Skip to navigation

Rack Management Service (RMS) Backend v2.2 New

View as MarkdownOpen in Claude

NICo delegates rack-level hardware operations to the Rack Management Service (RMS), a separate service that owns the protocols each device class speaks. NICo decides what should happen to a rack and RMS carries it out against compute trays, NVSwitch trays, and power shelves.

This page explains the shape of that integration: the service boundary, the deployed components, the transports and trust between them, and the RMS APIs NICo depends on. For the settings that turn the integration on, refer to RMS Configuration.

The Challenge

A single NVL rack presents several hardware management protocols at the same time. Compute trays, power shelves, and NVSwitch tray BMCs speak Redfish. NVSwitch trays also speak NVUE REST, the NVOS CLI over SSH, and image transfer over SFTP. A rack-wide firmware update has ordering rules between component classes, device reboots, and partial-failure states. RMS reports these as one outcome rather than as several dozen independent device calls.

Building that into NICo would put per-vendor hardware protocol handling inside the service that also owns tenancy, provisioning, and network isolation. RMS exists so that boundary stays clean: NICo keeps the site-level lifecycle, and one service behind a single gRPC API absorbs the hardware protocol surface.

How the Integration Works

Service Boundary

ConcernOwner
Rack, machine, and tenant lifecycle; inventory of recordNICo
Deciding when a rack enters maintenance and what to applyNICo
Selecting the firmware manifest for a rack profileNICo
Translating a request into Redfish, NVUE, SSH, SFTP, gRPC, and gNMI callsRMS
Per-device ordering, retries, and job aggregationRMS
Downloading firmware artifacts named by the manifestRMS

NICo builds an RMS client only when the site configuration supplies [rms] api_url. Without it, NICo Core still starts, but an RMS-backed Component Manager cannot initialize. Its RPCs return configuration errors.

Deployed Components

NICo and RMS deployment architecture, showing users, the NICo and RMS namespaces, shared platform services, and rack hardware, with the transport and authentication used on each connection

RMS runs as its own Deployment in its own namespace, alongside NICo rather than inside it:

  • rms-api-server runs in the rack-manager namespace and is reached through a ClusterIP Service of the same name. Port 8801 serves the gRPC API and port 8802 serves Prometheus metrics at /metrics. The RMS chart’s ServiceMonitor is disabled by the NICo site values and enabled by setup.sh only with --with-observability. Sites can instead configure an OpenTelemetry Collector to scrape the endpoint. When collectors run as a DaemonSet, shard the target so only one collector scrapes it and duplicate samples are not produced. The RMS API Deployment does not define Kubernetes liveness or readiness probes.
  • Replica count is one. RMS does not yet share state between replicas, so a load-balanced deployment can return inconsistent results.
  • Runtime configuration is a single TOML file the container reads at startup from /etc/rms/config.toml.
  • Persistence uses a database and user separate from NICo’s on the same PostgreSQL cluster, which keeps RMS migrations, permissions, and restore decisions independent of NICo’s.
  • Certificates come from the same cert-manager issuer that signs NICo’s own certificate, which is what lets the two services complete mutual TLS without extra configuration.

Transport and Trust

Credential-bearing connections crossing a trust boundary are authenticated. The mechanism differs by hop:

ConnectionTransportAuthentication
NICo Core to RMSgRPC on port 8801Mutual TLS
RMS to compute tray BMC and HMCRedfish over HTTPSHTTP basic authentication
RMS to power shelf controllerRedfish over HTTPSHTTP basic authentication
RMS to switch NVUE REST APIHTTPS on port 8765HTTP basic authentication and mutual TLS
RMS to switch NVOS CLI and image transferSSH and SFTP on port 22SSH credentials
RMS to switch NMX-CgRPC and gNMIMutual TLS
RMS to firmware artifact hostHTTPS when sending an API key; HTTP permitted only for unauthenticated downloadsOptional artifact API key, set by the manifest
RMS to PostgreSQLPostgreSQL over TCP on port 5432Password from a Kubernetes Secret, TLS required

NICo does not need a dedicated RMS client certificate. The RMS client library discovers NICo’s own SPIFFE certificate mount and presents it to RMS, and because the RMS server certificate is minted from the same issuer, both directions verify. Supplying explicit certificate paths is an override for sites that want different material.

RMS APIs NICo Calls

NICo uses a focused slice of the RMS API. The following table lists calls by workflow; some calls serve more than one workflow:

WorkflowRMS APIs
Rack maintenance firmware upgradeapply_firmware_object, get_job_status
Component Manager firmware update and shelf version listingapply_firmware_object, get_job_status, batch_get_firmware_inventory, list_firmware_objects
Switch system image updateapply_switch_system_image, get_switch_system_image_job_status
Power controlbatch_set_power_state, get_job_status
Switch certificate installationconfigure_switch_certificate, get_configure_switch_certificate_job_status
NVLink fabric configurationconfigure_scale_up_fabric_manager_v2, get_job_status, batch_get_scale_up_fabric_service_status
Machine slot and tray enrichmentbatch_get_node_device_info
Switch password rotation and decommissioningupdate_switch_system_password, batch_reset_switch_factory_default

The RMS compute backend delegates AcPowercycle to CoreComputeTrayManager, which uses NICo’s direct Redfish pool and the endpoint’s BMC credentials. This applies to direct requests (including pre-ingestion) and queued compute maintenance. The call returns command acceptance, with per-device Redfish errors and no RMS job ID; hardware support depends on the device’s Redfish implementation. Native RMS AC cycling is tracked in power-control support. RMS switch and power-shelf backends reject AcPowercycle. GracefulRestart and ForceRestart remain distinct RMS operations.

Queued compute AC cycles have dedicated maintenance phases. For hosts with managed DPUs, maintenance checks the platform before issuing the power command; a failed check retries without issuing the command. After the power command succeeds, Vera Rubin hosts with managed DPUs run ingestion’s onboard NIC sequence: enable, wait at least ten seconds, disable, then wait at least ten seconds. AC cycling re-enables these NICs, so the AC maintenance sequence restores their disabled configuration before completing. Other platforms and hosts without managed DPUs skip this sequence. While the request remains pending, BMC or NIC errors retain the persisted phase for retry without resubmitting an accepted cycle. AC maintenance uses the existing request-replacement behavior; it does not guarantee cleanup if another request replaces it. A failed power command can be retried, including when its response was lost; command acceptance and progress persistence are not atomic. Explicit direct/bypass requests retain direct dispatch and do not run this maintenance cleanup.

Firmware updates, system image updates, certificate installation, and fabric configuration run asynchronously. RMS normally returns a job identifier when it accepts the request, and NICo polls the matching status API until the job reaches a terminal state. Queued and in-progress states are nonterminal.

Component Manager also provides these passive status methods through its RMS backend:

Method purposeRMS APIs
Power statebatch_get_power_state
Installed firmwarebatch_get_firmware_inventory
Firmware manifest comparisoncompare_firmware_object
Tracked firmware jobsget_job_status, get_switch_system_image_job_status (switches)

These passive methods do not submit updates or move a firmware update to its next phase. Firmware job reads attempt to query the job identifiers recorded for each requested device. The shared deadline can prevent some queries, and repeated device entries can repeat them. These reads do not discover other RMS jobs. Neither an empty job list nor a completed job establishes that an entire firmware update finished. A missing or unreadable job does not establish update failure. Installed firmware, firmware manifest comparisons, and job status are independent observations; one does not confirm another.

Switch Update Polling

Poll GetComponentFirmwareStatus with the switch BMC MAC against the nico-api instance that submitted the NVOS job, and avoid overlapping caller polls. These practices do not establish whole-update or installed-firmware completion.

For switches, get_firmware_jobs only observes known work. The updater’s get_firmware_status poll can submit a queued firmware-object update after its NVOS image job completes. Without that polling, the queued phase does not advance. That polling must reach the nico-api instance that submitted the NVOS job. The queued phase exists only in that instance’s memory; restarting it before firmware-object submission loses the phase. A poll after restart or through another instance can report completion from the persisted NVOS job alone. Overlapping get_firmware_status polls can also report completion from the NVOS job alone while the firmware-object job is still running. A poll can retain the earlier job list after another poll submits that phase and removes its in-memory marker.

Firmware-object polling sends the tracked job ID to get_job_status with include_child_job_states=false. NICo requires exactly one response record whose job_id matches that ID and maps its JobExecutionState to queued, in-progress, completed, or failed. Empty, mismatched, duplicate, unspecified, or unrecognized evidence cannot establish completion. Rack maintenance keeps its previous device progress and polls again; ordinary component status reads return unknown with a diagnostic; passive job reads return StatusUnavailable.

A gRPC NOT_FOUND result means the job is absent. Shelf status reads return unknown, switch and compute-tray status reads return failed, rack maintenance retains progress for later polling, and passive job reads return JobNotFound. A job observed in the failed execution state remains a valid passive observation of failure. Switch system-image polling continues to use get_switch_system_image_job_status.

How a Firmware Manifest Reaches RMS

Firmware updates use a standardized firmware manifest. This JSON document names firmware components and the locations of their artifacts. The manifest travels from NICo configuration to RMS in four steps:

  1. A rack profile declares where its manifest lives, through [rack_profiles.<id>.firmware_object] url.
  2. When a rack begins a firmware upgrade, NICo resolves the profile for that rack. A rack profile without a firmware_object source skips the automatic firmware update rather than failing.
  3. NICo fetches the document from its HTTPS URL within the configured timeout and confirms it parses as a JSON object. The body is capped at 16 MiB because the manifest carries metadata, not firmware binaries. NICo does not verify the manifest with a signature or digest.
  4. NICo sends the document body inline to RMS as the config_json field of apply_firmware_object, alongside the rack identifier, the resolved node set, the firmware and hardware types. Automatic profile-driven maintenance has no caller token: rack firmware submits no token and the backend substitutes the NOAUTH value, while the NVOS path sends NOAUTH directly. An explicit maintenance request instead loads and sends its stored artifact access token.

RMS then reads the artifact URLs from the manifest body that NICo forwarded and downloads the artifact payloads itself. The payloads do not pass through NICo. The artifact host must therefore be reachable from the RMS namespace.

Key Insights

  • RMS is a backend, not a dependency of record. NICo remains the inventory owner. RMS is selected per component class, so a site can route compute trays through RMS while another class uses a different backend.
  • The integration is config-gated at both ends. NICo builds no RMS client without [rms] api_url, and RMS accepts no NICo traffic without matching TLS material.
  • Job-based updates. NICo uses the returned job identifiers to follow firmware, image, certificate, and fabric updates until they reach a terminal state. Delegated compute AC cycles return Redfish command acceptance without an RMS job. Direct dispatch does not start a state-controller poller for a pre-ingestion switch. The caller must poll GetComponentFirmwareStatus using its BMC MAC to advance a queued firmware-object phase; passive get_firmware_jobs reads do not advance it.
  • Manifests flow through NICo; artifacts do not. NICo hands RMS the document and RMS fetches the binaries, so artifact reachability is an RMS-side network requirement.
  • Shared PostgreSQL, separate database. RMS persists to the same cluster as NICo under its own database and user, which keeps lifecycle decisions independent.