes of reduced performance. High values indicate a need for better cooling or air flow.
fleetint_hw_metric_power_limit_throttle_secondsTotal time that a power limit throttled the processor since reset, in seconds.Identifies processors held back by power caps or power-supply constraints. High values suggest that the power budget is too low for the workload.
fleetint_hw_metric_consumed_power_wattsPower that the processor has consumed, in watts.Provides per-processor power for capacity planning and for detecting abnormal draw.
fleetint_hw_metric_core_voltage_voltsCore voltage of the processor, in volts.Unstable or low core voltage can cause errors and throttling, so tracking it helps find power-delivery problems at the processor.
fleetint_hw_metric_local_memory_bandwidth_bytesLocal memory bandwidth usage of the processor, in bytes.Shows how much memory traffic stays on memory attached to the same processor. Local access is faster than remote access.
fleetint_hw_metric_remote_memory_bandwidth_bytesRemote memory bandwidth usage of the processor, in bytes.Shows how much memory traffic crosses to memory attached to another processor. A high remote share slows workloads and indicates poor memory placement.
fleetint_hw_metric_kernel_time_percentShare of time that the processor has spent in kernel mode, as a percent.Separates operating system work from application work. A high kernel share can indicate driver or input and output overhead.
fleetint_hw_metric_user_time_percentShare of time that the processor has spent in user mode, as a percent.Shows how much processor time applications use. Together with kernel time, it explains where processor time goes.
fleetint_hw_metric_correctable_core_errors_countNumber of correctable errors in the processor cores, such as translation lookaside buffer (TLB) or cache errors.The hardware fixed these errors, but a rising count is an early warning of a degrading processor.
fleetint_hw_metric_uncorrectable_core_errors_countNumber of uncorrectable errors in the processor cores, such as TLB or cache errors.The hardware could not fix these errors. Any increase needs investigation and can mean the processor must leave service.
fleetint_hw_metric_correctable_other_errors_countNumber of correctable errors in all other processor components.Covers processor components other than the cores. A rising count is an early warning of a degrading part.
fleetint_hw_metric_uncorrectable_other_errors_countNumber of uncorrectable errors in all other processor components.Covers processor components other than the cores. Any increase needs investigation.
fleetint_hw_metric_pcie_replay_countTotal number of Peripheral Component Interconnect Express (PCIe) replays that the device issued. A replay is a resend of a packet after the acknowledgment timer expires.Replays indicate transmission problems on the PCIe link. Sustained growth suggests signal-integrity problems in cabling, risers, or the board.
fleetint_hw_metric_pcie_replay_rollover_countTotal number of PCIe replay rollovers that the device issued. A rollover happens when repeated replays fail and force the link into recovery.Shows that the link could not repair itself through replays alone. Any increase indicates a seriously degraded link.
fleetint_hw_metric_pcie_correctable_errors_countTotal number of correctable PCIe errors for the device.The link recovered from these errors without data loss, but growth indicates a degrading link.
fleetint_hw_metric_pcie_non_fatal_errors_countTotal number of non-fatal PCIe errors for the device.These errors disrupt a transfer but leave the link usable. Growth indicates a link that needs attention.
fleetint_hw_metric_pcie_fatal_errors_countTotal number of fatal PCIe errors for the device.These errors break the link. Any increase needs immediate investigation.
fleetint_hw_metric_pcie_l0_to_recovery_countTotal number of times the PCIe link moved from the normal operating state (L0) to the recovery state.Frequent recovery events show that the link repairs itself often, which indicates poor signal quality.
fleetint_hw_metric_pcie_bad_tlp_countTotal number of bad transaction layer packets (TLPs) on the PCIe link. A bad TLP is one that the transaction layer cannot process, for example because of corruption or a checksum mismatch.Bad packets force retransmission and slow transfers. Growth points to link quality problems.
fleetint_hw_metric_pcie_bad_dllp_countTotal number of bad data link layer packets (DLLPs) on the PCIe link. A bad DLLP is damaged or malformed.Damaged link-management packets indicate signal problems at a lower layer than packet data errors.
fleetint_hw_metric_pcie_nak_sent_countTotal number of negative acknowledgments (NAKs) that the device sent on the PCIe link, for example after it missed or could not decode a packet.Shows how often this side received bad data and asked for it again.
fleetint_hw_metric_pcie_nak_received_countTotal number of NAKs that the receiver on the other end of the PCIe link sent.Shows how often the other side rejected data that this side sent.
fleetint_hw_metric_pcie_flow_control_timeout_countTotal number of PCIe flow control credit timeouts.Timeouts indicate a link-level problem and typically cause link recovery.
fleetint_hw_metric_pcie_unsupported_request_countTotal number of unsupported PCIe requests that the device received.Indicates misdirected or unsupported requests, which can point to configuration or firmware problems.

Shared Processor, Memory, and Power Supply Metrics

The BMC reports the following metrics for more than one type of part.

MetricDescriptionRationale
fleetint_hw_metric_temperature_celsiusTemperature, in degrees Celsius, of a processor or a power supply.Provides per-part temperature in addition to the generic sensor readings. Overheating processors and power supplies throttle or shut down.
fleetint_hw_metric_bandwidth_percentFor a processor, the processor utilization as a percent. For a memory device, the memory bandwidth utilization as a percent.Shows how busy processors are and how close memory runs to its data-movement capacity. Sustained high memory values indicate bandwidth-bound workloads.
fleetint_hw_metric_operating_speed_mhzOperating speed of a processor, in MHz, or of a memory device, in MHz or mega-transfers per second (MT/s).Confirms that components run at the expected speed. Lower speeds indicate throttling, power-saving states, or configuration problems.

Memory Metrics

The following table lists the metrics that the BMC reports for each memory device.

MetricDescriptionRationale
fleetint_hw_metric_current_correctable_ecc_errors_countNumber of correctable error-correcting code (ECC) errors since the last reset.Shows short-term corrected error activity. Spikes help detect environmental or workload-triggered memory problems without being dominated by old history.
fleetint_hw_metric_current_uncorrectable_ecc_errors_countNumber of uncorrectable ECC errors since the last reset.Counts recent errors that ECC could detect but not fix. They indicate data corruption and potential system instability.
fleetint_hw_metric_lifetime_correctable_ecc_errors_countNumber of correctable ECC errors for the lifetime of the memory.Shows the long-term health of the memory. Use it to rank devices by error history and decide which to replace first.
fleetint_hw_metric_lifetime_uncorrectable_ecc_errors_countNumber of uncorrectable ECC errors for the lifetime of the memory.Tracks how many serious memory failures a device has had. High counts suggest a history of instability.
fleetint_hw_metric_corrected_volatile_errors_countNumber of corrected errors in volatile memory.Shows how often regular memory needs correction. A rising count is an early warning of a degrading device.
fleetint_hw_metric_corrected_persistent_errors_countNumber of corrected errors in persistent memory.Applies only to systems with persistent memory modules. A rising count is an early warning of a degrading module.
fleetint_hw_metric_current_indeterminate_correctable_errors_countNumber of indeterminate correctable errors since the last reset. The origin of these errors is unknown, so the same error can appear on more than one memory device.Surfaces errors that the classified counters miss. Treat increases as a warning to investigate.
fleetint_hw_metric_current_indeterminate_uncorrectable_errors_countNumber of indeterminate uncorrectable errors since the last reset. The origin of these errors is unknown, so the same error can appear on more than one memory device.Surfaces errors that the classified counters miss. These errors are more serious than the correctable variant.
fleetint_hw_metric_lifetime_indeterminate_correctable_errors_countNumber of indeterminate correctable errors for the lifetime of the memory.Provides the long-term history for unclassified errors so that you can compare devices.
fleetint_hw_metric_lifetime_indeterminate_uncorrectable_errors_countNumber of indeterminate uncorrectable errors for the lifetime of the memory.Provides the long-term history for serious unclassified errors.
fleetint_hw_metric_dirty_shutdown_countNumber of shutdowns that happened while outstanding writes to persistent memory had not completed.Applies only to persistent memory. Unclean shutdowns can leave data inconsistent and point to power problems.
fleetint_hw_metric_capacity_utilization_percentShare of the memory capacity in use, as a percent.Shows memory pressure on the node. Use it to find nodes that run out of memory or sit mostly idle.
fleetint_hw_metric_block_size_bytesBlock size of the memory structure elements, in bytes.Describes how the device is organized. It helps verify consistent configuration across nodes.

Storage Metrics

The following table lists the metrics that the BMC reports for each drive.

MetricDescriptionRationale
fleetint_hw_metric_correctable_io_read_errors_countNumber of correctable read errors for the lifetime of the drive.A rising count of corrected read errors is an early warning of a wearing or failing drive.
fleetint_hw_metric_correctable_io_write_errors_countNumber of correctable write errors for the lifetime of the drive.A rising count of corrected write errors is an early warning of a wearing or failing drive.
fleetint_hw_metric_uncorrectable_io_read_errors_countNumber of uncorrectable read errors for the lifetime of the drive.These errors can mean data loss. Any increase needs investigation.
fleetint_hw_metric_uncorrectable_io_write_errors_countNumber of uncorrectable write errors for the lifetime of the drive.These errors can mean data loss. Any increase needs investigation.
fleetint_hw_metric_bad_block_countTotal number of bad blocks that the drive reports.A rising count signals a wearing drive and helps plan replacement.
fleetint_hw_drive_predicted_media_life_left_percentagePredicted percentage of life remaining in the drive media. The collector derives it from drive inventory data.Predicts when a drive reaches the end of its life so you can replace it before it fails.
fleetint_hw_metric_power_on_hours_hoursNumber of hours that the drive has been powered on for its lifetime.Shows the age of the drive. Use it with error counts to judge drive health.
fleetint_hw_metric_native_command_queue_depth_countCurrent depth of the Native Command Queue, as the Serial Advanced Technology Attachment (SATA) specification defines it.Shows how heavily the workload loads the drive. A persistently deep queue points to a storage bottleneck. It applies to SATA drives.
fleetint_hw_metric_read_io_kibibytesTotal data read from the drive since the last reset or counter wrap, in kibibytes.Shows the read workload on the drive for capacity planning and for explaining drive wear.
fleetint_hw_metric_write_io_kibibytesTotal data written to the drive since the last reset or counter wrap, in kibibytes.Shows the write workload on the drive. Writes drive flash wear, so this helps explain remaining media life.

Power Supply Metrics

The following table lists the metrics that the BMC reports for each node power supply.

MetricDescriptionRationale
fleetint_hw_metric_input_voltage_voltsInput voltage of the power supply, in volts.Input voltage outside the expected range indicates a power-source problem or a failing supply.
fleetint_hw_metric_input_current_amperesInput current of the power supply, in amperes.Shows how heavily the supply loads the power source and helps find overloaded power paths.
fleetint_hw_metric_input_power_wattsInput power of the power supply, in watts.Shows the real power cost of the node, including conversion losses. Use it for capacity planning and energy accounting.
fleetint_hw_metric_output_power_wattsTotal output power of the power supply, in watts.Shows the total load on the supply. Comparing it with input power gives the supply efficiency, and comparing it with capacity shows headroom.
fleetint_hw_metric_energy_kilowatt_hoursTotal energy consumption of the power supply, in kilowatt-hours.Supports energy accounting and cost calculations at the power supply level.
fleetint_hw_metric_frequency_hertzFrequency of the power supply, in hertz.Frequency outside the normal range indicates a problem with the power source.
fleetint_hw_metric_fan_speed_percentFan speed of the power supply, as a percent.A slow or stopped power supply fan leads to overheating and failure of the supply.
fleetint_hw_powersupply_capacity_wattsMaximum power, in watts, that the supply is rated to deliver. The collector derives it from inventory data.Provides the limit against which to measure load. Compare output power with capacity to determine headroom.

Alerts

The collector generates an alert when a sensor reading crosses a threshold that the BMC defines. The BMC uses its firmware policy to determine whether a reading indicates a warning or a critical condition. The collector does not apply its own thresholds. Alerts report the raw values that the BMC reports, without conversion. The energy and altitude messages are the exception. They are informational readings that carry no threshold and no severity, so they do not signal a condition that needs action. Each alert uses one of the sensor metrics in Telemetry Metrics.

Alert messages use the following tokens.

TokenDescription
{criticality}Severity of the alert, such as warning or critical.
{sensor_context}The sensor and the part or area that it measures.
{value}The reading that the sensor reported, in the unit of the metric.
{threshold_condition}How the reading compares to the threshold, such as above or below.
{threshold_name}The threshold that the reading crossed, such as an upper caution or a lower critical threshold.
{threshold}The value of that threshold, in the same unit as the reading.

Thermal Alerts

The following table lists the thermal alerts.

AlertMetricMessageRationale
Temperaturefleetint_hw_sensor_temperature_celsius{criticality}: BMC temperature — {sensor_context} measured {value} °C, {threshold_condition} the {threshold_name} threshold of {threshold} °C.Warns of overheating from the BMC point of view. This view still works when the host operating system is unresponsive or offline. A warning gives you time to act before components throttle or shut down.

Power Alerts

The following table lists the power alerts.

AlertMetricMessageRationale
Currentfleetint_hw_sensor_current_amperes{criticality}: BMC current — {sensor_context} measured {value} A, {threshold_condition} the {threshold_name} threshold of {threshold} A.Flags a current that is too high or too low in a power path. It can indicate a failing supply or an overloaded circuit.
Energy, joulesfleetint_hw_sensor_energy_joules_jBMC energy reading — {sensor_context} measured {value} J.This informational reading is not a threshold alert. A cumulative counter has no normal range to cross, so the message reports the value only. The value supports energy accounting rather than fault detection.
Power drawfleetint_hw_sensor_power_watts{criticality}: BMC power draw — {sensor_context} measured {value} W, {threshold_condition} the {threshold_name} threshold of {threshold} W.Flags a component or supply that draws more or less power than the BMC expects. It can point to a fault or an abnormal load.
Voltagefleetint_hw_sensor_voltage_volts{criticality}: BMC voltage — {sensor_context} measured {value} V, {threshold_condition} the {threshold_name} threshold of {threshold} V.Flags a voltage outside the safe range. The alert gives early warning of unstable or failing power delivery before errors, throttling, or shutdowns occur.
Chargefleetint_hw_sensor_charge_ah_a_h{criticality}: BMC charge — {sensor_context} measured {value} A·h, {threshold_condition} the {threshold_name} threshold of {threshold} A·h.Flags low stored charge on components that report it, so that you can act before the charge affects the node.
Energy, kilowatt-hoursfleetint_hw_sensor_energyk_wh_kw_hBMC energy reading — {sensor_context} measured {value} kW·h.This informational reading is not a threshold alert. It reports the same cumulative energy as the joules message for BMCs that report in kilowatt-hours.
Energy, watt-hoursfleetint_hw_sensor_energy_wh_w_hBMC energy reading — {sensor_context} measured {value} W·h.This informational reading is not a threshold alert. It reports the same cumulative energy as the joules message for BMCs that report in watt-hours.
Frequencyfleetint_hw_sensor_frequency_hertz{criticality}: BMC power frequency — {sensor_context} measured {value} Hz, {threshold_condition} the {threshold_name} threshold of {threshold} Hz.Flags a frequency outside the normal range, which indicates a problem with the electrical supply.

Cooling Alerts

The following table lists the cooling alerts.

AlertMetricMessageRationale
Liquid flowfleetint_hw_sensor_liquid_flow_l_s{criticality}: BMC liquid flow — {sensor_context} measured {value} L/s, {threshold_condition} the {threshold_name} threshold of {threshold} L/s.Flags low or lost coolant flow, which can cause rapid overheating in a liquid-cooled node. It gives early warning of a pump failure or a blockage.
Fan or pump speedfleetint_hw_sensor_rotational_rpm{criticality}: BMC fan or pump speed — {sensor_context} measured {value} RPM, {threshold_condition} the {threshold_name} threshold of {threshold} RPM.Flags a fan or pump that runs too slowly or has stopped. A failing fan or pump is a common cause of rising temperatures.
Liquid levelfleetint_hw_sensor_liquid_level_cm{criticality}: BMC liquid level — {sensor_context} measured {value} cm, {threshold_condition} the {threshold_name} threshold of {threshold} cm.Flags a low coolant level. It gives early warning of coolant loss before flow and temperatures are affected.
Air flowfleetint_hw_sensor_air_flow_fti_3_min{criticality}: BMC air flow — {sensor_context} measured {value} ft³/min, {threshold_condition} the {threshold_name} threshold of {threshold} ft³/min.Flags low air flow through the chassis. It explains temperature increases when fan speeds look normal.

Environmental Alerts

The following table lists the environmental alerts.

AlertMetricMessageRationale
Absolute humidityfleetint_hw_sensor_absolute_humidity_g_m3{criticality}: BMC absolute humidity — {sensor_context} measured {value} g/m³, {threshold_condition} the {threshold_name} threshold of {threshold} g/m³.Flags humidity outside the safe range. Condensation risk depends on both humidity and temperature, so use the alert with the temperature alerts.
Barometric pressurefleetint_hw_sensor_barometric_mm_hg_{criticality}: BMC barometric pressure — {sensor_context} measured {value} mmHg, {threshold_condition} the {threshold_name} threshold of {threshold} mmHg.Flags unexpected ambient pressure. Pressure changes the cooling capacity of air, so it can explain a cooling shortfall.
Generic percentagefleetint_hw_sensor_percent_percent{criticality}: BMC environmental percentage — {sensor_context} measured {value}%, {threshold_condition} the {threshold_name} threshold of {threshold}%.Flags a percentage sensor that crosses a threshold. The meaning depends on the sensor, so use the sensor context in the message to interpret it.
Pressurefleetint_hw_sensor_pressure_pa{criticality}: BMC pressure — {sensor_context} measured {value} Pa, {threshold_condition} the {threshold_name} threshold of {threshold} Pa.Flags pressure changes that can indicate air flow or cooling problems.
Pressure, kilopascalsfleetint_hw_sensor_pressurek_pa_kpa{criticality}: BMC pressure — {sensor_context} measured {value} kPa, {threshold_condition} the {threshold_name} threshold of {threshold} kPa.Flags the same pressure changes for BMCs that report in kilopascals.
Relative humidityfleetint_hw_sensor_humidity_percent{criticality}: BMC relative humidity — {sensor_context} measured {value}%, {threshold_condition} the {threshold_name} threshold of {threshold}%.Flags air that is too humid or too dry. High humidity risks condensation, and low humidity risks static discharge.
Altitudefleetint_hw_sensor_altitude_paBMC altitude inventory reading — {sensor_context} reported {value} Pa.This informational reading is not a threshold alert. It reports the altitude as inventory data, and altitude affects air-cooling capacity, so the reading helps explain cooling behavior.

Logs

The collector reads event records, health reports, and firmware inventory from the BMC and reports them as logs. Each log has a type, a body, a severity, and attributes. Log collection depends on how you configure the Out-of-Band Collector.

BMC Log Entries and Events

The BMC records hardware events even when the host is down, so these logs show faults that the host never saw. The following table lists the logs that carry entries and events from the BMC.

Log TypeBodySeverityAttributesRationale
redfish_periodic_logThe message of a Redfish log entry.FATAL for a Critical entry, WARN for Warning, INFO for OK, and TRACE for any other severity.machine_id, entry_id, service_idCollects entries from the BMC log services, such as the system event log, on a recurring schedule. The entries give an audit trail for failure investigations. Collecting on a schedule works with any BMC that exposes log services.
redfish_sse_eventThe message of a Redfish event.OK, Warning, or Critical, or another severity that the source reports. The value is Unknown when the event reports no severity.message_id, event_type, event_id, event_timestamp, message_args, message_severity, origin_of_condition, log_entry_id, event_group_id, resolutionReceives events from the BMC as they occur through the Redfish event stream, which uses Server-Sent Events (SSE). The collector learns about faults without waiting for the next poll. Each event identifies the resource that caused the condition. It can include a suggested resolution and a group identifier that links events with the same root cause.

Health Reports

A health report summarizes the result of one group of BMC checks. Every health report log has the following format.

FieldValue
Bodyhealth report: <alerts> alerts, <successes> ok (source: <source>)
SeverityWARN when the report contains alerts, and INFO otherwise.
Attributesevent.type=health_report

A tray is a serviceable enclosure within a rack-scale system. The leak detection reports apply to liquid-cooled systems whose BMCs expose leak detectors. The following table lists the health report logs by source.

Log TypeSourceDescriptionRationale
health_report_bmc_sensorsBmcSensorsSummarizes the alerts from BMC sensors.Gives one record of how many sensors are in alert, so you can chart and alert on overall sensor health without reading each sensor alert.
health_report_bmc_eventsBmcEventsSummarizes the alerts that BMC events raise, such as an asserted chassis intrusion sensor.Condenses the BMC event stream into a count of active alerts, so that a burst of events shows up as one signal.
health_report_bmc_leak_detectorsBmcLeakDetectorsSummarizes the observations from the leak detectors that the BMC exposes.Reports coolant leaks as the BMC sees them. A leak can damage hardware and create an electrical hazard, so it needs its own signal.
health_report_tray_leak_detectionTrayLeakDetectionSummarizes the leak status of a tray, derived from the leak detector observations.Rolls detector observations up to the tray, which is the unit that you service or remove from use after a leak.
health_report_rack_leak_detectionRackLeakDetectionSummarizes the leak status of a rack.A leak that affects several trays is a rack-level problem that needs a response beyond a single node. This report raises it as its own signal.

Firmware Inventory

The following table lists the firmware inventory log.

Log TypeBodySeverityAttributesRationale
firmware_inventory<component name>: <firmware version>INFOevent.type=firmwareRecords the firmware version of each component that the BMC reports, such as the BMC, the BIOS, and device firmware. It shows nodes that run different versions, confirms that an update took effect, and correlates faults with a firmware release.

Log Attributes

The following table describes the attributes that the logs carry.

AttributeDescriptionRationale
machine_idMachine identifier, which is the same value that the in-band agent reports.Joins the log with in-band data for the same node.
entry_idIdentifier of the Redfish log entry.Traces a log back to its entry on the BMC and detects repeated entries.
service_idIdentifier of the Redfish log service that holds the entry.Shows which BMC log produced the entry.
message_idIdentifier of the event message in a Redfish message registry.Identifies the kind of event, so you can group and filter events without parsing the message text.
event_typeType of the event. Redfish deprecated this property, and it appears when the BMC still reports it.Preserves the event classification from BMCs that still use it.
event_idUnique identifier of the event instance.Separates one occurrence from another and supports deduplication.
event_timestampTime that the event occurred, as the BMC reports it.Orders events by when they happened rather than when the collector received them.
message_argsArguments that the BMC substitutes into the message.Provides the values behind the message text, such as the affected component, in a structured form.
message_severitySeverity of the message in the event.Supports filtering and alerting on severity.
origin_of_conditionLink to the resource that originated the condition that caused the event.Pinpoints the component that caused the event.
log_entry_idIdentifier of the log entry that the BMC created for the event, if it created one.Links an event to the matching entry in the BMC log, so you can cross-reference the two log types.
event_group_idIdentifier that correlates events with the same root cause. Redfish defines a value of 0 as no related events.Groups related events so that one failure does not look like many unrelated problems.
resolutionSuggestion from the BMC on how to resolve the condition that caused the event.Gives you a first action to take without looking up the event code.
event.typeType of record. The value is health_report for health reports and firmware for firmware inventory.Separates health reports and firmware inventory from other logs.